Installation Manual for SMX Modules - OEM Automatic AB
Installation Manual for SMX Modules - OEM Automatic AB
Installation Manual for SMX Modules - OEM Automatic AB
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Installation</strong> <strong>Manual</strong><br />
Alarm code A 4611 / A 4612<br />
Alarm message<br />
Cause<br />
Remedy<br />
OLC2 Teach In position fault<br />
Teach In position outside measuring range<br />
Check transfer position<br />
Alarm code A 4613 / A 4614<br />
Alarm message<br />
Cause<br />
Remedy<br />
OLC1 Teach In ZSC activation fault<br />
The drive moved during Teach In (ZSC fault)<br />
The drive must be stopped when using the Teach In function<br />
Check whether ZSC has already triggered<br />
Alarm code A 4615 / A 4616<br />
Alarm message<br />
Cause<br />
Remedy<br />
OLC2 Teach In ZSC activation fault<br />
The drive moved during Teach In (ZSC fault)<br />
The drive must be stopped when using the Teach In function<br />
Check whether ZSC has already triggered<br />
Alarm code A 4901 / A 4902<br />
Alarm message<br />
Cause<br />
Remedy<br />
CCW and CW rotation monitoring JSS1 activated at the same time<br />
Multiple activation<br />
In programming make sure that only one "Enable" is activated<br />
Alarm code A 4903 / A 4904<br />
Alarm message<br />
Cause<br />
Remedy<br />
CCW and CW rotation monitoring JSS2 activated at the same time<br />
Multiple activation<br />
In programming make sure that only one "Enable" is activated<br />
Alarm code A 5001 / A 5002<br />
Alarm message<br />
Cause<br />
Remedy<br />
Test deactivation of digital inputs 1...14 faulty<br />
Inputs are still active after deactivation<br />
Check wiring of digital inputs<br />
Alarm code A 6701 / A 6702<br />
Alarm message<br />
Cause<br />
Remedy<br />
Timeout fault MET<br />
Input element with time monitoring is faulty<br />
Check wiring of input element<br />
Input element faulty<br />
Alarm code A 6703 / A 6704<br />
Alarm message<br />
Cause<br />
Remedy<br />
Timeout fault MEZ<br />
Two-hand control element with time monitoring is faulty<br />
Check wiring of input element<br />
Input element faulty<br />
HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 74 of 74