Code Type Description and Remedy<br />
1057 The firmware download was aborted. The<br />
program initiated a restart.<br />
Remedy: Repeat the firmware download.<br />
1101 CTRL Host adaptation error - error on the controller<br />
board.<br />
Remedy: Replace the controller board.<br />
1210 There is a device with faulty firmware in the<br />
INTERBUS ring.<br />
Remedy: Replace the device.<br />
Add_Error_Info: Number of faulty devices.<br />
1211 A slave number was set that is not permitted<br />
(permitted: 0 or 1) or there is a hardware fault.<br />
Remedy: Enter the correct slave number (0 or 1)<br />
or replace the device.<br />
Add_Error_Info: Incorrect slave number.<br />
1212 There is a device with an incorrect protocol chip in<br />
the INTERBUS ring. Only devices with protocol<br />
chip SUPI 3 (or later) are permitted.<br />
1213 1. Data lengths have been used that are not<br />
permitted in microprocessor mode (e.g., zero<br />
words).<br />
Remedy: Remove the external voltage supply of<br />
the system coupler briefly to initialize the slave<br />
part again.<br />
2. The slave part of the system coupler does not<br />
have the correct ID code.<br />
Remedy: Enter the correct ID code.<br />
1217 The protocol chip has been initialized more than<br />
once. (The SUPI 3 protocol chip can only be<br />
initialized once if the NOT-READY ID code is<br />
present in the hardware. This does not apply to<br />
other ID codes.)<br />
Remedy: Ensure that the protocol chip is<br />
initialized only once.<br />
Disconnect the protocol chip from the supply and<br />
then try again.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />