Terminal Designation<br />
X25:1 AI 1+<br />
X25:2 AI 1-<br />
X25:3 AI 2+<br />
X25:4 AI 2-<br />
X26:1<br />
X26:2<br />
X26:3<br />
X26:4<br />
AI 3+<br />
AI 3-<br />
AI 4+<br />
AI 4-<br />
Function<br />
Analog input AIN1 +<br />
Analog input AIN1 -<br />
Analog input AIN2 +<br />
Analog input AIN2 -<br />
Analog input AIN3 +<br />
Analog input AIN3 -<br />
Analog input AIN4 +<br />
Analog input AIN4 -<br />
<strong>SMX</strong>12A<br />
<strong>SMX</strong>12A<br />
Terminal assignment <strong>SMX</strong>51<br />
Terminal Designation Function<br />
X41:1<br />
X41:2<br />
X41:3<br />
X41:4<br />
X41:5<br />
X41:6<br />
X41:7<br />
X41:8<br />
X41:9<br />
NC<br />
CAN_LO<br />
CAN_GND<br />
NC<br />
NC<br />
CAN_GND<br />
CAN_HI<br />
NC<br />
NC<br />
With terminating resistor 120 Ohm<br />
11.5 Parameterization<br />
Parameterization takes place via the program SafePLC <strong>SMX</strong>. The transmission of these data<br />
to the module requires a programming adapter, the drivers of which must first be installed by<br />
the user.<br />
Parameterization is described in the programming manual.<br />
11.6 Function test<br />
As a measure to ensure the safety of the module, the reliability of all safety functions must be<br />
checked once every year. For this purpose the modules used in the parameterization (inputs,<br />
outputs, monitoring functions and logic modules) must be checked with respect to function or<br />
shut-down.<br />
See programming manual.<br />
11.7 Validation<br />
In order to assure the reliability of the implemented safety functions the user must check and<br />
document the parameters and links after the start-up and parameterization has taken place.<br />
This is supported by a validation assistant in the programming desktop (see chapter "Safety<br />
related examination").<br />