16.04.2014 Views

LARUCP R-1 Occupancy Plan Review List - ladbs

LARUCP R-1 Occupancy Plan Review List - ladbs

LARUCP R-1 Occupancy Plan Review List - ladbs

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

CITY of Los Angeles<br />

<strong>LARUCP</strong> R-1 OCCUPANCY PLAN REVIEW LIST<br />

PLAN CHECK NO. PLAN CHECK EXPIRATION DATE: 18 months from submittal date<br />

PCIS# (s): _____________________________ JOB ADDRESS:<br />

APPLICANT TEL. NO. INITIAL VALUATION<br />

SQUARE FOOTAGE USE ZONE FIRE ZONE FLOOD ZONE<br />

OCCUPANCY GROUP TYPE OF CONSTRUCTION NO. OF STORIES<br />

REVIEWED BY: _________________<br />

DATE: ______________ TEL. NO. : __________________<br />

E-MAIL: _______________________@LADBS.LACITY.ORG Website: LADBS.ORG<br />

BUILDING SPRINKLERS THROUGHOUT? 9 YES 9 NO<br />

SPRINKLER USED IN LIEU OF ONE-HOUR CONSTRUCTION? 9 YES 9 NO<br />

SPRINKLER USED FOR AREA INCREASE? 9 YES 9 NO<br />

SPRINKLER USED FOR STORY INCREASE? 9 YES 9 NO<br />

Your application for a permit, together with plans and specifications, has been examined and you are advised that the<br />

issuance of a permit is withheld for the reasons hereinafter set forth. The approval of plans and specifications does not<br />

permit the violation of any section of the Building Code, or other local ordinance or state law.<br />

NOTE: Numbers in parenthesis refer to Code sections of the 2001 edition of the California Building Code, (T=Table),<br />

Plumbing Code (P.C.), Mechanical Code (M.C.) or Fire Code (F.C.). N.D.S. refers to The National Design Specifications.<br />

(*) Corrections used by the City of Los Angeles that may not be used by other municipalities.<br />

Project applicants/representatives are advised to initiate the sign-off processes for the required clearances, listed in<br />

the Clearance Summary Worksheet, as soon as possible. The time to obtain the sign-off from some departments, i.e.,<br />

Department of City <strong>Plan</strong>ning, may be time-consuming.<br />

If you cannot comply with the plan check corrections circled under PLANNING & ZONING of this correction sheet,<br />

and instead, wish to obtain a discretionary approval from the Department of City <strong>Plan</strong>ning, please initiate the request<br />

for discretionary approval as soon as possible as the process may be time-consuming due to the probable requirement<br />

of a public hearing.<br />

INSTRUCTIONS<br />

! Corrections with circled item numbers apply to this plan check.<br />

! Incorporate all comments as marked on checked set of plans and calculations and this corrections sheet. In the left hand<br />

margin of the circled corrections, please indicate the sheet number and detail or note number on the plans where the<br />

corrections are made. Once all the circled corrections and additional corrections have been addressed, contact the plan<br />

check engineer to schedule a verification appointment to demonstrate compliance with all the corrections.<br />

! Bring the original checked set of plans and calculations along with this correction sheet to the verification appointment.<br />

Do not schedule a verification until all corrections have been addressed.<br />

! Incomplete, indefinite or faded drawings or calculations will not be accepted.<br />

! The plan check engineer will only be available for conference and telephone calls between the hours of and<br />

on the following days:<br />

. Appointments are recommended.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 1 of 23<br />

www.<strong>ladbs</strong>.org


A. APPLICATION<br />

1. Obtain the building Permit prior to expiration or file an<br />

extension with an additional fee of $ .<br />

2. Valuation is low. It should be $ .<br />

Pay a supplemental plan check fee of $ .<br />

3. Art development fees are applicable to the proposed hotel. ( 107.4.6)<br />

4. Complete the permit application form to show the legal<br />

description, building area, street address, owner, designer,<br />

occupancy group, type of construction, fire zone,<br />

.<br />

5. A separate application and permit(s) is/are required for:<br />

a. Retaining walls<br />

b. Block walls (>3.5')<br />

c. Signs<br />

d. Swimming pools<br />

e. Fire sprinkler systems<br />

f. Each separate structure<br />

g. Electrical work<br />

h. Mechanical work<br />

i. Plumbing work<br />

* j. Grading (Backfill)(Removal/Recompaction)(Site grading)<br />

* k. Shoring<br />

* l. Demolition work<br />

* m. ( )<br />

6. Obtain proof of lot cut date prior to___________<br />

(After 6-1-46 comply to zone minimums.)<br />

(After 7-29-62 obtain Certificate of Compliance<br />

from City <strong>Plan</strong>ning.)<br />

7. A recorded affidavit is required for ( ). The<br />

affidavit must be approved by the plan check engineer prior to<br />

recording.<br />

8. Provide copies of the following documents which appear on<br />

this parcel: ( ).<br />

For information on how to obtain copies of affidavits,<br />

please call Building and Safety Records Section, Metro<br />

office (213) 482-6899 or Van Nuys Office (818) 374-4390.<br />

For all other City <strong>Plan</strong>ning documents contact the<br />

Department of City <strong>Plan</strong>ning at (213) 978-1259, or fax<br />

request to (213) 978-1263. Additional corrections and/ or<br />

Clearances may follow upon review of the documents.<br />

9. Provide a copy of the Certificate of <strong>Occupancy</strong> and/or<br />

building permit showing the permitted use and required<br />

parking.<br />

10. Show the legal description, building area, occupancy<br />

group(s), use(s), type of construction, number of story(s),<br />

fire zone, lot size, lot area and height on the first sheet or<br />

title sheet of plans.<br />

11. Comply with protection of adjoining property by giving a 30<br />

day written notice (by certified mail) of attached letter to<br />

adjacent property owners, of intent to excavate where<br />

excavation is deeper than the foundation of adjoining building<br />

and located closer to property line than the depth of<br />

excavation.<br />

12. The permit application must be signed by the property owner,<br />

or licensed contractor, or authorized agent at the time the<br />

permit is to be issued:<br />

a. For owner-builder permits: Owner’s signature must be<br />

verified by notarization or personal identification.<br />

b. For contractor building permits: Prior to the issuance<br />

of a building permit, the contractor shall have the following:<br />

I. Certificate of workers Compensation Insurance<br />

made out to the Contractors State License Board.<br />

II. Notarized letter of authorization for agents.<br />

III.Copy of Contractors State License or pocket ID.<br />

* IV. Copy of ( ) City business tax<br />

registration certificate or a newly paid receipt<br />

for one.<br />

13. (Soil)(Foundation)(Geology) report(s) must be approved by<br />

City Grading Section. Provide copy of approved report and<br />

Department approval letter. Show compliance with all the<br />

requirements of the reports and the approval letter conditions.<br />

14. Provide temporary shoring plans for excavations that remove<br />

the lateral support from a public way or an existing building.<br />

Excavations adjacent to a public way require Public Works<br />

approval prior to issuance of building permit.<br />

B. REFERRALS<br />

1. Please see the attached clearance summary worksheet for the<br />

clearance required prior to issuance of building permit.<br />

Project applicants/representatives are advised to<br />

initiate the sign-off processes for these clearances<br />

as soon as possible. The time to obtain the signoff<br />

from some departments, i.e., Department of<br />

City <strong>Plan</strong>ning, may be time-consuming. Read<br />

the comments attached to the clearance, if any,<br />

as they often contain important and useful<br />

information.<br />

2. Call ( ) ___________ for information on obtaining the<br />

required clearance for ______________ Specific <strong>Plan</strong>,<br />

_______________ HPOZ, ______________ CDO, and<br />

_______________ POD. Not all projects can be cleared the<br />

same day and an appointment may be necessary.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 2 of 23<br />

