SYSFAIL Yellow<br />
STOP ON<br />
TR<br />
UL<br />
US<br />
Green<br />
ON<br />
Green<br />
ON<br />
Green<br />
ON<br />
Error message (system failure)<br />
A runtime error occurred in the IEC<br />
61131 runtime system program.<br />
Transmit/receive<br />
PCP <strong>com</strong>munication in progress.<br />
U (logic)<br />
The supply voltage is present.<br />
Supply voltage<br />
The 24 V supply voltage for the actuators<br />
is present.<br />
LED Indicators on the<br />
IBS ISA FC/486/DX/I-T Controller Board<br />
1 Red FAIL<br />
ON If the IB_RDY_RUN LED is off at the<br />
same time, a controller error has<br />
occurred on the master.<br />
ON If the FC_RDY_RUN LED is off at the<br />
same time, an error has occurred on<br />
the coprocessor board.<br />
ON If the IB_RDY_RUN LED and the<br />
FC_RDY_RUN LED are off at the<br />
same time, a controller error has<br />
occurred on the master and on the<br />
coprocessor board.<br />
ON If the IB_RDY_RUN LED and the<br />
FC_RDY_RUN LED are on at the<br />
same time, an INTERBUS error has<br />
occurred.<br />
OFF No error occurred.<br />
2 Green IB_RDY_RUN<br />
ON<br />
Flashing<br />
INTERBUS is in the RUN state.<br />
INTERBUS is in the READY or<br />
ACTIVE state.<br />
OFF Controller error on the master.<br />
3 Green UL<br />
ON<br />
OFF<br />
Field Controller is supplied with<br />
voltage.<br />
No voltage at the Field Controller.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
4 Green FC_RDY_RUN<br />
ON The program is being processed.<br />
Flashing The IEC 61131 runtime system is in<br />
the READY state (coprocessor has<br />
been started up).<br />
OFF Coprocessor has not been started up.<br />
Error on the coprocessor board.<br />