202F Code Type Description and Remedy 202F The maximum number of parameters was exceeded for a service in an SVC file. Remedy: Check the SVC file and reduce the number of parameters. Add_Error_Info: Line number with incorrect entry. 2030 A negative service confirmation was received. 2111* FC Battery supply has failed. The date and time of the realtime clock as well as the retain data may be lost. Remedy: Replace the battery with a new 3.6 V AA lithium battery. 2112* FC The IP address has not yet been parameterized or has the value "0.0.0.0". This warning is always issued for new devices. Remedy: Parameterize the IP address. 2113* FC An error occurred when transmitting configuration data from PC WORX (e.g., connection loss, voltage failure). Remedy: Repeat data transmission. 2211* FC Stack overflow in the task of the IEC 61131 runtime system. Remedy: Increase the stack. 2212* FC Memory exceeded in an array of the IEC 61131 runtime system. Remedy: Check access to the array and increase the size of the array, if necessary. 2214* FC Division by zero in the task of the IEC 61131 runtime system. Remedy: Remove error in the program. onlinecomponents.com 2216* FC Value range exceeded in the task of the IEC 61131 runtime system. Remedy: Remove error in the program. 2217* FC Watchdog released in the task of the IEC 61131 runtime system. Remedy: Remove error in the program. 106 5277CC01

8040 Code Type Description and Remedy 2218* FC Runtime is too long in the task of the IEC 61131 runtime system. Remedy: Remove error in the program. 2219 You called a function block, which does not exist in the firmware or in the IEC 61131 runtime system. 221A 221B 221C 221D*FC One program in the IEC 61131 runtime system was stopped from the program. An unexpected breakpoint occurred. An internal exception occurred. String error. Remedy: Remove error in the program. 221E* FC – Division by zero in the task of the IEC 61131 runtime system. – Watchdog released in the task of the IEC 61131 runtime system. – Execution time is too long. Remedy: Remove error in the program. 2410 to 242B 26xx 6342 Bus error indication Fatal error. For more detailed information, please refer to the IBS SYS FW G4 UM E Firmware Manual, Order No. 27 45 18 5, Revision C or later. An exception occurred at the processor. The loworder byte contains the vector number of the exception. The controller board has detected an error in the connected bus system during INTERBUS operation. The bus cannot be operated any longer. The controller board is searching for the error location. Remedy: Read the error cause using the "Get_Error_Info" service (0316 hex ) or use the diagnostics in the CMD software. onlinecomponents.com 8040 The specified device is indicating a single channel error. Remedy: Check the channel of the specified device. Add_Error_Info: Error location (Segment . Position). 5277CC01 107

202F<br />

Code Type Description and Remedy<br />

202F<br />

The maximum number of parameters was<br />

exceeded for a service in an SVC file.<br />

Remedy: Check the SVC file and reduce the<br />

number of parameters.<br />

Add_Error_Info: Line number with incorrect<br />

entry.<br />

2030 A negative service confirmation was received.<br />

2111* FC Battery supply has failed. The date and time of the<br />

realtime clock as well as the retain data may be<br />

lost.<br />

Remedy: Replace the battery with a new 3.6 V<br />

AA lithium battery.<br />

2112* FC The IP address has not yet been parameterized or<br />

has the value "0.0.0.0". This warning is always<br />

issued for new devices.<br />

Remedy: Parameterize the IP address.<br />

2113* FC An error occurred when transmitting configuration<br />

data from PC WORX (e.g., connection loss,<br />

voltage failure).<br />

Remedy: Repeat data transmission.<br />

2211* FC Stack overflow in the task of the IEC 61131<br />

runtime system.<br />

Remedy: Increase the stack.<br />

2212* FC Memory exceeded in an array of the IEC 61131<br />

runtime system.<br />

Remedy: Check access to the array and increase<br />

the size of the array, if necessary.<br />

2214* FC Division by zero in the task of the IEC 61131<br />

runtime system.<br />

Remedy: Remove error in the program.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

2216* FC Value range exceeded in the task of the IEC<br />

61131 runtime system.<br />

Remedy: Remove error in the program.<br />

2217* FC Watchdog released in the task of the IEC 61131<br />

runtime system.<br />

Remedy: Remove error in the program.<br />

106 5277CC01