FLM BK DN M12 DI8 M12 - Onlinecomponents.com

FLM BK DN M12 DI8 M12 - Onlinecomponents.com FLM BK DN M12 DI8 M12 - Onlinecomponents.com

onlinecomponents.com
from onlinecomponents.com More from this publisher
06.05.2014 Views

FLM BK DN M12 DI8 M12 Fieldline Modular Bus Coupler for DeviceNet With 8 Digital Inputs Data Sheet Function 01/2005 This data sheet is only valid in association with the FLS FLM SYS INST UM E (Order No. 26 98 97 3) and FLS FLM DN SYS PRO UM E (Order No. 26 99 082) user manuals. The device connects a Fieldline modular station to DeviceNet and is also used to acquire digital signals. Fieldline Features – Connection to DeviceNet using M12 connectors (A-encoded) – Opens the Fieldline modular local bus using M12 connectors (B-encoded) – Connection of up to 16 local bus I/O devices – 500 kBaud in the local bus – Connection of digital sensors to M12 connectors (A-encoded) – Flexible voltage supply concept – LED diagnostic and status indicators for bus operation and voltage supply – IP65/IP67 protection – Short-circuit and overload protection of the sensor supply DeviceNet Features – I/O peer-to-peer communication – Eplicit messages – Consistent configuration – Faulted node recovery – Automatic baud rate detection (125 kBaud, 250 kBaud, 500 kBaud) – I/O slave messages with the following transmission modes: Polling, cyclic transmission, change-of-state (COS), bit strobing – Configuration via rotary encoding switch, EDS files as well as tools – Certified acc. to ODVA onlinecomponents.com Figure 1 % = FLM BK DN M12 DI8 M12 7111_en_00 1

<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Fieldline Modular Bus Coupler for<br />