www.<strong>ladbs</strong>.org


3. Prior to issuance of building permit, obtain approval from:<br />

a). California Division of Occupational Safety and<br />

Health(Cal-OSHA) for (excavations exceeding 5-ft height<br />

where worker descends) (Building over 3-story’s or 35-ft<br />

height). 350 W. 4 th St. Ste 850, Los Angeles, CA<br />

(213)576-7451 or 6150 Van Nuys Bl, Rm 405, Van Nuys,<br />

CA (818)901-5403<br />

b). Los Angeles County Health Department for: (food<br />

establishment)(swimming pool)(potable chemical<br />

toilet)(water well construction/monitoring/destruction)<br />

3530 Wilshire Bl, 9 th floor Los Angeles, CA (213)351-<br />

7352<br />

6851 Lennox Ave, 3 rd floor, Van Nuys, CA (818)902-4470<br />

6053 Bristol Parkway, 2 nd floor, Culver City, CA<br />

(310)665-8483<br />

122 W. 8 th St. Rm 20-A, San Pedro, CA (310)519-6081<br />

Admin HQ: 5050 Commerce Dr., Baldwin Park, CA<br />

(626)430-5560<br />

c). Dept. of Conservation, Division of Oil and Gas (DOG) for<br />

project on land with an abandoned oil well. 5816<br />

Corporate Ave., Room 200, Cypress, CA (714)816-6847.<br />

4. Rough grading approval is required before a building permit<br />

can be issued.<br />

5. Parcel Map/Tract Map _______________ must be recorded<br />

before a permit can be issued. Submit a copy of the recorded<br />

map.<br />

6. Submit a copy of CUP, plot plan number .<br />

7. For energy insulation requirements, see attached sheet.<br />

Submit energy calculations for the shell. The energy<br />

Certificate of Compliance shall be a part of the plans.<br />

D. BEST MANAGEMENT PRACTICES<br />

1. Storm water provisions are required to be shown on the plans<br />

in accordance with the following requirements of exception<br />

14, section 106.4.1.<br />

a. Construction Projects - Small construction sites with less<br />

than two acres of disturbed soil and not located in<br />

designated hillside areas nor in or adjacent to an<br />

environmental sensitive areas shall implement the Best<br />

Management Practices (BMP) identified on attachment<br />

“A” entitled “Minimum Requirements for Construction<br />

Projects/Certification Statement”. In addition, attachment<br />

“A” shall be signed by the owner or an authorize agent of<br />

the owner.<br />

b. Priority Projects - Medium construction sites of two or<br />

more acres and up to, but less than five acres of disturbed<br />

soil shall prepare a local Storm Water Pollution Prevention<br />

<strong>Plan</strong> (SWPPP). The plans shall show all BMPs necessary<br />

to control and prevent discharge of sediments and other<br />

pollutants generated by the construction activities specific<br />

to each site, see Attachment “B” . Included as part of the<br />

SWPPP, the owner or authorized agent of the owner must<br />

sign the certification statement, attachment “1", and<br />

incorporate attachment “2" into the SWPPP. All sediment<br />

and pollution prevention measures identified on the plans<br />

shall be in place and maintained for the duration of the<br />

project or until no longer deemed necessary by the<br />

responsible City/County inspector.<br />

c. General Construction Permit Projects - Large construction<br />

sites with five acres or more disturbed soil are required to<br />

comply with the State General Permit for Construction<br />

Activity. This permits requires the submittal of a Notice of<br />

Intent to the State Water Resources Control Board and<br />

development of a state Storm Water Pollution Prevention<br />

<strong>Plan</strong>. The developer is required to show proof of these<br />

submittals.<br />

2. Note: An Wet Weather Erosion Control <strong>Plan</strong> (WWECP),<br />

utilizing sediment and erosion control BMPs, for projects that<br />

will leave disturb soil during the rainy season (October 1 to<br />

April 15) is required. The WWECP must be prepared, for<br />

projects that have already broken ground, not less than 30<br />

days priors to the beginning of each rainy season during which<br />

soil will be disturbed, and implemented throughout the entire<br />

rainy season. A copy of the WWECP shall be kept on the<br />

project site at all times beginning 30 days prior to the start of<br />

the rainy season through the end of the rainy season. For<br />

projects that will begin construction during the rainy season,<br />

the WWECP must be available 30 days before construction<br />

commences. The WWECP must be submitted to the Bureau of<br />

Engineering, Public Works for review and approval. The<br />

WWECP is not a requirement for the issuance of a building or<br />

grading permit.<br />

D. SITE PLAN<br />

1. The address of the building and the name and address of the<br />

owner and designer are required on the first sheet of the plans.<br />

2. Provide fully dimensioned plot plan to scale, in ink, or copied<br />

to the application plot plan sheet provided. Show building<br />

lines, easements, lot size, zone boundaries, highway<br />

dedication lines, street center line, alley, parking spaces, area<br />

separation walls, and location of all buildings. (Show type of<br />

construction, number of stories and use of all buildings.)<br />

Must agree with plot plan shown on plans. (106.3.2.1)<br />

3. Building projections into public properties must comply with<br />

Chapter 32.<br />

4. Note on the plans: "Temporary pedestrian protection shall be<br />

provided as required by Section 303.7<br />

5. Show on site plans finish floor, natural and grade elevations.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 3 of 23<br />

