transmission paths between these devices. If devices were<br />

connected to the branch of the device (8.0), they would not<br />

belong to the error location.<br />

Bus Errors E0 - EA<br />

In general, the display indicates the error segment and<br />

position in the event of a bus error.<br />

Error codes 0BE0 hex to 0BEA hex are assigned to bus errors<br />

where the error location or area cannot clearly be defined.<br />

The controller board display only shows the last two<br />

characters, i.e., E0 hex to EA hex .<br />

The error codes are described on page 49 and<br />

onwards.<br />

In the event of bus errors of this type, the bus stops. The<br />

outputs are reset in the LOOK FOR FAIL state. They remain<br />

reset until the bus is restarted and data cycles are transmitted<br />

without errors.<br />

Display reading:<br />

– Line 1 - Error type (BUS)<br />

– Line 2 - Corresponding error code, e.g., E1<br />

The background illumination changes to red.<br />

If an error of this type occurs and the diagnostic<br />

information is read from the diagnostic parameter<br />

registers with the "Read_Value" service, the error<br />

code is mapped to the diagnostic parameter register,<br />

and the value 0000 hex is mapped to the extended<br />

diagnostic parameter register.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

5277CC01 39