interbus - Onlinecomponents.com
interbus - Onlinecomponents.com
interbus - Onlinecomponents.com
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
0A36<br />
Code Type Description and Remedy<br />
0A36 USER Error when defining a process data item. Using<br />
the "Put_Process_Data_Description_List" service<br />
(0321 hex ) a bit string process data item was<br />
defined, which exceeds the byte boundary.<br />
Remedy: Do not exceed the byte boundaries of<br />
bit string process data (8 bits, maximum).<br />
Add_Error_Info: Index of the process data<br />
description.<br />
0A40 USER Incorrect entry in the process data reference list<br />
(PDRL).<br />
Add_Error_Info: PDRL_Index of the incorrect<br />
PDRL entry.<br />
0A41 USER Incorrect entry in the process data reference list<br />
(PDRL). There is no OUT PD specified as the<br />
target.<br />
Add_Error_Info: PDRL_Index of the incorrect<br />
PDRL entry.<br />
0A42 USER Incorrect entry in the process data reference list<br />
(PDRL). There is no IN PD specified as the<br />
source.<br />
Add_Error_Info: PDRL_Index of the incorrect<br />
PDRL entry.<br />
0A43 USER Incorrect entry in the process data reference list<br />
(PDRL). The specified device number does not<br />
exist.<br />
Add_Error_Info: PDRL_Index of the incorrect<br />
PDRL entry.<br />
0A44 USER Incorrect entry in the process data reference list<br />
(PDRL). You specified a data consistency for a<br />
process data item, which does not correspond to<br />
its length.<br />
Add_Error_Info: PDRL_Index of the incorrect<br />
PDRL entry.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
0A45 USER Incorrect entry in the process data reference list<br />
(PDRL). You specified a value that does not exist<br />
for the PDD_Index parameter.<br />
Add_Error_Info: PDRL_Index of the incorrect<br />
PDRL entry.<br />
68 5277CC01