MODE - DIAG<br />

3.2 Unsuccessful Start of ID and Data Cycles<br />

If errors occur during the execution of cycles, which<br />

also lead to a bus error during normal operation, the<br />

background color of the display changes from<br />

green to red.<br />

Case 1: No error was detected.<br />

Line 2: Number of the device up to which startup<br />

was possible.<br />

Line 3: Contents of the IPMS error register. It<br />

contains additional error information, which<br />

can be analyzed by specialists.<br />

Case 2: An error was detected but not located.<br />

Line 2: Bus length in words with which ID cycles<br />

are currently run. As long as errors occur,<br />

the bus is operated with its maximum<br />

length.<br />

Line 3: Contents of the IPMS error register.<br />

Case 3: An error was detected and located.<br />

Line 2: Physical number of the device that<br />

detected a transmission error (plus 4000).<br />

Line 3: Contents of the IPMS error register.<br />

ADBG Menu Item (Auto Debug)<br />

This menu item has the same function as the DEBG menu<br />

item. The only difference is that the functions are executed<br />

automatically.<br />

After selecting this menu item, an attempt is made to start up<br />

the bus. If startup was possible without any errors, data and<br />

ID cycles will start after a waiting time of 1 second.<br />

The LED diagnostic indicators on the devices enable you to<br />

determine to what extent the bus is started up. If all BA LEDs<br />

are active, the bus is running without errors.<br />

As soon as a bus error occurs, an attempt is made to restart<br />

the bus after a waiting time of 1 second. This is repeated until<br />

startup is successful.<br />

The display reading corresponds to that of the DEBG menu<br />

item.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />