<strong>Installation</strong> <strong>Manual</strong><br />

4.6 Connection of digital inputs DI1 to DI14<br />

The <strong>SMX</strong> has 14 secure digital inputs These are suitable <strong>for</strong> connecting single or twochannel<br />

signals with and without cycling, or without cross-shorting test.<br />

The connected signals must have a "High"-level of DC 24 V (DC +15 V...+ DC 30 V ) and a<br />

"Low"-level of (DC -3 V...DC +5 V, type 1 acc. to EN61131-2). The inputs are provided with<br />

internal input filters.<br />

A device internal diagnostic function cyclically tests the correct function of the inputs<br />

including the input filters. A detected fault will set the <strong>SMX</strong> into an alarm status. At the same<br />

time all outputs of the <strong>SMX</strong> are rendered passive.<br />

Besides the actual signal inputs DI1 to DI14 the <strong>SMX</strong> module holds two clock inputs P1 and<br />

P2 available. The clock outputs are switching-type 24 VDC outputs.<br />

The clock outputs are solely intended <strong>for</strong> monitoring the digital inputs (DI1 ... DI14) and<br />

cannot be used <strong>for</strong> any other function within the application.<br />

The switching frequency is 125 Hz <strong>for</strong> each output. In the planning stage one must bear in<br />

mind that the outputs may only be loaded with a total current of max. 250 mA.<br />

Furthermore, approved OSSD-outputs can be connected to the inputs DI1-DI4 and DI9-DI14<br />

without limitation<br />

Note:<br />

Digital inputs DI5 to DI8 are not suitable <strong>for</strong> OSSDs, because there is no compliance<br />

with EN 61131-2 Type 2 requirements.<br />

Short circuits in the external wiring between different inputs and against the supply voltage<br />

<strong>for</strong> the <strong>SMX</strong> must be ruled out by external measures, appropriate routing of cables in<br />

particular.<br />

Each input of the <strong>SMX</strong> module can be configured individually <strong>for</strong> the following signal<br />

sources:<br />

Input assigned to pulse P1<br />

Input assigned to pulse P2<br />

Input assigned to continuous voltage DC 24 V<br />

The internal structure of the <strong>SMX</strong>-series corresponds with category 4 of EN 13849-1 with<br />

respect to architecture and function. Each input has the following internal architecture:<br />

HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 19 of 19