<strong>Installation</strong> <strong>Manual</strong><br />
Two-hand button<br />
Switch type Comment Classification category Classification SIL<br />
2 two-way switch Two-hand button higher Type III C Pl e<br />
SIL3<br />
requirements<br />
2 normally open Two-hand button<br />
monitored<br />
Type III A Pl e<br />
SIL1<br />
Note: With these input elements a fixed pulse assignment takes place, which cannot be<br />
influenced by the user!<br />
Light curtain<br />
Switch type Comment Classification category Classification SIL<br />
2 normally closed Light curtain higher<br />
Pl e SIL 3<br />
requirements<br />
2 normally closed Light curtain monitored Pl e SIL 3<br />
time monitored<br />
1 normally open + 1 Light curtain higher<br />
Pl e SIL 3<br />
normally closed requirements<br />
1 normally open + 1<br />
normally closed time<br />
monitored<br />
Light curtain monitored Pl e SIL 3<br />
Mode selector switch<br />
Switch type Comment Classification category Classification SIL<br />
2 positions Mode selector switch<br />
Pl e SIL 3<br />
monitored<br />
3 positions Mode selector switch<br />
monitored<br />
Pl e SIL 3<br />
Safety note: When changing the status of the switch the SafePLC program to be created<br />
must ensure that the outputs of the module are deactivated (note: Standard 60204-Part1-<br />
Paragraph 9.2.3).<br />
Sensor<br />
Switch type Comment Classification category Classification SIL<br />
1 normally closed Sensor input standard Pl d SIL 2<br />
1 normally open Sensor input standard Pl d SIL 2<br />
2 normally closed Sensor input higher<br />
Pl e SIL 3<br />
requirements<br />
2 normally closed Sensor input monitored Pl e SIL 3<br />
time monitored<br />
1 normally open + 1 Sensor input higher<br />
Pl e SIL 3<br />
normally closed<br />
1 normally open + 1<br />
normally closed time<br />
monitored<br />
requirements<br />
Sensor input monitored Pl e SIL 3<br />
HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 97 of 97