<strong>Installation</strong> <strong>Manual</strong><br />

Attention:<br />

The sensor connections must neither be plugged on nor pulled off during operation. This<br />

could cause damage to electrical components of the encoder. Always de-energize connected<br />

encoders and the <strong>SMX</strong> module be<strong>for</strong>e plugging on or pulling off encoder connections.<br />

Lines twisted in pairs <strong>for</strong> signal transmission acc. to RS485 standard must be used <strong>for</strong> data<br />

and clock signals or track A and track B. The wire cross-section must in each individual case<br />

be chosen in compliance with the current consumption of the encoder and the cable length<br />

required <strong>for</strong> the installation.<br />

The following applies when using absolute encoders:<br />

In Slave-mode the clock signal is generated by an external process and is read in by the<br />

<strong>SMX</strong> module together with the data signal. This type of reading causes a beat which results<br />

in a reading fault of the following magnitude:<br />

F = (reading time of encoder by external system [ms] / 8 [ms] ) * 100 %<br />

The size of the resulting reading fault F must be taken into account when determining the<br />

thresholds in the applied monitoring functions, because this fault cannot be compensated!<br />

HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 27 of 27