www.<strong>ladbs</strong>.org


6. Show location and distance of active and abandoned oil wells<br />

with respect to building perimeter.<br />

E. *PLANNING & ZONING<br />

If you cannot comply with circled corrections in this<br />

section, and instead, wish to obtain a discretionary<br />

approval from the Department of City <strong>Plan</strong>ning,<br />

please initiate the request for discretionary approval<br />

as soon as possible as the process may be timeconsuming<br />

due to the probable requirement of a<br />

public hearing.<br />

1. Number of dwelling units is excessive for lot area in the<br />

( ) Zone.<br />

2. A basement containing habitable rooms is considered a story<br />

for side yard, rear yard and number of stories.<br />

12.21C1(l), 12.21.1A8.<br />

3. Yards- Provide and dimension: ____________ front yard;<br />

____________ side yard; ___________ rear yard.<br />

4. Building exceeds (45' height) (3 times buildable area) limit(s)<br />

of Height District #1. Not limited as to number of stories.<br />

12.21.1.<br />

5. Provide ( ) paved parking spaces. A minimum of 1 space<br />

per unit shall be standard stall. 12.21A4, 5.<br />

6. Maximum driveway slope is 20%. Grade details and<br />

transition slopes are required where slope exceeds 12½%.<br />

Maximum driveway cross slope is 10%. Maximum slope<br />

within parking area is 5%. 12.21A5(g).<br />

7. Parking is not permitted in the required front yard, and 5'<br />

side yard along the side street lot line of a corner lot.<br />

12.21A6(a).<br />

8. Automobiles are not permitted to back onto a public street or<br />

sidewalk. 12.21A5(i)1.<br />

9. Provide parking design per the attached Building Department<br />

Standards. <strong>Plan</strong>s shall be drawn to an appropriate scale<br />

(suggest 1/8"=1') and be fully dimensioned to show aisle<br />

widths (including Fig 3 circulation driveway), stall widths<br />

(including increases for obstructions and end aisle stalls).<br />

12.21A5<br />

10. Walls - Parking and turning areas within 15' of a property line<br />

must be enclosed by a 5'-9" high wall*. A 3' high wall* is<br />

required where within 15' of the sidewalk. 12.21A6(d), (e),(f).<br />

*A concrete or masonry construction is required for parking<br />

areas.<br />

11. Maintain minimum 10'(20') separation between buildings.<br />

12.21C2(a).<br />

12. Provide a minimum 10'(12') passageway from the street to<br />

each dwelling unit and guest room. 12.21C2(b).<br />

13. Maximum eave projection of ( ) inches allowed in<br />

( ). 12.22C20(b).<br />

14. Projection of ( ) into the<br />

( ) yard/passageway<br />

(not permitted) (limited to<br />

). 12.22C2.<br />

15. (Fences) (<strong>Plan</strong>ters) (Retaining walls) shall not exceed a height<br />

