0BC3 Code Type Description and Remedy 0BC3 0BC4 0BC5 The protocol chip in a Loop device is too hot. Remedy: Reduce the ambient temperature or provide ventilation for the Loop device. Add_Error_Info: Error location (Segment . Position). The internal current source is overloaded on a Loop device. Remedy: Reduce the number of connected sensors/actuators or check the sensors/actuators for errors. Add_Error_Info: Error location (Segment . Position). The output of the device is overloaded. Remedy: Reduce the number of connected sensors/actuators or check the sensors/actuators for errors. Add_Error_Info: Error location (Segment . Position). 0BD0 USER The controller board could not start up the connected configuration, as no bus configuration is connected. Remedy: Connect the bus configuration. 0BD1 0BD2 EVNT The process data could not be updated within the specified PD cycle time. The controller board indicates this only if it has been activated with the "Set_Value" service (0750 hex ) before. Remedy: Check your system or increase the value set for the PD cycle time using the "Set_Value" service (0750 hex ). The bus warning time has elapsed. No data cycle could be transmitted within the specified bus warning time. Remedy: Check the system or increase the bus warning time with the "Set_Value" service or using CMD or PC WORX software. onlinecomponents.com 0BD4 USER A single bus error occurred. (The controller board indicates this only if this function has been activated before.) 80 5277CC01

0BE0 Code Type Description and Remedy 0BD5 USER An error occurred in the bus segment, which is connected to the branching branch interface of the indicated device. The branching interface was switched off. Add_Error_Info: Device number of the device that was switched off. 0BDB BUS 0BDC 0BDD BUS The process preprocessing task is no longer in the RUN state. The bus was stopped to prevent data transmission without preprocessing. Error in the preprocessing program (e.g.,division by zero) or preprocessing intentionally stopped by the user. A SYSFAIL on the host system generated an alarm stop on the controller board while it was in the ACTIVE or RUN state. (This error message must already be enabled ("Set_Value" service (0750 hex )). The bus was stopped, as inconsistent data could otherwise have been transmitted, e.g.,by a byte access to a 16-bit locked MPM address (“ page 116). Remedy: See Error Code 0B8F on page 77. 0BDE USER A synchronization error occurred in bussynchronous mode. Remedy: Check the system or increase the cycle time with the "Set_Value" service or using CMD or PC WORX software. 0BDF LOOK FOR FAIL A bus error occurred. The controller board has set data transmission and is searching for the error location and error cause. Remedy: Wait for the troubleshooting results. 0BE0 BUS See Error Code E0 on page 49. onlinecomponents.com 5277CC01 81

0BC3<br />

Code Type Description and Remedy<br />

0BC3<br />

0BC4<br />

0BC5<br />

The protocol chip in a Loop device is too hot.<br />

Remedy: Reduce the ambient temperature or<br />

provide ventilation for the Loop device.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

The internal current source is overloaded on a<br />

Loop device.<br />

Remedy: Reduce the number of connected<br />

sensors/actuators or check the sensors/actuators<br />

for errors.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

The output of the device is overloaded.<br />

Remedy: Reduce the number of connected<br />

sensors/actuators or check the sensors/actuators<br />

for errors.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

0BD0 USER The controller board could not start up the<br />

connected configuration, as no bus configuration<br />

is connected.<br />

Remedy: Connect the bus configuration.<br />

0BD1<br />

0BD2 EVNT<br />

The process data could not be updated within the<br />

specified PD cycle time. The controller board<br />

indicates this only if it has been activated with the<br />

"Set_Value" service (0750 hex ) before.<br />

Remedy: Check your system or increase the<br />

value set for the PD cycle time using the<br />

"Set_Value" service (0750 hex ).<br />

The bus warning time has elapsed. No data cycle<br />

could be transmitted within the specified bus<br />

warning time.<br />

Remedy: Check the system or increase the bus<br />

warning time with the "Set_Value" service or<br />

using CMD or PC WORX software.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

0BD4 USER A single bus error occurred. (The controller board<br />

indicates this only if this function has been<br />

activated before.)<br />

80 5277CC01