0A35<br />
Code Type Description and Remedy<br />
0A31 USER The controller board cannot process the<br />
"Put_Process_Data_Description_List" service<br />
(0321 hex ) or the<br />
"Get_Process_Data_Description_List" service<br />
(0323 hex ), as the device number used does not<br />
exist.<br />
Add_Error_Info: Non-existent device number in<br />
the format [RRLL].<br />
RR = Remote bus segment number<br />
LL = Local bus segment number<br />
0A32 USER The controller board could not process the<br />
"Put_Process_Data_Description_List" service<br />
(0321 hex ). An invalid value was specified in a<br />
process data description for the PDD_Index<br />
parameter.<br />
Remedy: Assign values in the range from<br />
0000 hex to 7FFF hex for this parameter (except for<br />
6010 hex and 6011 hex ). Every PDD index must be<br />
assigned only once.<br />
Add_Error_Info: Index of the process data<br />
description.<br />
0A33 USER The process data direction (IN or OUT data) was<br />
defined incorrectly.<br />
Remedy: Use the Data_Direction parameter to<br />
define the data direction for the process data<br />
description:<br />
0C hex for IN PDD, 0D hex for OUT PDD.<br />
Add_Error_Info: Index of the process data<br />
description.<br />
0A34 USER The internal address area of a device was<br />
exceeded when writing to a process data item.<br />
Add_Error_Info: Index of the PD object.<br />
0A35 USER A data type and a data length that do not<br />
correspond were specified when writing to a<br />
process data item.<br />
Add_Error_Info: Index of the process data<br />
description.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
5277CC01 67