Alarm code A 3177 / A 3178<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on DI10<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3179 / A 3180<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on DI11<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3181 / A 3182<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on DI12<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3183 / A 3184<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on DI13<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3185 / A 3186<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on DI14<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3197 / A 3198<br />
Alarm message Faulty OSSD input test<br />
Cause<br />
OSSD test faulty<br />
Remedy • 24 V check the input voltage on all OSSD inputs<br />
Alarm code A 3209 / A 3210<br />
Fault message<br />
Cause<br />
Remedy<br />
Encoder supply voltage X31 faulty.<br />
• Encoder supply voltage does not comply with configured<br />
threshold<br />
• Component fault in module<br />
• Check configuration!<br />
• Check encoder supply voltage<br />
• Switch device off/on.<br />