DeviceNet With 8 Digital Inputs<br />

Data Sheet<br />

Function<br />

01/2005<br />

This data sheet is only valid in<br />

association with the<br />

FLS <strong>FLM</strong> SYS INST UM E<br />

(Order No. 26 98 97 3) and<br />

FLS <strong>FLM</strong> <strong>DN</strong> SYS PRO UM E<br />

(Order No. 26 99 082) user manuals.<br />

The device connects a Fieldline modular station<br />

to DeviceNet and is also used to acquire digital<br />

signals.<br />

Fieldline Features<br />

– Connection to DeviceNet using <strong>M12</strong> connectors<br />

(A-encoded)<br />

– Opens the Fieldline modular local bus using<br />

<strong>M12</strong> connectors (B-encoded)<br />

– Connection of up to 16 local bus<br />

I/O devices<br />

– 500 kBaud in the local bus<br />

– Connection of digital sensors to <strong>M12</strong> connectors<br />

(A-encoded)<br />

– Flexible voltage supply concept<br />

– LED diagnostic and status indicators for<br />

bus operation and voltage supply<br />

– IP65/IP67 protection<br />

– Short-circuit and overload protection of the<br />

sensor supply<br />

DeviceNet Features<br />

– I/O peer-to-peer <strong>com</strong>munication<br />

– Eplicit messages<br />

– Consistent configuration<br />

– Faulted node recovery<br />

– Automatic baud rate detection<br />

(125 kBaud, 250 kBaud, 500 kBaud)<br />

– I/O slave messages with the following transmission<br />

modes:<br />

Polling, cyclic transmission,<br />

change-of-state (COS), bit strobing<br />

– Configuration via rotary encoding switch,<br />

EDS files as well as tools<br />

– Certified acc. to ODVA<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

Figure 1<br />

% = <br />

<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

7111_en_00 1


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Pin Assignment<br />

* 7 5 1<br />

* 7 5 7 6<br />

7 5<br />

1<br />

Figure 2<br />

* 7 5 7 <br />

1<br />

7 6<br />

1<br />

7 5<br />

* , <br />

7 5<br />

5 *<br />

5 4 7 <br />

. <br />

-<br />

,<br />

"<br />

7 6 * 7 6<br />

$<br />

'<br />

&<br />

: <br />

<br />

+<br />

"<br />

*<br />

) $<br />

' &<br />

7<br />

: <br />

5 7 5<br />

7 6<br />

1 1<br />

1! 1"<br />

1# 1$<br />

1% 1&<br />

Connections of the device<br />

<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

1 > EI 1 &<br />

% ) <br />

Des.<br />

FE<br />

BUS IN<br />

BUS OUT<br />

LB OUT<br />

U LS IN<br />

Meaning<br />

Functional earth ground<br />

DeviceNet IN<br />

DeviceNet OUT<br />

Local bus OUT (<strong>FLM</strong> local bus)<br />

Power supply IN<br />

(logic and sensor supply)<br />

U LS OUT Voltage supply OUT (logic and<br />

sensor supply) for additional devices<br />

IN1 to IN8 Inputs 1 to 8<br />

In general, the maximum current load<br />

of 4 A per contact must not be exceeded.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

2 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Pin Assignment DeviceNet<br />

Pin Assignment of the Local Bus<br />

* 7 5 1<br />

* 7 5 7 6<br />

* 7 6<br />

Figure 3<br />

DeviceNet pin assignment<br />

(<strong>M12</strong> A-encoded)<br />

Pin IN OUT<br />

1 CAN_SHLD CAN_SHLD<br />

2 V+ V+<br />

3 V– V–<br />

4 CAN_High CAN_High<br />

5 CAN_Low CAN_Low<br />

$ $ " ! ) "<br />

The thread and, if required, pin 1 are<br />

used for shielding.<br />

The shield is connected to FE in the<br />

device.<br />

For information on bus cables, please<br />

refer to the<br />

FLS <strong>FLM</strong> <strong>DN</strong> SYS PRO UM E<br />

user manual<br />

Figure 4<br />

Pin LB OUT<br />

1 DO<br />

2 DO<br />

3 DI<br />

4 DI<br />

5 GND<br />

% & ) #<br />

Pin assignment of the local bus<br />

(LB OUT) (<strong>M12</strong> B-encoded)<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

7111_en_00 3


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Pin Assignment of the Voltage Supply U LS Pin Assignment of the Inputs<br />

1<br />

7 6<br />

% ) #<br />

$ $ # ) $<br />

Figure 5 Pin assignment U LS Figure 6 Pin assignment of the inputs<br />

* The 24 V <strong>com</strong>munications power supply U L<br />

is only used for test purposes. For the operation<br />

of the DeviceNet network, the <strong>com</strong>munications<br />

power supply V+/V– must be<br />

fed from the bus cable.<br />

Pin IN OUT<br />

1 U L +24 V U L +24 V<br />

2 U S GND U S GND<br />

3 U L GND U L GND<br />

4 U S +24 V U S +24 V<br />

Voltages U L and U S at female connector<br />

U LS OUT can each only carry<br />

a maximum current of 2 A.<br />

Assignment of the Input Sockets<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

For the following <strong>FLM</strong> local bus devices<br />

it is absolutely necessary to feed<br />

U LS .<br />

Pin<br />

Input Socket<br />

1 U S +24 V<br />

2 See Figure 7<br />

3 GND<br />

4 Input<br />

5 FE<br />

Figure 7<br />

1 N<br />

<br />

"<br />

" 8<br />

#<br />

!<br />

1 N <br />

$ ' # " * #<br />

Assignment of the input socket<br />

Two input signals can be connected<br />

to each input socket.<br />

4 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Local Diagnostic and Status Indicators<br />

7 <br />

5<br />

7 5<br />

Figure 8<br />

* 7 5<br />

1<br />

7 6<br />

1<br />

7 5<br />

* , <br />

7 <br />

5<br />

,<br />

-<br />

+<br />

*<br />

)<br />

7 5<br />

.<br />

<br />

'<br />

&<br />

N <br />

<br />

' &<br />

N <br />

5 *<br />

4 7 <br />

"<br />

$<br />

"<br />

$<br />

1 1<br />

1! 1"<br />

1# 1$<br />

1% 1&<br />

7 6<br />

7 5<br />

5<br />

: :<br />

: :<br />

: :<br />

: :<br />

% ) !<br />

4 7 <br />

Diagnostic and status indicators of<br />

the <strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Rotary Encoding Switches<br />

