26.04.2014 Views

SNAP-TITE - Hise Rise Hose Specifications.pdf

SNAP-TITE - Hise Rise Hose Specifications.pdf

SNAP-TITE - Hise Rise Hose Specifications.pdf

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

PONN FIRE FIGHTING PRODUCTS<br />

<strong>Specifications</strong> for PONN Conquest<br />

A Type of <strong>Hose</strong><br />

A-1 The hose shall be lightweight, double jacketed, and polyurethane<br />

lined. The hose shall be of premium quality, designed to be<br />

abrasion resistant, low temperature flexible and to meet or exceed<br />

all of today's firefighting service requirements.<br />

A-2 The manufacturer's quality assurance system shall be ISO-<br />

9001 certified. A copy of the certificate shall accompany the bid.<br />

A-3 All fire hose shall be manufactured, coupled and subjected to<br />

the hydrostatic proof test pressure in accordance with NFPA<br />

Standard 1961, latest edition. Certificates of conformance shall be<br />

available at the customers' request.<br />

Comply Yes _____ No _____<br />

B Sizes<br />

B-1 The sizes shall be: 1 1/2" - 1 3/4" - 2" - 2 1/2" - 3" - 4" and 5"<br />

C Materials and Workmanship<br />

All materials and workmanship used in the fabrication of the fire<br />

hose shall be first quality.<br />

C-1 Materials<br />

The buyer reserves the right to have any or all material supplied<br />

and tested by a qualified independent source. If the material<br />

supplied does not meet the specification and no exceptions were<br />

taken, the supplier (bidder) shall be responsible for the following:<br />

1-Cost of testing service<br />

2-Price difference between the bid price and the next lowest<br />

bidder, along with any other related expenses to purchase the<br />

material specified.<br />

C-2 It is not the intention of the specification to bar from consideration<br />

any hose of improved design or quality that will meet or<br />

exceed the published specifications.<br />

D Detailed <strong>Specifications</strong><br />

D-1 Outer jacket construction<br />

The jackets shall be evenly, firmly and well woven with fine count<br />

virgin ring-spun polyester in the warp ends. The jackets shall be<br />

free of unsightly defects, dirt, knots, lumps and irregularities of twist<br />

that might effect the serviceability of the finished product. Open<br />

end and air entangled yarns will not be acceptable. The filler or<br />

weft yarns shall be made of high tenacity, low stretch filament<br />

polyester, and shall be completely covered by the warp ends.<br />

Comply Yes _____ No _____<br />

D-2 Inner jacket construction<br />

The inner jacket warp and weft yarns shall be 100% high tenacity -<br />

low stretch filament polyester for greater strength. These yarns<br />

shall be completely encapsulated by a polyurethane compound.<br />

Comply Yes _____ No _____<br />

E Lining<br />

E-1 The lining material shall be a polyurethane compound applied<br />

by a through-the-weave process. The material shall be applied to<br />

create a very smooth waterway to reduce friction loss. The lining<br />

materials shall fill the openings of the weave encapsulating each<br />

and every warp and weft yarn. Linings that are glued or applied by<br />

a hot melt process are not acceptable.<br />

Comply Yes _____ No _____<br />

E-2 Backing<br />

Backing or adhesives of any kind shall not be acceptable.<br />

Comply Yes _____ No _____<br />

E-3 The lining shall remain flexible to -60°F (-51°C).<br />

Comply Yes _____ No _____<br />

E-4 The lining shall have a tensile strength of 5000 psi.<br />

Comply Yes _____ No _____<br />

E-5 The adhesion between the lining and the inner jacket shall not<br />

be less than 25 lbs. (11 kg)<br />

Comply Yes _____ No _____<br />

E-6 When specified for potable water, the polyurethane lining<br />

material shall be approved by the National Sanitation Foundation<br />

to meet NSF Standard 61.<br />

Comply Yes _____ No _____<br />

E-7 Ozone resistance<br />

There shall be no visible signs of liner cracking when tested to<br />

100 pphm at 122°F (50°C) for 100 hours.<br />

Comply Yes _____ No _____<br />

F Finished <strong>Hose</strong><br />

F-1 <strong>Hose</strong> must be 50 ft. when measured at 0 psi.<br />

F-2 Weights uncoupled 50'<br />

1-1/2" 1-3/4" 2" 2-1/2" 3" 4" 5"<br />

Lbs/50' 15 17 20 27.5 34 50 52<br />

Kg/15m 6.8 7.7 9.1 12.5 15.4 22.7 23.6<br />

F-3 Coil diameter 50ft.<br />

1 1/2" 1 3/4" 2" 2 1/2" 3" 4" 5"<br />

Inches: 15 15.5 16 16.75 18 22 26<br />

CM: 38 40 41 42.5 45.7 55.9 66<br />

F-4 Pressure test requirements<br />

Each section of hose shall withstand a hydrostatic pressure test<br />

(proof) as shown below for a minimum of 15 seconds without<br />

leakage or breaking of threads in the hose. Other requirements to<br />

conform with NFPA 1961, latest edition.<br />

<strong>Hose</strong> Minimum Service<br />

Size Proof Burst Test<br />

1-1/2"-1-3/4"-2"-2-1/2" 800 psi 1200 psi 400 psi<br />

3"- 4"-5" 600 psi 900 psi 300 psi<br />

Comply Yes _____ No _____<br />

F-5 The elongation between 10 psi and the proof test pressure<br />

shall not exceed 5%. There shall be no contraction of hose<br />

between 10 psi and proof test pressure.<br />

Comply Yes _____ No _____<br />

F-6 The expansion of the hose between 10 psi and the proof test<br />

pressure shall not exceed 5%.<br />

Comply Yes _____ No _____<br />

F-7 Warp from a straight line between 10 psi and proof test<br />

pressure shall not exceed 10". The hose shall not rise from the<br />

test table. (50 ft length)<br />

Comply Yes _____ No _____


F-8 Twist of the hose (50' length) between 10 psi and the proof<br />

test pressure shall not exceed 3-1/2 turns for the 1-1/2", 1-3/4", 2"<br />

and 1-1/2" turns for the 2-1/2", 3", 4" and 5" sizes. No final twist in<br />

a direction to loosen the couplings (left) shall be permitted.<br />

Comply Yes _____ No _____<br />

G Safety factors<br />

G-1 Dura-Cote process (option)<br />

The outer jacket shall be impregnated with a specially developed<br />

compound. This compound when applied to the hose increases<br />

the abrasion resistance of the fabric to well over 30,000 cycles on<br />

an abrasion tester. Dura-Cote contains a special flame retardant,<br />

which increases the burn resistance from less than one minute to<br />

over five minutes on a special flame test. Dura-Cote also<br />

decreases water pick-up by 100%, and adds resistance to<br />

petrochemicals. Dura-Cote is available in five colors; red, yellow,<br />

orange, blue and tan.<br />

Comply Yes _____ No _____<br />

G-2 When coated with Dura-Cote, hose shall pass a flame test, as<br />

depicted below, for a period of five minutes without bursting.<br />

3"<br />

FLAME<br />

Comply Yes _____ No _____<br />

5-1/4"<br />

G-3 When coated with Dura-Cote, hose shall pass a hot cube test<br />

(British Standard 6391) for a period of two minutes. The procedure<br />

calls for the test cube to be heated to 1112° F (600 °C).<br />

Comply Yes _____ No _____<br />

G-4 Kink Resistance<br />

A 50' length of hose shall be pressurized to 50 psi nozzle pressure<br />

with water flowing. A loop shall be formed in the center of the<br />

length with the hose side by side and both couplings together. This<br />

loop must pass through a 34" doorway without kinking or otherwise<br />

limiting the flow of water to the nozzle.<br />

Comply Yes _____ No _____<br />

G-5 Friction loss per 100' attack hose 2-50' long.<br />

GPM 150 180 200 220 240<br />

1-3/4" 16 20 25 29 30<br />

2" 10 12 18 10 23<br />

All tests conducted with a 15/16 straight bore nozzle.<br />

Comply Yes _____ No _____<br />

G-6 Ponn Color Coding System (Option)<br />

Ponn has been the leader in color coded hoses for 20 years. A one<br />

inch stripe of contrasting color is woven into the outer jacket<br />

running the full length of the hose for identification purposes. There<br />

are nine colors available meeting NFPA 1901 recommendations for<br />

pump panel discharge identification. These colors are: red, yellow,<br />

blue, green, tan, orange, black, purple and silver.<br />

Comply Yes _____ No _____<br />

G-7 Color coding can be used in conjunction with the Dura-Cote<br />

process in limited colors only as another option. The stripe color<br />

must be a darker shade than the Dura-Cote.<br />

Comply Yes _____ No _____<br />

NOTE: <strong>Hose</strong> is filled with water and pressurized to 75 psi.<br />

! WARNING !<br />

FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL<br />

INJURY AND PROPERTY DAMAGE.<br />

This document and other information from Snap-tite, Inc., its subsidiaries and authorized distributors provide product and/or system options for further investigation by users having<br />

technical expertise. It is important that you analyze all aspects of your application and review the information concerning the product or system in the current product catalog. Due to the<br />

variety of operation conditions and applications for these products or systems, the user, through its own analysis and testing, is solely responsible for making the final selection of the products<br />

and systems and assuring that all performance, safety and warning requirements of the application are met.<br />

The products described herein, including without limitation, product features, specifications, design, availability and pricing, are subject to change by Snap-tite, Inc. and its subsidiaries at<br />

any time without notice.<br />

ISO-9001 Certified<br />

03-0024PE-0100

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!