05.05.2014 Views

csmstr - Omega Engineering

csmstr - Omega Engineering

csmstr - Omega Engineering

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

CSPID – PID MODULE PROGRAMMING<br />

CRIMSON USER MANUAL - MODULAR CONTROLLER<br />

MODE<br />

Deviation Low<br />

Deviation High<br />

In Band<br />

DESCRIPTION<br />

If the Process Value falls below the Setpoint Value by the<br />

amount of the Alarm Value, the alarm activates. In this<br />

mode, the alarm point tracks the Setpoint Value.<br />

If the Process Value exceeds the Setpoint Value by the<br />

amount of the Alarm Value, the alarm activates. In this<br />

mode, the alarm point tracks the Setpoint Value.<br />

If the difference between the Setpoint Value and the<br />

Process Value is not greater than the Alarm Value, the<br />

alarm activates.<br />

Out of Band<br />

If the Process Value exceeds, or falls below, the Setpoint<br />

Value by an amount equal to the Alarm Value, the alarm<br />

activates. In this mode, the alarm point tracks the Setpoint<br />

Value.<br />

• The Value property is the point at which the alarm will turn on. The alarm values<br />

are entered as process units or degrees.<br />

• The Hysteresis value separates the on and off points of the alarm ie. a high acting<br />

alarm programmed to turn on at 500 with a Hysteresis of 10, will turn off when<br />

the PV falls below 490.<br />

• The Latching property dictates how the alarm behaves once activated. See the<br />

Alarm Behavior Chart below for more information.<br />

• The Standby property provides a means of preventing so called nuisance alarms<br />

during power up. See the Alarm Behavior Chart below for more information.<br />

ALARM BEHAVIOR CHART<br />

LATCHING STANDBY ALARM BEHAVIOR<br />

Alarm automatically turns on and off as the Process Value crosses in and out of<br />

the alarm region.<br />

The AlarmAccept bit disables alarm, regardless of the state of the process. If the<br />

alarm condition exists, and the bit is written to a “0”, the alarm activates.<br />

Once activated, the alarm stays active until accepted.<br />

<br />

If the alarm condition no longer exists, writing the Alarm Accept bit to “1”<br />

resets the alarm condition.<br />

As long as the Alarm Accept bit is “1”, the alarm automatically turns on and off<br />

as the Process Value crosses in and out of the alarm region.<br />

PAGE 24<br />

http://www.redlion.net/controller

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!