Use the rotary encoding switches X10 and X1 to<br />

– Set the device ID and<br />

– Set the baud rate manually, if required<br />

The valid value range for the device ID is between<br />

0 dec and 63 dec . A <strong>com</strong>munication fault is<br />

triggered for all values outside this value range.<br />

For information on setting the device<br />

ID and setting the baud rate manually,<br />

please refer to page 14 and<br />

page 15.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

Des. Color Meaning<br />

UL Green LED Communications power<br />

ON:<br />

Communications power present.<br />

OFF:<br />

Communications power too low.<br />

7111_en_00 5


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Des. Color Meaning<br />

NS Green/red LED Network status<br />

Green ON: Device is online, connection has been reestablished.<br />

Green, flashing: Device is online, no connection has been reestablished.<br />

Red ON: Critical connection error<br />

Red flashing: Connection timeout<br />

Flashing red/ Network access error<br />

green<br />

OFF:<br />

Missing device supply (In this state the UL LED is also off because of<br />

the missing 24 V <strong>com</strong>munications power.) or device is offline.<br />

MS LED<br />

Device status<br />

Green/red<br />

Green ON: Device ready to operate<br />

Green, OFF Voltage not present.<br />

Green, flashing: Standby or faulty configuration<br />

Red ON: A critical error is present.<br />

Red flashing: A minor error is present.<br />

Flashing red/ Selftest<br />

green<br />

RUN LED<br />

Status of local bus <strong>com</strong>munication<br />

green/red/yellow<br />

Green ON Local bus is running data cycles.<br />

Green, flashing: I/O error present.<br />

1 Hz<br />

Red ON: Local bus stopped.<br />

Red flashing: Local bus diagnostics is running (troubleshooting).<br />

1 Hz<br />

ON yellow After power up, the local bus is connected with the bus coupler. However,<br />

it does not run any data cycles yet.<br />

Green/yellow Preprogrammed error values are written to the outputs.<br />

Flashing: 1 Hz<br />

Red/yellow There are differences between specified and current configuration.<br />

Flashing: 1 Hz<br />

OFF:<br />

Voltage not present.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

6 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Des. Color Meaning<br />

US Green/red LED Voltage supply for inputs IN1 to IN8<br />

Green ON: Voltage supply present.<br />

Red ON: Overload or voltage supply too low.<br />

OFF:<br />

Voltage supply not present.<br />

XX Yellow LED Status indicators for the inputs<br />

ON:<br />

Input active<br />

OFF:<br />

Input not active<br />

During manual baud rate setting as well as autoconfiguration of the local bus, the RUN<br />

LED only has one sinlge meaning, see page 15 and page 16.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

7111_en_00 7


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Internal Circuit Diagram<br />

