0BC2<br />

Code Type Description and Remedy<br />

0BB4<br />

0BB5<br />

0BB6<br />

The microprocessor of the indicated device<br />

performed a reset.<br />

Remedy: Check the device.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Deterioration of the transmission quality on the<br />

data forward path at the in<strong>com</strong>ing bus interface<br />

(IN) of the indicated device.<br />

Remedy: Check device and connection.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Deterioration of the transmission quality on the<br />

data return path at the in<strong>com</strong>ing bus interface (IN)<br />

of the indicated device.<br />

Remedy: Check device and connection.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

0BB7 RBUS The specified device indicated a timeout and<br />

reset all outputs, if available. The response is<br />

identical to the response given upon a bus reset.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

Remedy: Reduce the cycle time.<br />

0BC0<br />

Error message for a system coupler.<br />

– The lower-level bus changed to the STOP<br />

state due to a bus error.<br />

– Voltage reset of the system coupler master<br />

part.<br />

Remedy: Read the exact error cause, e.g., using<br />

the "Get_Error_ Info" service (0316 hex ), or read<br />

the diagnostic register or diagnostics using CMD<br />

or PC WORX software.<br />

Add_Error_Info: Error location<br />

(Segment . Position) of the INTERBUS device.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

0BC2<br />

The voltage for sensors is too low on a Loop<br />

device.<br />

Remedy: Reduce the number of connected<br />

devices or reduce the extension of the ring.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />