0A29<br />

Code Type Description and Remedy<br />

0A29 USER When switching devices on or off using the<br />

"Control_Active_Configuration" service (0713 hex )<br />

you caused inconsistencies between mutually<br />

dependent groups.<br />

Add_Error_Info: Line number of the<br />

configuration frame.<br />

0A2A USER Using the "Control_Active_Configuration" service<br />

(0713 hex ) you caused inconsistencies when<br />

switching mutually dependent devices (active/<br />

inactive).<br />

Add_Error_Info: Line number of the<br />

configuration frame.<br />

0A2B USER Status conflict within a group. You assigned<br />

different statuses to devices belonging to one<br />

group.<br />

Remedy: Always assign the same status to the<br />

devices of one group.<br />

Add_Error_Info: Line number of the<br />

configuration frame.<br />

0A2C USER The specified device number does not exist.<br />

Add_Error_Info: Non-existent device number.<br />

0A2D USER You connected too many PCP devices or you<br />

configured more than the permitted number of<br />

PCP devices.<br />

Remedy: Reduce the number of connected or<br />

configured PCP devices. A maximum of 126 PCP<br />

devices is permitted, depending on the controller<br />

board used and the firmware version.<br />

0A2E USER You have reached the firmware memory limit.<br />

Remedy: Reduce the number of modules<br />

occupying less than 1 word of address space.<br />

Alternatively you can rearrange the modules.<br />

Position those devices that occupy less than 1<br />

word one after the other.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

0A2F USER The controller board could not execute the<br />

"Initiate_Load_Configuration" service (0306 hex ),<br />

as the number of devices was specified as "0".<br />

Remedy: Specify the correct number of devices.<br />

0A30 USER Incorrect entry in the process data description list<br />

(PDDL).<br />

Remedy: Check the PDDL.<br />