Key:<br />

* 7 5 1 <br />

8 8 <br />

* 7 5 7 6<br />

8 8 <br />

7 5<br />

1<br />

Figure 9<br />

# 8<br />

" 8<br />

# 8<br />

" 8<br />

8 8 <br />

, *<br />

+<br />

&<br />

<br />

<br />

<br />

<br />

* 7 6<br />

7 5<br />

7 6<br />

% ) %<br />

Internal wiring of the connection<br />

points<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

, <br />

*<br />

Functional earth ground<br />

Optocoupler<br />

Protocol chip<br />

Local bus/protocol unit<br />

Power supply unit with electrical<br />

isolation<br />

Input<br />

LED<br />

Electrically isolated area<br />

For information on electrically<br />

isolated areas, please refer to<br />

page 20.<br />

8 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Connection Example<br />

Figure 10<br />

Typical sensor connections<br />

Connection Notes<br />

1 1<br />

1! 1"<br />

Meet noise immunity requirements<br />

Connect FE using a mounting screw<br />

or a cable connection to the FE connection<br />

latch (when mounting on a<br />

non-conductive surface).<br />

Ensure degree of protection<br />

To ensure IP65/IP67 protection, cover<br />

unused sockets with protective<br />

caps.<br />

$ ' # " ) &<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

Avoid damage to the electronics<br />

Make sure you only supply the sensors<br />

with the voltage U S provided at<br />

the connection points.<br />

" 8<br />

" 8<br />

1 <br />

1 !<br />

1<br />

1 "<br />

Avoid polarity reversal<br />

Avoid polarity reversal of the supply<br />

voltages U L and U S in order to prevent<br />

damage to the device.<br />

Observe connection point assignment<br />

When connecting the sensors, observe<br />

the assignment of the connection<br />

points to the DeviceNet<br />

IN process data.<br />

7111_en_00 9


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Configuration Data<br />

The configuration data depend on the connected local bus devices.<br />

Input address area<br />

(produced process data)<br />

Output address area<br />

(consumed process data)<br />

ID code<br />

Vendor code<br />

2 bytes for status information of the bus coupler<br />

+ 1 byte for digital inputs of the bus coupler<br />

+ n byte for input data of the connected local bus devices<br />

1001 dec<br />

562 dec<br />

n bytes for input data of the connected local bus devices<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

10 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

I/O Mapping<br />

The memory image maps the status bit that - per<br />

default - is contained in the generated data. In<br />

addition to the status word, input data for digital<br />

and analog input devices as well as function<br />

modules can be contained in the input memory<br />

image.<br />

The control byte that is not contained as per default<br />

is mapped in the output memory image. In<br />

addition to the control byte, the output memory<br />

image can contain output data for digital and analog<br />

output devices.<br />

During I/O mapping the order is determined by<br />

the type and the position of the I/O device. The<br />

devices next to the bus coupler are mapped first.<br />

The digital points are mapped first. Then the analog<br />

channels and function modules are<br />

mapped, independent of their physical position<br />

in the station. The analog channels are mapped<br />

in front of the function data words.<br />

Function modules or modules with PCP are not<br />

supported by FW.101.<br />

If the generated data contain diagnostic<br />

status data, i.e. the status<br />

word, this data type appears in the input<br />

image in front of the digital and<br />

analog input data. If the received data<br />

contain the <strong>com</strong>mand byte, the output<br />

image appears in front of the digital<br />

and analog output data.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

If the overall number of digital points of the same<br />

image is not 8, unused bits are present between<br />

the digital and the analog (or functional) data<br />

area.<br />

The start of analog data on an even or<br />

uneven byte depends on the I/O data<br />

that are connected to the bus coupler.<br />

In the event of a start on an uneven<br />

byte, analog data in the master scanner<br />

might <strong>com</strong>prise two words. If the<br />

analog data are to begin on an even<br />

byte, the optional I/O filling function<br />

"Pad I/O" can be enabled. In this way,<br />

analog data and functional data are<br />

beginning on an even-byte limit. This<br />

function can be enabled by an EDS<br />

file or by sending an explicit message.<br />

7111_en_00 11


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Example I/O Data Table (Memory Image)<br />

The following table shows an example memory<br />

image for mixed input/output device configurations.<br />

The entire amount of input bytes (including the<br />

status word) is 14. The entire amount of output<br />

bytes is 10. The example consists of the following<br />

I/O devices:<br />

– 1 <strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>DI8</strong> with 8 input data bits<br />

– 1 <strong>FLM</strong> DIO 4/4 with 4 input data bits and 4<br />

output data bits<br />

– 1 <strong>FLM</strong> AO4 with 8 bytes (4 words)<br />

– 1 <strong>FLM</strong> DO8 with 1 byte<br />

– 1 <strong>FLM</strong> <strong>DI8</strong> with 1 byte<br />

– 1 <strong>FLM</strong> AI4 with 8 bytes (4 words)<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

12 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Byte 0<br />

Byte 1<br />

Byte 2<br />

Byte 3<br />

Byte 4<br />

Byte 5<br />

Byte 6<br />

Byte 7<br />

Byte 8<br />

Byte 9<br />

Byte 10<br />

Byte 11<br />

Byte 12<br />

Byte 13<br />

Input Data<br />

Output Data<br />

Bit 7


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Diagnostic Data<br />

For more information on the diagnostic<br />

data of the <strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong><br />

<strong>M12</strong>, please refer to the<br />

FLS <strong>FLM</strong> <strong>DN</strong> SYS PRO UM E user<br />

manual.<br />

Setting the Device ID<br />

You must set the device ID directly after<br />

installation and before connecting<br />

the supply voltages.<br />

The device ID is set in the range from 0 dec to<br />

63 dec using the two rotary encoding switches<br />

X10 and X1. A <strong>com</strong>munication fault is triggered<br />

for all values outside this value range.<br />

The device ID set is read upon system startup<br />

and accepted in the device settings. Changing<br />

the switch positions during operation has no effect<br />

on the address settings. Only a system restart<br />

will change the address settings.<br />

Dynamic address changing via DeviceNet is<br />

not supported.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

14 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Setting the Baud Rate Manually<br />

