interbus - Onlinecomponents.com
interbus - Onlinecomponents.com
interbus - Onlinecomponents.com
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
0A28<br />
Code Type Description and Remedy<br />
0A23 USER You assigned inconsistent device levels.<br />
Remedy: Check the configuration frame<br />
(“ page 116). Do not assign different device<br />
levels in a bus segment.<br />
Add_Error_Info: Line number of the<br />
configuration frame.<br />
0A24 USER Within one local bus segment the connected<br />
devices have different operating states.<br />
Not all devices were switched on or off using the<br />
"Control_Active_Configuration" service<br />
(0713 hex ).<br />
Remedy: Switch all devices in a local bus<br />
segment on or off. Only use the Segment_On or<br />
Segment_Off <strong>com</strong>mands for the service.<br />
Add_Error_Info: Line number of the<br />
configuration frame.<br />
0A25 USER The controller board did not accept the group<br />
definition. You assigned different group numbers<br />
for devices in one bus segment.<br />
Remedy: Always assign the same group number<br />
to all devices in one bus segment.<br />
Add_Error_Info: Line number of the<br />
configuration frame.<br />
0A26 USER The controller board did not accept the definition<br />
of an alternative group. The assigned group<br />
number is invalid.<br />
Add_Error_Info: Line number of the<br />
configuration frame.<br />
0A27 USER The controller board did not accept the definition<br />
of an alternative group. The first device in the<br />
alternative group is not a remote bus device.<br />
Add_Error_Info: Line number of the<br />
configuration frame.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
0A28 USER The controller board could not activate the<br />
specified group. You tried to activate several<br />
alternative groups at the same time.<br />
Add_Error_Info: Line number of the<br />
configuration frame.<br />
5277CC01 65