<strong>Installation</strong> <strong>Manual</strong><br />

12 Safety related examination<br />

In order to assure the reliability of the implemented safety functions the user must check and<br />

document the parameters and links after the start-up and parameterization has taken place.<br />

This is supported by the parameterization software SafePLC <strong>SMX</strong> (see programming<br />

manual).<br />

On the first page one can enter general system data. The last page of the validation report<br />

contains individual evidence concerning the safety related examination.<br />

Here the following entries are mandatory:<br />

• Serial number (identical with the serial number on the type plate)<br />

• Identity of the module<br />

Here the responsible tester confirms that the CRC's displayed in the programming desktop<br />

are identical with the CRC stored in the <strong>SMX</strong> module.<br />

Once all header data have been entered, the validation report can be generated by pressing<br />

the control button "Save". The parameterization tool then creates a text file (.TXT) with the<br />

file name of the program data set. The text file contains the following in<strong>for</strong>mation:<br />

• The 3 pages of header data edited above<br />

• The configuration of the encoder<br />

• The parameters of the existing monitoring function<br />

• The PLC program as instruction list<br />

After the transmission of the configuration and program data to the <strong>SMX</strong> module the status<br />

LED flashes yellow. This indicates that the configuration data have not yet been validated.<br />

Pressing the button "LOCK CONFIGURATION" at the end of the validation dialog highlights<br />

the data as "Validated" and the LED flashes in green.<br />

HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 53 of 53