The baud rate is set automatically. If there is no <strong>com</strong>munication between the bus and the<br />

device you must set the baud rate manually.<br />

The baud rate is stored in the non-volatile memory<br />

of the device and read upon system startup.<br />

Changing the baud rate manually during operation<br />

only takes effect upon the next system initialization<br />

(done by the DeviceNet master or<br />

by switching the device off and on again).<br />

To set the baud rate, proceed as follows:<br />

• Select the desired setting using the X1 rotary<br />

encoding switch:<br />

0: 125 kbaud<br />

1: 250 kbaud<br />

2: 500 kbaud<br />

3: Automatic baud rate recognition<br />

A: Setting the baud rate using the software<br />

• Set the X10 rotary encoding switch to position<br />

"D".<br />

• Wait for five seconds.<br />

If the switch position is not changed within<br />

these five seconds the value of the X1 rotary<br />

encoding switch is directly latched in a<br />

buffer.<br />

The RUN LED starts to flash red and then remains<br />

red.<br />

• Set the X10 rotary encoding switch to position<br />

"E".<br />

• Wait for five seconds.<br />

The RUN LED flashes yellow and then its<br />

yellow light indicates valid data transmission<br />

into the non-volatile memory.<br />

The baud rate is programmed.<br />

• Set the X10 rotary encoding switch to position<br />

"F".<br />

• Wait for five seconds.<br />

The RUN LED flashes green and then its<br />

green light indicates the successful termination<br />

of the programming process.<br />

You can stop the programming procedure at any<br />

time by setting the X10 rotary encoding switch to<br />

position "F".<br />

The programming mode is automatically<br />

stopped after ten minutes, if the rotary encoding<br />

switch positions are not changed during this<br />

time. In this case the device will not store any<br />

data.<br />

Set the original device ID again.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

The order of settings for the X10 rotary encoding switch during programming can be remembered<br />

easily as you can see here: "D" like "Do", "E" like "Enter", "F" like "Finished"<br />

7111_en_00 15


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Autoconfiguration of the Local Bus<br />

Besides setting the baud rate and the address,<br />

the following settings at the rotary encoding<br />

switch are possible:<br />

• You can stop the configuration procedure at<br />

any time by setting the X10 rotary encoding<br />

switch to position "F".<br />

X1 = B<br />

X1 = C<br />

Read localbus<br />

Clear: All settings are<br />

set back to default upon delivery<br />

The local bus configuration is stored in the nonvolatile<br />

memory of the device is stored and the<br />

system start is read out and <strong>com</strong>pared to the real<br />

configuration.<br />

For autoconfiguration, proceed as follows :<br />

• Select the autoconfiguration using the X1 rotary<br />

encoding switch:<br />

X1 = Read B localbus (autoconfiguration)<br />

• Set the X10 rotary encoding switch to position<br />

"D".<br />

• Wait for five seconds.<br />

The RUN LED starts to flash red and then remains<br />

red.<br />

• Set the X10 rotary encoding switch to position<br />

"E".<br />

• Wait for five seconds.<br />

The green RUN LED flashes yellow and then its<br />

yellow light indicates valid data transmission into<br />

the non-volatile memory.<br />

• Set the X10 rotary encoding switch to position<br />

"F".<br />

• Wait for five seconds.<br />

The RUN LED flashes green and then its green<br />

light indicates the successful termination of the<br />

configuration process.<br />

Set the original device ID again.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

