15 Fault types <strong>SMX</strong><br />
The <strong>SMX</strong> generally differentiates between two types of faults as per assignment below:<br />
Fault type<br />
Fatal Error<br />
Alarm<br />
ECS-Alarm<br />
Description<br />
Severe exceptional error caused by the<br />
program run in the <strong>SMX</strong>. Cyclic program<br />
sequence is no longer possible <strong>for</strong> safety<br />
related reasons. The last active process is<br />
the operation of the 7-segment display by<br />
system A. System B is in stop mode.<br />
Functional fault, caused by an external<br />
process. Both systems continue to run<br />
cyclically and serve all requests from the<br />
communication interfaces. Sensing of the<br />
external process is also maintained.<br />
When using the ECS function in the<br />
programming desktop, the encoder alarm<br />
messages are marked "E" instead of "A".<br />
Effect<br />
on the<br />
system<br />
All outputs<br />
are<br />
switched<br />
off!<br />
All outputs<br />
are<br />
switched<br />
off!<br />
ECS<br />
function<br />
block<br />
delivers "0"<br />
as a result.<br />
Reset<br />
condition<br />
Reset possible<br />
by switching the<br />
<strong>SMX</strong>(POR)<br />
off/on.<br />
Reset<br />
possible via<br />
parameterizable<br />
input<br />
Reset<br />
possible via<br />
parameterizable<br />
input<br />
Recognizing faults system, A and system B:<br />
• System A: odd numbered<br />
• System B: even numbered<br />
15.1 Fault indication<br />
There are two possible ways of displaying the fault number<br />
15.1.1 <strong>SMX</strong>.. without expansion modules<br />
F,A or E __ __ __ __<br />
Fault number<br />
15.1.2 <strong>SMX</strong>.. with expansion modules<br />
F,A or E __ __ __ __ __<br />
1) Fault number<br />
Note 1) 0: Base module<br />
1: Expansion module with logic address 1<br />
2: Expansion module with logic address 2<br />
HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 56 of 56