0A55<br />

Code Type Description and Remedy<br />

0A52 USER You tried to jumper an active device.<br />

Remedy: First switch off the device using<br />

"Control_Active_Configuration" (0713 hex ).<br />

Add_Error_Info: Line number of the<br />

configuration frame.<br />

0A53 USER The maximum permissible number of remote bus<br />

devices was exceeded by the user when using the<br />

"Load_Configuration" service (0307 hex ) or when<br />

reading the connected devices using the<br />

"Create_Configuration" service (0710 hex ).<br />

Remedy: Reduce the number of remote bus<br />

devices to less than 254.<br />

0A54 USER The maximum permissible number of I/O points<br />

was exceeded by the user when using the<br />

"Load_Configuration" service (0307 hex ) or when<br />

automatically reading the connected devices<br />

using the "Create_Configuration" service<br />

(0710 hex ).<br />

Remedy: Reduce the number of I/O points to the<br />

maximum number of digital inputs and outputs for<br />

the input and output data area. Depending on the<br />

type of controller board, you may use up to 8192<br />

I/O points. To obtain the exact number, refer to<br />

the documentation for your controller board.<br />

0A55 USER The configuration data transmitted to the<br />

controller board using the<br />

"Compare_Configuration" service (0317 hex ) does<br />

not correspond to the configuration frame<br />

specified with the Frame_Reference parameter<br />

(“ page 116).<br />

The device number (Segment . Position)<br />

specified by the Add_Error_Info parameter has<br />

been entered differently.<br />

Remedy: The detected bus configuration does<br />

not correspond to the expected bus configuration.<br />

Check the list of transmitted configuration data<br />

against the specified configuration frame.<br />

Add_Error_Info: Line number of the<br />

configuration frame, which does not correspond<br />

to the transmitted configuration data.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

5277CC01 71