16 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Technical Data<br />

Device Dimensions<br />

% <br />

% # $ <br />

$ & <br />

$ $ " <br />

! <br />

<br />

% & <br />

% & <br />

General Data<br />

Order Designation<br />

<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Order No. 27 36 34 3<br />

Housing dimensions (width x height x depth) 70 mm x 178 mm x 49.3 mm<br />

Weight<br />

290 g, approximately<br />

Type of sensor connection<br />

2, 3 or 4-wire technology<br />

Permissible temperature (operation)<br />

-25°C to +60°C<br />

Permissible temperature (storage/transport) -25°C to +85°C<br />

Permissible humidity (storage/transport) 95%<br />

For a short period, slight condensation may appear on the housing.<br />

% ) $<br />

Permissible air pressure (operation)<br />

80 kPa to 106 kPa<br />

(up to 2,000 m above sea level)<br />

Permissible air pressure (storage/transport) 70 kPa to 106 kPa<br />

(up to 3,000 m above sea level)<br />

Degree of protection IP65/IP67 according to IEC 60529<br />

Class of protection Class 3 according to VDE 0106, IEC 60536<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

" <br />

# % # <br />

" ' ! <br />

' " <br />

7111_en_00 17


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Mechanical Requirements<br />

Vibration test<br />

5g load in each space direction<br />

Sinusoidal vibrations according to EN 60068-2-6<br />

Shock test according to EN 60068-2-27 30g load, half sinusoidal wave positive and<br />

negative in each space direction<br />

For additional information on mechanical requirements and ambient conditions, please<br />

contact Phoenix Contact.<br />

Power Supply<br />

Nominal value<br />

Range<br />

Current consumption at V+ at 24 V DC<br />

Current consumption at U S at 24 V DC<br />

24 V DC<br />

11 V DC to 30 V DC<br />

65 mA, typical (100 mA, maximum)<br />

10 mA + sensor current, typical<br />

(700 mA, maximum)<br />

Digital Inputs<br />

Number 8<br />

Input design According to IEC 61131-2 type 1<br />

Definition of switching thresholds<br />

Maximum low-level voltage<br />

Minimum high-level voltage<br />

U Lmax < 5 V<br />

U Hmin > 11 V<br />

Nominal input voltage<br />

24 V DC<br />

Range<br />

-30 V DC < U IN < + 30 V DC<br />

Nominal input current<br />

5 mA<br />

Current flow<br />

Linear in the range 1 V < U IN < 30 V<br />

Delay time<br />

t ON = 3.1 ms, typical<br />

t OFF = 4.1 ms, typical<br />

Permissible cable length to the sensor<br />

< 30 m<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

18 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Input Characteristic Curve<br />

Input Voltage (V)<br />

Sensor Supply<br />

Minimum sensor voltage<br />

Nominal current per channel<br />

Nominal current per device<br />

Overload protection<br />

Short-circuit protection<br />

Typical Input Current (mA)<br />

-30 < U IN < 0.7 0<br />

3 0.5<br />

6 1.0<br />

9 1.6<br />

12 2.3<br />

15 3.0<br />

18 3.8<br />

21 4.5<br />

24 5.2<br />

27 6.0<br />

30 6.7<br />

U S – 1 V<br />

75 mA, typical<br />

600 mA, maximum<br />

Electronic per device<br />

Electronic per device<br />

Error Messages to the Higher-Level Control or Computer System<br />

Sensor supply short-circuit<br />

Yes<br />

Sensor supply overload<br />

Yes<br />

If an error is triggered by an overload or short circuit of the sensor supply, the device<br />

switches off the sensor supply of the channels and sends an I/O error message to the<br />

master.<br />

If the sensor supply U S is not sufficiently high, the device sends an I/O error message<br />

to the master.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

7111_en_00 19


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Interface<br />

Bus system<br />

In<strong>com</strong>ing and Outgoing Bus<br />

Coupling of shield connection<br />

Electrical isolation<br />

Transmission speed<br />

Local Bus<br />

Bus system<br />

Coupling of shield connection<br />

Electrical isolation<br />

Transmission speed<br />

Electrical Isolation/Isolation of the Voltage Areas<br />

DeviceNet<br />

High resistance and a capacitance to FE<br />

In<strong>com</strong>ing and outgoing bus are connected<br />

Yes<br />

125 kBaud, 250 kBaud, 500 kBaud<br />

Fieldline modular local bus<br />

Directly on FE<br />

No<br />

500 kbaud<br />

For device connection, please note instructions and regulations in the "Installing the<br />

