Alarm code A 3081 / A 3082<br />

Alarm message<br />

Cause<br />

Remedy<br />

Pulse2 plausibility fault on expansion inlet EAEx.9<br />

Configured Pulse2 voltage not applied to this input.<br />

• Check the configuration of the digital input acc. to planning and<br />

circuit diagram<br />

• Check wiring<br />

Alarm code A 3083 / A 3084<br />

Alarm message<br />

Cause<br />

Remedy<br />

Faulty 24 V signal on EAEx.9<br />

No permanent 24 V voltage applied to this input<br />

• Check the voltage on the digital input!<br />

• Check wiring<br />

• Check whether Pulse1 or Pulse2 is applied<br />

Alarm code A 3085 / A 3086<br />

Alarm message<br />

Cause<br />

Remedy<br />

Pulse1 plausibility fault on expansion inlet EAEx.10<br />

Configured Pulse2 voltage not applied to this input.<br />

• Check the configuration of the digital input acc. to planning and<br />

circuit diagram<br />

• Check wiring<br />

Alarm code A 3087 / A 3088<br />

Alarm message<br />

Cause<br />

Remedy<br />

Pulse2 plausibility fault on expansion inlet EAEx.10<br />

Configured Pulse2 voltage not applied to this input.<br />

• Check the configuration of the digital input acc. to planning and<br />

circuit diagram<br />

• Check wiring<br />

Alarm code A 3089 / A 3090<br />

Alarm message<br />

Cause<br />

Remedy<br />

Faulty 24 V signal on EAEx.10<br />

No permanent 24 V voltage applied to this input<br />

• Check the voltage on the digital input!<br />

• Check wiring<br />

• Check whether Pulse1 or Pulse2 is applied<br />

Alarm code A 3101 / A 3102<br />

Alarm message<br />

Cause<br />

Remedy<br />

Pulse1 plausibility fault on input DI1<br />

Configured Pulse1 voltage not applied to this input.<br />

• Check the configuration of the digital input acc. to planning and<br />

circuit diagram<br />

• Check wiring<br />

Alarm code A 3103 / A 3104<br />

Alarm message<br />

Cause<br />

Remedy<br />

Pulse1 plausibility fault on input DI2<br />

Configured Pulse1 voltage not applied to this input.<br />

• Check the configuration of the digital input acc. to planning and<br />

circuit diagram<br />

• Check wiring<br />