Error Localization<br />

If a bus error occurs in the bus system, a diagnostic routine is<br />

automatically started on the controller board. This routine<br />

attempts to start up the bus one segment at a time in order to<br />

locate the error.<br />

During error localization the display shows the message<br />

LOOK FOR FAIL (Figure 16).<br />

The background illumination changes to red.<br />

Figure 16<br />

, E= C I JE? I J= JK I HA C EI JA H<br />

<br />

1 6 - 4 * 7 5<br />

<br />

% $ # " ! % $ # " ! <br />

5 A C A J<br />

5 A C A J<br />

5 A C A J!<br />

Message during error localization<br />

# % % + ! !<br />

On <strong>com</strong>pletion of the diagnostic routine, the detected error is<br />

shown on the display. Possible indications:<br />

– RBUS for a remote bus error<br />

– LBUS for a local bus error<br />

– BUS for a general bus error<br />

– OUT1 for an error at the outgoing interface<br />

– OUT2 for an error at the branching interface<br />

– DEV for an error on the device<br />

With FW 4.35 or later, the station name can be displayed for<br />

priority 1 and 2 located errors by pressing ENTER. However,<br />

this is only possible if the name was previously assigned to<br />

the segment and position using CMD or PC WORX software.<br />