Fieldline Product Range" user manual FLS <strong>FLM</strong> SYS INST UM E (Order<br />

No.2698973).<br />

Separate Potentials in the <strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong> Input Device<br />

- Test Distance - Test Voltage<br />

24 V supply (U L ) / FE 500 V AC, 50 Hz, 1 min<br />

24 V supply (U L ) / digital inputs (sensor supply) 500 V AC, 50 Hz, 1 min<br />

24 V supply (U L ) / bus logic 500 V AC, 50 Hz, 1 min<br />

Bus logic / FE<br />

500 V AC, 50 Hz, 1 min<br />

Bus logic / digital inputs (sensor supply)<br />

500 V AC, 50 Hz, 1 min<br />

FE / digital inputs (sensor supply)<br />

500 V AC, 50 Hz, 1 min<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

20 7111_en_00


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Ordering Data<br />

Ordering Data Device and Accessories<br />

Description Order Designation Order No.<br />

Fieldline-stand-alone device for DeviceNet <strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong> 27 36 34 3<br />

with 8 digital inputs<br />

Protective caps (for unused sockets) IBS IP PROT-IO 27 59 91 9<br />

pack of 5<br />

Protective cap<br />

(for unused male connectors)<br />

pack of 5<br />

PROT-<strong>M12</strong>-M 27 36 19 4<br />

Socket, metal, shielded, A-encoded, 5-pos., SACC-<strong>M12</strong>FSB-5SC SH 15 12 57 1<br />

for the in<strong>com</strong>ing network<br />

Connector, metal, shielded, B-encoded, SACC-<strong>M12</strong>MSB-5SC SH 15 13 57 0<br />

5-pos., for the outgoing local bus<br />

Markers<br />

ZBF 12:UNBEDRUCKT 08 09 73 5<br />

pack of 10<br />

Jumper cable for voltage supply, A-encoded, SAC-5P-MS/0,13-186 / FS 15 18 48 1<br />

5-pos., unshielded<br />

Data jumper for the local bus,<br />

SAC-5P-MSB/0,13-PUR/FSB SCO SH 15 18 47 8<br />

B-encoded, 5-pos., shielded<br />

Assembly system for five devices <strong>FLM</strong> MP 5 27 36 66 0<br />

Assembly system for seven devices <strong>FLM</strong> MP 7 27 36 67 3<br />

Additional accessories for connecting the actuators can be found in the Phoenix Contact PLUSCON<br />

catalog.<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

7111_en_00 21


<strong>FLM</strong> <strong>BK</strong> <strong>DN</strong> <strong>M12</strong> <strong>DI8</strong> <strong>M12</strong><br />

Ordering Data for Documentation<br />

Description Order Designation Order No.<br />

"Installing the Fieldline Product Range" FLS<strong>FLM</strong>SYSINSTUM E 2698973<br />

user manual<br />

"Configuring a DeviceNet TM System Using<br />

Devices in the Fieldline Product Range"<br />

user manual<br />

FLS <strong>FLM</strong> <strong>DN</strong> SYS PRO UM E 26 99 08 2<br />

Make sure you always use the latest documentation.<br />

It can be downloaded at www.download.phoenixcontact.<strong>com</strong>.<br />

A conversion table is available on the Internet at<br />

www.download.phoenixcontact.<strong>com</strong>/general/7000_en_00.pdf.<br />

PHOENIX CONTACT GmbH & Co. KG<br />

Flachsmarktstr. 8<br />

32825 Blomberg<br />

Germany<br />

+ 49 - (0) 52 35 - 3-00<br />

+ 49 - (0) 52 35 - 3-4 12 00<br />

www.phoenixcontact.<strong>com</strong><br />

Worldwide Locations:<br />

www.phoenixcontact.<strong>com</strong>/salesnetwork<br />

online<strong>com</strong>ponents.<strong>com</strong><br />

© PHOENIX CONTACT 01/2005 Technical modifications reserved. TNR 7111<br />

22 7111_en_00

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!