interbus - Onlinecomponents.com
interbus - Onlinecomponents.com
interbus - Onlinecomponents.com
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
MODE - DIAG<br />
USER<br />
Line 1 - USER - User Error<br />
Line 2: PARA (diagnostic parameter register)<br />
Line 3: Error code or error location (seg./pos.)<br />
Line 2: BIT (diagnostic status register)<br />
Line 3: Bits set in the status register. Value<br />
displayed in hexadecimal notation and<br />
binary representation by the status<br />
segments.<br />
Line 2: MSG (message code for negative<br />
confirmation). The controller board could<br />
not execute the called service and sent a<br />
negative confirmation consisting of the<br />
message code (MSG), parameter count<br />
(CNT), result (RELT), and Add_Error_Info<br />
(INFO).<br />
Line 3: Number of the service that failed.<br />
Line 2: CNT (parameter count)<br />
Line 3: Number of subsequent data words<br />
belonging to the negative confirmation<br />
Line 2: RELT - Result<br />
The Result parameter consists of two<br />
bytes, which indicate why the request<br />
could not be processed:<br />
Bits 15 - 8: error class, bits 7 - 0: error<br />
code.<br />
Line 3: Error class/error code. (Please refer to the<br />
manuals indicated under MSG for the<br />
meaning of these values)<br />
Line 2: INFO (additional error information)<br />
Line 3: Additional_Code (Please refer to the<br />
manuals indicated under MSG for the<br />
meaning of this value).<br />
Line 1 - PF - Peripheral Fault<br />
Line 2: PARA (diagnostic parameter register)<br />
Line 3: Error code or error location (seg./pos.)<br />
Line 2: BIT (diagnostic status register)<br />
Line 3: Bits set in the status register. Value<br />
displayed in hexadecimal notation and<br />
binary representation by the status<br />
segments.<br />
Line 2: TN - Device number of the faulty device<br />
(seg./pos.)<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
PF<br />
For more detailed information, please refer to the<br />
PCP Manual IBS SYS PCP G4 UM E, Order No.<br />
27 45 16 9 or the Firmware Manual<br />
IBS SYS FW G4 UM E, Order No. 27 45 18 5.<br />
5277CC01 21