Alarm code A 3149 / A 3150<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse2 plausibility fault on input DI10<br />
Configured Pulse2 voltage not applied to this input.<br />
• Check the configuration of the digital input DI10 acc. to planning<br />
and circuit diagram<br />
• Check wiring<br />
Alarm code A 3151 / A 3152<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse2 plausibility fault on input DI11<br />
Configured Pulse2 voltage not applied to this input.<br />
• Check the configuration of the digital input DI11 acc. to planning<br />
and circuit diagram<br />
• Check wiring<br />
Alarm code A 3153 / A 3154<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse2 plausibility fault on input DI12<br />
Configured Pulse2 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
Alarm code A 3155 / A 3156<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse2 plausibility fault on input DI13<br />
Configured Pulse2 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
Alarm code A 3157 / A 3158<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse2 plausibility fault on input DI14<br />
Configured Pulse2 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
Alarm code A 3159 / A 3160<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on DI1<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3161 / A 3162<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on DI2<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 66 of 66