0A4B<br />

Code Type Description and Remedy<br />

0A4B USER Error when assigning a process data item. Using<br />

the "Load_PDRL" service (0325 hex ) you assigned<br />

a bit string process data item that exceeds the<br />

byte boundary.<br />

Remedy: A bit string process data item must not<br />

exceed the byte boundary.<br />

Add_Error_Info: Bit position of the incorrectly<br />

assigned bit string process data item in the MPM<br />

(“ page 116).<br />

0A4C USER Error when assigning a process data item. You<br />

assigned an odd byte address.<br />

Remedy: Only assign even byte addresses to<br />

process data with a data consistency of 16, 32 or<br />

64 bits.<br />

Add_Error_Info: PDRL_Index of the incorrect<br />

PDRL entry.<br />

0A50 USER Error when assigning a process data item. You<br />

assigned an output process data description or an<br />

input host address several times.<br />

Remedy: Each output process data description<br />

should only be assigned one host address and<br />

each input host address should only be assigned<br />

one process data description.<br />

Add_Error_Info: PDRL_Index of the incorrect<br />

PDRL entry.<br />

Additional information for system coupler cards<br />

If a large bus configuration (system coupler card and<br />

number of devices > 225, all with 32 bits of DIO) is<br />

read with the "Create_Configuration" service<br />

(0710 hex ), the default I/O data will be stored in<br />

address area 0000 hex to 03FF hex . This causes a<br />

conflict with system coupler address 0380 hex .<br />

Remedy: Assign the system coupler to an address<br />

located after the address area of the default I/O data.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

0A51 USER The controller board did not accept the<br />

Frame_Reference parameter.<br />

Remedy: Values between 1 and 254 are<br />

permitted.<br />