of ( ) ft. above the natural ground level in required<br />

( ) yard. 12.22C20(f).<br />

16. Provide 30" minimum clear access around main building(s)<br />

and accessory living quarters. 12.22C20(l).<br />

17. Comply with the provisions of Specific <strong>Plan</strong> (<br />

).<br />

18. Zoning Information File No. ( ) requires that<br />

___________________________________________________<br />

___________________________________________________<br />

____________________________________________________<br />

19. For hotels and motels, provide a 400 sq ft loading zone with<br />

a 20' minimum length along the alley. 12.21C6(c).<br />

20. Provide a recycling room or area for 4 or more units.<br />

12.21A19(c).<br />

13. For development of over 5 units, Provide a total minimum<br />

usable open space on site of: 100 sq ft for each unit smaller<br />

than 3 habitable rooms; 125 sq ft for each unit of 3 habitable<br />

rooms; and 175 sq ft for each unit over 3 habitable rooms. (A<br />

kitchen is not counted in this section as a habitable room.)<br />

Sec.12.21G2<br />

a) Common open space shall be open to the sky and have no<br />

structures that project into the open space area and readily<br />

accessible to all residents of the site. Sec. 12.21G2(a)<br />

b) 400 ft 2 -15' min. Common open space shall have a<br />

minimum of 400 sf. with no horizontal dimension less than<br />

15 ft. Sec. 12.21G2(a)(1)(iii)<br />

c) At Grade Level: Common open space shall be located at<br />

grade level or first habitable room level, except for<br />

developments in R3, R4 and/or R5. Sec.12.21G2(a)(1)(iv).<br />

d) Obtain City <strong>Plan</strong>ning Approval: 25% of the common<br />

open space to be landscaped according to City <strong>Plan</strong>ning<br />

Standards.12.21G2(A)(3).<br />

22. Accessory building is not permitted on front half of lot,<br />

except when located minimum 55-ft from the front line or<br />

private garage located on sloping lot in accordance with<br />

12.21C5(l).<br />

12.21C5(b).<br />

23. Provide minimum 5-ft setback from rear property line ( 10'<br />

from alley center line ) and ( )_setback from side<br />

property line for accessory building containing recreation<br />

room or accessory living quarters. 12.21C5(e), (f), (g)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 4 of 23<br />

www.<strong>ladbs</strong>.org


24. No mezzanine is permitted within a recreation room.<br />

12.03<br />

PLANS & CALCULATIONS<br />

F. ACCESSIBILITY REQUIREMENTS<br />

1. For the State of California requirements, see separate<br />

correction sheet.<br />

G. SECURITY REQUIREMENTS<br />

Compliance with Chapter 67* is required at door(s) to<br />

individual units, at exterior doors to the main building, at<br />

doors between the R-1 and S-3 occupancies and at all doors to<br />

the Group B/F/M/R/S occupancy.<br />

General:<br />

1. All entry doors to dwelling units or guest rooms shall be arranged<br />

so that the occupant has a view of the area immediately outside<br />

the door without opening the door. Such view may be provided<br />

by a door viewer, through windows located in the vicinity of the<br />

door or through view ports in the door or adjoining wall. (6706)<br />

2.. Screens, barricades, or fences made of material which preclude<br />

human climbing shall be provided at every portion of every roof,<br />

balcony, or similar surface which is within 8 ft. of the utility pole or<br />

similar structures. (6707)<br />

Doors:<br />

3. Wood flush-type doors shall be 1 3/8" thick minimum with solid<br />

core construction. 91.6709.1 - Door stops of in-swinging doors shall<br />

be of one-piece construction with the jamb or joined by rabbet to the<br />

jamb. (6709.4)<br />

4. Every door in a security opening for an apartment house shall be<br />

provided with a light bulb (60 watt min.) At a maximum height of 8<br />

feet on the exterior. (6708)<br />

5. All pin-type door hinges accessible from outside shall have nonremovable<br />

hinge pins. Hinges shall have min. 1/4" dia. steel jamb stud<br />

with 1/4" min. protection. The strike plate for latches and holding<br />

device for projecting dead bolts in wood construction shall be secured<br />

to the jamb and the wall framing with screws no less than 2-1/2" long.<br />

(6709.5, 6709.7)<br />

6. Provide dead bolts with hardened inserts; deadlocking latch with<br />

key-operated locks on exterior. Locks must be openable from inside<br />

without key, special knowledge or special effort (latch not required in<br />

B, F, and S occupancies. (6709.2)<br />

7. Straight dead bolts shall have a min. throw of 1" and an<br />

embedment of not less than 5/8", and a hook-shaped or an<br />

expanding-lug deadbolt shall have a minimum throw of 3/4".<br />

(6709.2)<br />

8. The use of a locking system which consists of a deadlocking latch<br />

operated by a doorknob and a deadbolt operated by a non-removable<br />

thumb turn which is independent of the deadlocking latch and which<br />

must be separately operated, shall not be considered as a system which<br />

requires special knowledge or effort when used in dwelling units. The<br />

door knob and the thumb turn which operates the deadbolt shall not be<br />

separated by more than 8 inches.<br />

9. Wood panel type doors must have panels at least 9/16 in. thick<br />

with shaped portions not less than 1/4 in. thick and individual panels<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 5 of 23<br />

