0954<br />

Code Type Description and Remedy<br />

0954 USER The controller board could not process the service<br />

called last for the RS-232 interface, as an<br />

incorrect value was specified for the<br />

Parameter_Count parameter.<br />

Remedy: Check the call of this service. The<br />

Parameter_Count parameter must correspond to<br />

the number of subsequent words.<br />

0955 USER The message was not read or sent, as the<br />

maximum permissible length of 1024 bytes for the<br />

RS-232 interfaces was exceeded.<br />

Remedy: If the error code occurs after a request,<br />

the message can be read step by step. Some<br />

services can be called several times to read large<br />

data records. Enter an address offset for the<br />

second call.<br />

0956 USER The message could not be read or sent, as when<br />

sending PCP services via the SSGI (Standard<br />

Signal Interface), a PCP service was written to an<br />

SSGI box with an incorrect <strong>com</strong>munication<br />

reference.<br />

Remedy: Only write a PCP service to the SSGI<br />

box, if the box number corresponds to the<br />

<strong>com</strong>munication reference.<br />

0957 USER All remote PCP services of the established<br />

connection were aborted, as the connection was<br />

interrupted due to an abort on a <strong>com</strong>munication<br />

reference.<br />

Remedy: Check the application program and<br />

start it again.<br />

0960 USER The variable ID used for the diagnostic display is<br />

invalid.<br />

Remedy: Set the correct variable ID.<br />

Add_Error_Info: Invalid variable ID.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

0970 USER When <strong>com</strong>municating with the controller board<br />

(e.g., via IB Loader), an error occurred in the<br />

runtime system of the controller board.<br />

Remedy: Provide a waiting time between<br />

services.<br />

09D0 USER You are using a parameterization memory that is<br />

not supported by your firmware.<br />

Remedy: Replace the existing parameterization<br />

memory with a suitable one.<br />