0BF0<br />

Code Type Description and Remedy<br />

0BF0 BUS<br />

0BF1 BUS<br />

0BF2 BUS<br />

0BF3 BUS<br />

0BF4 BUS<br />

The controller board reset all outputs and stopped<br />

data transmission.<br />

The error cause is located in a remote bus device<br />

or a device prior to it, including all branching bus<br />

segments.<br />

It may have been caused by the voltage reset of a<br />

device or a cable break. There may be a fault on<br />

the jumper in the connector for the outgoing<br />

remote or local bus.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Interrupted data transmission at the specified bus<br />

terminal module. The connector for the branching<br />

remote bus branch is not plugged in or the jumper<br />

in the connector for the branching remote bus<br />

branch is faulty.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Interrupted data transmission at the specified bus<br />

terminal module. The connector for the outgoing<br />

remote bus is not plugged in or the jumper in the<br />

connector for the outgoing remote bus is faulty.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Interrupted data transmission at the specified bus<br />

terminal module or in its local bus.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Transmission error (CRC error) on the data<br />

forward path of the in<strong>com</strong>ing bus interface (IN) of<br />

the indicated device.<br />

Remedy: Check the segment:<br />

– Shielding of the bus cables (connectors)<br />

– Grounding/equipotential bonding<br />

– Faulty connectors or joints<br />

– Voltage dips on the <strong>com</strong>munications power for<br />

remote bus devices<br />

– Faulty fiber optic assembly<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

online<strong>com</strong>ponents.<strong>com</strong><br />