must be no more than 300 sq. in. in area. Mullions shall be considered<br />

a part of adjacent panels except mullions not over 18 inches long may<br />

have an overall width of not less than 2 inches. Stiles and rails shall be<br />

of solid lumber in thickness with overall dimensions of not less than<br />

1 3/8 inches and 3 inches in width. (6709.1 item 2 )<br />

10. Sliding doors shall be provided with a device in the upper channel<br />

of the moving panel to prohibit raising and removing of the moving<br />

panel in the closed or partially open position. (6710)<br />

11. Sliding glass doors shall be equipped with locking devices and<br />

shall be so constructed and installed that they remain intact and<br />

engaged when subjected to the tests specified in section 6717.1.<br />

12. Metal or wooden overhead or sliding doors shall be secured with<br />

a cylinder lock, padlock with a min. 9/32" diameter hardened steel<br />

shackle and bolted, hardened steel hasps, metal slide board, bolt or<br />

equivalent device unless secured electrically operated. (6711)<br />

13. Provide metal guides at top and bottom of metal accordion grate<br />

or grille-type doors and cylinder locks or padlocks. Cylinder guards<br />

shall be installed on all cylinder locks whenever the cylinder projects<br />

beyond the face of the door or is otherwise accessible to gripping<br />

tools. (6712)<br />

Glazing:<br />

14. In B, F, M, and S occupancies, panes of glazing with at least one<br />

dimension greater than 5 in. but less than 48 in, shall be constructed<br />

of tempered or approved burglary-resistant material or protected with<br />

metal bars or grilles. (6714)<br />

15. Glazed openings within 40" of the door lock when the door is in<br />

the closed position, shall be fully tempered glass or approved burglary<br />

resistant material, or shall be protected by metal bars, screens or grills<br />

having a maximum opening of 2". The provisions of this section shall<br />

not apply to view ports or windows which do not exceed 2" in their<br />

greatest dimensions. (6713)<br />

Windows:<br />

16. Louvered windows shall be protected by metal bars or grills with<br />

openings that have at least one dimension of 6" or less, which are<br />

constructed to preclude human entry. (6715.3)<br />

17. Other openable windows shall be provided with substantial<br />

locking devices. In B, F, M and S occupancies, such devices shall be<br />

glide bars, bolts, cross-bars, and/or padlocks with minimum 9/32"<br />

hardened steel shackles and bolted, hardened steel hasps. (6715.2)<br />

18. Sliding windows shall be provided with a device in the upper<br />

channel of the moving panel to prohibit raising and removing of the<br />

moving panel in the closed or partially open position. ( 6715.1)<br />

19. Sliding windows shall be equipped with locking devices and<br />

shall be so constructed and installed that they remain intact and<br />

engaged when subjected to the tests specified in (6717.2)<br />

20. Any release for metal bars, grills, grates or similar devices<br />

constructed to preclude human entry that are installed shall be located<br />

on the inside of the adjacent room and at least 24 inches from the<br />

closest opening through such metal bars, grills, grates or similar<br />

devices that exceeds two inches in any dimension. (6715.4)<br />

Openings other than Doors or Glazed Openings:<br />

21. All other openings must be protected by metal bars or<br />

grilles with openings of not less than 6 inches in one dimension.<br />

(67160<br />

13. Provide security lighting for garage and/or exterior parking<br />

area serving dwelling units or guestrooms and for recreation<br />

room, service rooms accessory to apartment houses, and at<br />

every door in a security opening. Security lighting shall have<br />

a surface illumination of 0.2 foot-candles at the floor level.<br />

www.<strong>ladbs</strong>.org


(6708, 6305, 12.21A5(k))<br />

H. SOUND REQUIREMENTS BETWEEN UNITS<br />

General<br />

In Group R Occupancies, wall and floor- ceiling assemblies<br />

separating dwelling units or guest rooms from each other and<br />

from public space such as interior corridors and service areas<br />

shall provide airborne sound<br />

insulation for walls, and both airborne and impact sound<br />

insulation for floor-ceiling assemblies. All such separating walls<br />

and floor-ceiling assemblies shall provide an airborne sound<br />

insulation equal to that required to meet a sound transmission<br />

class (STC) f 50 (45 if field tested). All separating floor-ceiling<br />

shall provide impact sound insulation equal to that required to<br />

meet an impact insulation class (IIC) of 50 (45 if field tested)<br />

(1208A.2).<br />

EXCEPTION: Impact sound insulation is not required for floorceiling<br />

assemblies over non-habitable rooms or spaces not<br />

designed to be occupied, such as garages, mechanical rooms or<br />

storage areas.<br />

1. Identify all sound rated partitions on the floor plans.<br />

2. Provide construction details for sound rated wall<br />

assemblies.<br />

3. Provide construction details for sound rated floor-ceiling<br />

assemblies<br />

4. All penetration into sound rated partitions or approved<br />

permanent resilient sealant. ~<br />

5. All rigid conduit, ducts, plumbing pipes, appliance vents<br />

located in sound assemblies shall be isolated from the building<br />

construction by means of resilient sleeves, mounts or minimum<br />

1/4" thick approved resilient material. vents located in sound<br />

assemblies shall be isolated from the building construction by<br />

means of resilient sleeves, mounts or minimum 1/4" thick<br />

approved resilient material<br />

6. An approved permanent, and resilient acoustical sealant<br />

shall be provided along the joint between the floor and the<br />

separation walls. ~ floor-ceiling assemblies shall be sealed,<br />

lined or insulated with<br />

7. Carpets or similar surface material which are part of the<br />

floor-ceiling assembly must be installed and inspected before<br />

the Certificate of <strong>Occupancy</strong> is issued and may be replaced only<br />

