1011<br />

Code Type Description and Remedy<br />

0DD8 OUT2<br />

0DD9<br />

0DDA<br />

0DDB<br />

The local bus connected to the indicated bus<br />

terminal module consists of more local bus<br />

devices than were entered in the active<br />

configuration. This may also apply to INTERBUS<br />

cables to which no device is connected.<br />

Add_Error_Info: Error location<br />

(Segment . Position).<br />

0DDC OUT2 The device connected to the branching bus<br />

0DDD interface (OUT2) of the indicated device is<br />

0DDE unknown (invalid ID code).<br />

0DDF Add_Error_Info: Error location<br />

(Segment . Position).<br />

0Fxx CTRL<br />

0FA4 CTRL<br />

0FC3 CTRL<br />

System error on the controller board (hardware or<br />

firmware error).<br />

Remedy: Reload the firmware. If the error<br />

message is still generated, a hardware fault has<br />

occurred. Replace the controller board.<br />

Checksum error on the parameterization memory.<br />

Writing the parameterization memory was<br />

aborted.<br />

Remedy: Format the parameterization memory<br />

using firmware Version ˜ 4.12.<br />

In<strong>com</strong>patibility with the PLC diagnostic block<br />

when acknowledging peripheral faults (PF)<br />

automatically using firmware Version ˆ 4.15.<br />

Remedy: Reload the firmware. If the error<br />

message is still generated, a hardware fault has<br />

occurred. Replace the controller board.<br />

1010 CTRL Firmware error on the controller board.<br />

Possible causes: There is no CPU in the rack or<br />

the CPU is in the RUN state, even though the<br />

controller board is in test mode.<br />

Remedy: Operate the controller board in a<br />

system with CPU or place the CPU in the STOP<br />

state, if the controller board is in test mode.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

1011 CTRL Hardware fault on the controller board.<br />

Remedy: Replace the controller board.<br />