0C13<br />
Code Type Description and Remedy<br />
0BF5 BUS<br />
Transmission error (CRC error) on the data return<br />
path of the in<strong>com</strong>ing bus interface (IN) of the<br />
indicated device.<br />
Remedy: See Error Code 0BF4 on page 82.<br />
Add_Error_Info: Error location<br />
(Segment . Position).<br />
0BF6 BUS See Error Code 0BF0 on page 82.<br />
Add_Error_Info: Error location<br />
(Segment . Position).<br />
0BF8<br />
0BF9<br />
0BFA<br />
0BFB<br />
0BFC<br />
A multiple error occurred on the indicated device.<br />
It was not possible to find the exact location of the<br />
error. Possible error locations:<br />
– Indicated devices<br />
– The <strong>com</strong>plete bus located prior to the device<br />
– All devices connected to OUT2 of the<br />
indicated device<br />
Remedy: Check the system:<br />
– Shielding of the bus cables (connectors)<br />
– Grounding/equipotential bonding<br />
– Faulty connectors or joints<br />
– Cable breaks<br />
– Voltage dips on the <strong>com</strong>munications power for<br />
remote bus devices<br />
You can view information about the error location<br />
via the PF TEN or CRC TEN menu item (page 28)<br />
("Get_Diag_Info" service (032B hex )).<br />
Add_Error_Info: Error location<br />
(Segment . Position).<br />
See Error Code 0BF0 on page 82, but the error<br />
may be located in several places.<br />
The error may occur on all transmission paths and<br />
devices in the branches located prior to the<br />
indicated device.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
0C10 RB<br />
0C11<br />
0C12<br />
0C13<br />
A device entered in the active configuration and<br />
not marked as switched off is missing from the<br />
connected bus configuration.<br />
Remedy: Compare the bus configuration with the<br />
active configuration. Take the disabled bus<br />
segments into account.<br />
Add_Error_Info: Error location<br />
(Segment . Position).<br />
5277CC01 83