by other floor covering that provides the required impact sound<br />

insulation. (1208A.3)<br />

8. Metal ventilating and conditioned air ducts located in sound<br />

assemblies shall be lined. (Exception: Ducts serving only exit<br />

ways, kitchen cooking facilities, and bathrooms need not be<br />

lined).<br />

9. Mineral fiber insulation shall be installed in joist spaces<br />

whenever a plumbing piping, or duct penetrates a floor-ceiling<br />

assembly or where such unit passes through the plane of the<br />

floor-ceiling assembly from within a wall. The insulation shall be<br />

installed to a point 12" beyond the pipe or duct. This<br />

requirement is not applicable to fire sprinkler pipe, gas line or<br />

electrical conduit. ~<br />

10. Electrical outlet boxes in opposite faces of separation walls<br />

shall be separated horizontally by 24" and note that back and<br />

sides of boxes will be sealed with 1/8" resilient sealant and<br />

backed by a minimum of 2" thick mineral fiber insulation. (TV,<br />

telephone and intercom outlets must be installed in boxes<br />

accordingly.)~<br />

11. The entrance doors to residential units from interior<br />

corridors are required to have a minimum STC rating of 26.<br />

(Laminated 1 3/4" solid-core doors with resilient stops and<br />

gaskets or 18 gauge insulated steel slab doors with<br />

compression seals all around, including thresholds will meet this<br />

requirement). (1208A.2).<br />

12. Wall mounted lavatories and toilets are not permitted on<br />

sound rated partitions. ~<br />

I. AREA AND OCCUPANCY<br />

1. Show on the plans the proposed number of stories, occupancy<br />

group(s), type(s) of construction and area justification for this<br />

structure. Vent shafts and courts do not count as area. The<br />

mezzanine floor area must be included in the area of the story<br />

in which it is located. The basement need not be included in<br />

the total allowable area if it does not exceed the area permitted<br />

for a one-story building. Provide an area breakdown by level.<br />

2. Exterior (court) (bearing) (nonbearing) walls within<br />

feet of property lines must be of hour<br />

construction. (503.2)<br />

3. Provide minimum 30" high parapet on the ( )<br />

exterior walls. (709.4)<br />

4. Openings in exterior (court) walls within feet of<br />

property lines (must be protected with three-fourths-hour fire<br />

assemblies) (not permitted). (503.2)<br />

5. Limit openings to 50% of the area of any exterior wall where<br />

protected openings are required. (503.2.2)<br />

6. The building as shown is a mixed-occupancy building. The<br />

sum of the ratios of the actual area for each separate<br />

occupancy divided by the total allowable area for separate<br />

occupancy must not exceed one. ( 504.3)<br />

7. A property line must be assumed between buildings on the<br />

same property(court walls) to determine wall and opening<br />

protection requirements. ( 503.3)<br />

8. The total floor area must be limited to______ square feet,<br />

including increase of _______ percent for ______________-<br />

foot yards, 100 percent for multistory buildings and doubling<br />

(tripling in one-story buildings) for sprinkler through-out.<br />

(504 & 505)<br />

8. The floor area of the 2 nd floor between area separation walls<br />

shall not exceed 3000 sq. ft., otherwise 1 hour construction<br />

shall be provided. (310.2.2)<br />

9. Unobstructed yards of feet must be maintained on<br />

sides of the building to permit a Percent<br />

floor area increase. (505)<br />

10. Complete and return the attached yard Affidavit as part of the<br />

area justification.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 6 of 23<br />

