Code Type Description and Remedy<br />
1012 CTRL – There is an error in the firmware.<br />
– The download of the new firmware failed<br />
during the firmware update.<br />
– A hardware fault has occurred.<br />
Remedy: Reload the firmware. If the error<br />
message is still generated, a hardware fault has<br />
occurred. Replace the controller board.<br />
1013 CTRL A firmware error occurred. (See Error Code<br />
1012.)<br />
1019<br />
101A<br />
101B<br />
101C<br />
101D<br />
101E<br />
CTRL MPM manager error - error on the controller<br />
board.<br />
Remedy: Replace the controller board.<br />
1020 CTRL<br />
1021<br />
1022<br />
1023<br />
1024<br />
1025<br />
1030 CTRL<br />
1031<br />
1032<br />
1033<br />
1034<br />
1035<br />
1036<br />
1051 CTRL<br />
1052<br />
1053<br />
1054<br />
1055<br />
Parameterization memory error on the controller<br />
board.<br />
Remedy: Replace the parameterization memory<br />
or controller board.<br />
Power on selftest error - hardware fault on the<br />
controller board.<br />
Possible cause: The PLC is running when the<br />
controller board is reset.<br />
Remedy:<br />
– First stop the PLC and then reset the<br />
controller board.<br />
– Replace the controller board.<br />
RS-232 error - error on the controller board.<br />
Remedy: Replace the controller board.<br />
online<strong>com</strong>ponents.<strong>com</strong><br />
1056 The firmware download was aborted. Timeout in<br />
the transmission protocol or at the RS-232/V24<br />
interface.<br />
Remedy: Check the RS-232/V24 connection and<br />
restart transmission.<br />