Installation Manual Alarm code A 3053 / A 3054 Alarm message Cause Remedy Faulty 24 V signal on EAEx.4 No permanent 24 V voltage applied to this input • Check the voltage on the digital input! • Check wiring • Check whether Pulse1 or Pulse2 is applied Alarm code A 3055 / A 3056 Alarm message Cause Remedy Pulse1 plausibility fault on expansion inlet EAEx.5 Configured Pulse1 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3057 / A 3058 Alarm message Cause Remedy Pulse2 plausibility fault on expansion inlet EAEx.5 Configured Pulse2 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3059 / A 3060 Alarm message Cause Remedy Faulty 24 V signal on EAEx.5 No permanent 24 V voltage applied to this input • Check the voltage on the digital input! • Check wiring • Check whether Pulse1 or Pulse2 is applied Alarm code A 3061 / A 3062 Alarm message Cause Remedy Pulse1 plausibility fault on expansion inlet EAEx.6 Configured Pulse1 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3063 / A 3064 Alarm message Cause Remedy Pulse2 plausibility fault on expansion inlet EAEx.6 Configured Pulse2 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3065 / A 3066 Alarm message Cause Remedy Pulse1 plausibility fault on expansion inlet EAEx.7 Configured Pulse1 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring HB-37350-810-01-10E-EN SMX installation manual.doc Page 60 of 60
Installation Manual Alarm code A 3067 / A 3068 Alarm message Cause Remedy Pulse1 plausibility fault on expansion inlet EAEx.7 Configured Pulse1 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3069 / A 3070 Alarm message Cause Remedy Pulse2 plausibility fault on expansion inlet EAEx.7 Configured Pulse2 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3071 / A 3072 Alarm message Cause Remedy Faulty 24 V signal on EAEx.7 No permanent 24 V voltage applied to this input • Check the voltage on the digital input! • Check wiring • Check whether Pulse1 or Pulse2 is applied Alarm code A 3073 / A 3074 Alarm message Cause Remedy Pulse1 plausibility fault on expansion inlet EAEx.8 Configured Pulse2 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3075 / A 3076 Alarm message Cause Remedy Pulse2 plausibility fault on expansion inlet EAEx.8 Configured Pulse2 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring Alarm code A 3077 / A 3078 Alarm message Cause Remedy Faulty 24 V signal on EAEx.8 No permanent 24 V voltage applied to this input • Check the voltage on the digital input! • Check wiring • Check whether Pulse1 or Pulse2 is applied Alarm code A 3079 / A 3080 Alarm message Cause Remedy Pulse1 plausibility fault on expansion inlet EAEx.9 Configured Pulse2 voltage not applied to this input. • Check the configuration of the digital input acc. to planning and circuit diagram • Check wiring HB-37350-810-01-10E-EN SMX installation manual.doc Page 61 of 61
- Page 9 and 10: Installation Manual 3.1.2 SMX11 Typ
- Page 11 and 12: Installation Manual 3.1.4 SMX12A Ty
- Page 13 and 14: Installation Manual 3.1.6 Type plat
- Page 15 and 16: Installation Manual 4.2 Installatio
- Page 17 and 18: Installation Manual 4.4 External 24
- Page 19 and 20: Installation Manual 4.6 Connection
- Page 21 and 22: Installation Manual Note: • In th
- Page 23 and 24: Installation Manual 2. Single-chann
- Page 25 and 26: Installation Manual 4.8 Connection
- Page 27 and 28: Installation Manual Attention: The
- Page 29 and 30: Installation Manual 6.2 Connection
- Page 31 and 32: Installation Manual 6.4 Connection
- Page 33 and 34: Installation Manual 8 Sensor type A
- Page 35 and 36: Installation Manual For application
- Page 37 and 38: Installation Manual The test functi
- Page 39 and 40: Installation Manual 10.1.2 Single-p
- Page 41 and 42: Installation Manual 10.1.4 Single-p
- Page 43 and 44: Installation Manual 10.1.6 Wiring o
- Page 45 and 46: Installation Manual 10.2.2 Wiring t
- Page 47 and 48: Installation Manual Response times
- Page 49 and 50: Installation Manual 11 Start-up 11.
- Page 51 and 52: Installation Manual 11.4 Terminal a
- Page 53 and 54: Installation Manual 12 Safety relat
- Page 55 and 56: Installation Manual 14 Technical da
- Page 57 and 58: Installation Manual 15.2 Alarm list
- Page 59: Installation Manual Alarm code A 30
- Page 63 and 64: Installation Manual Alarm code A 31
- Page 65 and 66: Installation Manual Alarm code A 31
- Page 67 and 68: Installation Manual Alarm code A 31
- Page 69 and 70: Installation Manual Alarm code A 32
- Page 71 and 72: Installation Manual Alarm code A 33
- Page 73 and 74: Installation Manual Alarm code A 35
- Page 75 and 76: Installation Manual 15.3 Fatal Erro
- Page 77 and 78: Installation Manual Fatal Error Cod
- Page 79 and 80: Installation Manual Fatal Error Cod
- Page 81 and 82: Installation Manual Fatal Error Cod
- Page 83 and 84: Installation Manual Fatal Error Cod
- Page 85 and 86: Installation Manual Fatal Error Cod
- Page 87 and 88: Installation Manual 16 Encoder type
- Page 89 and 90: Installation Manual 17 Switch types
- Page 91 and 92: Installation Manual Type Graphic sy
- Page 93 and 94: Installation Manual 10 eSwitch_3oT
- Page 95 and 96: Installation Manual eTwoHand_2s LD
- Page 97 and 98: Installation Manual Two-hand button
<strong>Installation</strong> <strong>Manual</strong><br />
Alarm code A 3053 / A 3054<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on EAEx.4<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3055 / A 3056<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse1 plausibility fault on expansion inlet EAEx.5<br />
Configured Pulse1 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
Alarm code A 3057 / A 3058<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse2 plausibility fault on expansion inlet EAEx.5<br />
Configured Pulse2 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
Alarm code A 3059 / A 3060<br />
Alarm message<br />
Cause<br />
Remedy<br />
Faulty 24 V signal on EAEx.5<br />
No permanent 24 V voltage applied to this input<br />
• Check the voltage on the digital input!<br />
• Check wiring<br />
• Check whether Pulse1 or Pulse2 is applied<br />
Alarm code A 3061 / A 3062<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse1 plausibility fault on expansion inlet EAEx.6<br />
Configured Pulse1 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
Alarm code A 3063 / A 3064<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse2 plausibility fault on expansion inlet EAEx.6<br />
Configured Pulse2 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
Alarm code A 3065 / A 3066<br />
Alarm message<br />
Cause<br />
Remedy<br />
Pulse1 plausibility fault on expansion inlet EAEx.7<br />
Configured Pulse1 voltage not applied to this input.<br />
• Check the configuration of the digital input acc. to planning and<br />
circuit diagram<br />
• Check wiring<br />
HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 60 of 60