4.2 <strong>Installation</strong> and assembly of the <strong>SMX</strong> module<br />

The module is solely to be installed in control cabinets with a degree of protection of at least<br />

IP54.<br />

The modules must be vertically fastened on a top hat rail<br />

The ventilation slots must be kept unobstructed, to ensure adequate air circulation inside the<br />

module.<br />

4.3 <strong>Installation</strong> of backplane bus system<br />

Mounting several <strong>SMX</strong> modules (<strong>SMX</strong>10, <strong>SMX</strong>11, <strong>SMX</strong>12, <strong>SMX</strong>12A) on one top hat rail in<br />

connection with the backplane bus system is also possible. These modules can be combined<br />

with a communication extension. In this case the backplane bus system needs to be<br />

configured by BBH when placing the order and delivered in accordance with the application<br />

in question.<br />

The backplane bus system consists of a 5-pin plug connector with snap-in contacts. In these<br />

plug connectors all 5 contacts are equipped by standard. In this case the component is not<br />

specially marked. On a second variant of the plug connector only 3 contacts are equipped.<br />

Note:<br />

Expansion modules have no own power supply unit and depend on a DC power supply via<br />

the backplane bus system. Base modules (<strong>SMX</strong>10, <strong>SMX</strong>11, <strong>SMX</strong>12, <strong>SMX</strong>12A) are equipped<br />

with a rein<strong>for</strong>ced power supply unit and always feed in to the backplane bus.<br />

There are two different types of backplane bus connectors:<br />

• TB1: Standard design (all contacts are present)<br />

• TB2: Interrupter design (the two power conductors are not present and are marked<br />

with a green dot)<br />

Using the backplane bus connector TB1:<br />

The backplane bus connector TB1 can only be installed in connection with expansion<br />

modules without their own power supply. Connection of several standalone modules is not<br />

possible.<br />

Using the backplane bus connector TB2:<br />

The backplane bus connector TB2 is used <strong>for</strong> combining several base modules with<br />

expansion modules. A detailed description can be found under point 4.3.1.<br />

HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 15 of 15