0BE0<br />
Code Type Description and Remedy<br />
0BD5 USER An error occurred in the bus segment, which is<br />
connected to the branching branch interface of<br />
the indicated device. The branching interface was<br />
switched off.<br />
Add_Error_Info: Device number of the device<br />
that was switched off.<br />
0BDB BUS<br />
0BDC<br />
0BDD BUS<br />
The process preprocessing task is no longer in<br />
the RUN state. The bus was stopped to prevent<br />
data transmission without preprocessing. Error in<br />
the preprocessing program (e.g.,division by zero)<br />
or preprocessing intentionally stopped by the<br />
user.<br />
A SYSFAIL on the host system generated an<br />
alarm stop on the controller board while it was in<br />
the ACTIVE or RUN state.<br />
(This error message must already be enabled<br />
("Set_Value" service (0750 hex )).<br />
The bus was stopped, as inconsistent data could<br />
otherwise have been transmitted, e.g.,by a byte<br />
access to a 16-bit locked MPM address<br />
(“ page 116).<br />
Remedy: See Error Code 0B8F on page 77.<br />
0BDE USER A synchronization error occurred in bussynchronous<br />
mode.<br />
Remedy: Check the system or increase the cycle<br />
time with the "Set_Value" service or using CMD or<br />
PC WORX software.<br />
0BDF LOOK<br />
FOR<br />
FAIL<br />
A bus error occurred. The controller board has set<br />
data transmission and is searching for the error<br />
location and error cause.<br />
Remedy: Wait for the troubleshooting results.<br />
0BE0 BUS See Error Code E0 on page 49.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
5277CC01 81