www.<strong>ladbs</strong>.org


11. Clearly identify on the plans, provide details for and show<br />

the required opening protection for the following:<br />

a. The 1-hour occupancy separation between the R-1 and<br />

Occupancies.<br />

(302.3,T-3-B)<br />

b. The 3-hour occupancy separation between the R-1 and<br />

S-3 occupancies. (302.3,311.2.2.1,T-3-B)<br />

c. The ____hour area separation wall(s). (504.6)<br />

d. Show location of all area separation walls on plot,<br />

floor, foundation, and roof plans.<br />

12. Show maximum height of the structure on all elevation views.<br />

13. This structure is of type construction. Show on the<br />

plans the required roof, exterior wall<br />

construction, structural frame protection, and floor<br />

construction.<br />

(T-6-A)<br />

14. Ducts through two-hour area separation walls require dampers.<br />

15. Projections beyond the exterior wall must not extend beyond:<br />

a. A point one-third the distance to the property line from an<br />

exterior wall. (503.2.1)<br />

b. A point one-third the distance from an assumed vertical<br />

plane located where fire- resistive protection of openings<br />

is first required due to location on property.<br />

(503.2.1 & 705)<br />

c. A point more than 12" into area when openings are<br />

prohibited. ( 503.2.1)<br />

16. Exterior exit stairways, balconies and ramps must not project<br />

into yards where wall openings are not permitted or must be<br />

protected.<br />

17. Horizontal occupancy separation must be supported with a<br />

structural system having equivalent fire-resistive protection.<br />

(302.2)<br />

18. Vertical occupancy separations must afford a complete<br />

separation and must extend through underfloor and attic areas,<br />

including areas where fire-resistive ceilings are specified.<br />

( 302.2)<br />

19. Provide detail to show that (2) hour area separation<br />

walls will comply with Section 504.6<br />

a. Extend vertically from the foundation to a point 30 inches<br />

above the roof. (504.6.4)<br />

b. Total width of all openings limited to 25 percent of the<br />

wall length in the story under consideration. (504.6.2)<br />

c. All openings to be protected with fire assemblies having a<br />

fire-resistive rating of (1-1/2) (3) hours.<br />

d. Ducts through area separation walls should be avoided. If<br />

allowed duct penetrations should be protected as required<br />

in 713.11.<br />

20. Fire blocking must be provided in accordance with Section<br />

708.2.1 in the following locations:<br />

a. In concealed spaces of stud walls and partitions, including<br />

furred spaces, at the ceiling and floor levels.<br />

b. In concealed spaces of stud walls and partitions, including<br />

furred spaces, at 10-foot intervals along the length of the<br />

wall.<br />

c. At all interconnections between concealed vertical and<br />

horizontal spaces such as occur at soffits, drop ceilings and<br />

covered ceilings.<br />

d. In concealed spaces between stair stringers at the top and<br />

bottom of the run and between studs along and in line with<br />

the run of stairs if the wall under the stairs is unfinished.<br />

e. In openings around vents, pipes, ducts, chimneys,<br />

fireplaces and similar openings which afford a passage for<br />

fire at ceiling and floor levels, with noncombustible<br />

materials.<br />

21. Draft stops must be provided in the following locations:<br />

a. In the attics, mansards, overhangs, false fronts set out from<br />

walls and similar concealed spaces, and in floor-ceiling<br />

assemblies. Draft stops shall be in line with walls<br />

separating individual dwelling units and guest rooms from<br />

each other and from other uses. The separated attic space<br />

cannot exceed 3000 sq. ft and the greatest horizontal<br />

dimension cannot exceed 60 ft. (708.3.1-1.2, 708.3.1.2.1,<br />

1505.7)<br />

b. Show draft-stop construction on the plans. Draft-stopping<br />

materials must not be less than ½-inch gypsum board, 3/8-<br />

inch plywood, 3/8-inch Type 2-M particle board or other<br />

materials approved by the building department. Draftstopping<br />

must be adequately supported. ( 708.3.1.3)<br />

22. Members providing vertical support for concrete or masonry<br />

in upper story require 1-hour fire resistive protection. ( 704.4)<br />

23. Exterior stairs must be constructed of As<br />

specified in Section 602.4. (603.4) (604.4) (605.4) (606.4)<br />

24. No openings other than required exits are permitted in walls<br />

of exit passageways. The passageways must be of<br />

- hour fire-resistive construction. Openings must be<br />

protected with labeled three-fourths-hour fire assemblies.<br />

( 1011.1)<br />

25. An automatic sprinkler system is required in all buildings 3<br />

stories or more in height or containing 5 or more dwelling<br />

units. Note on plan sheet “This building and garage<br />

must be equipped with an automatic fire extinguishing<br />

system.” (904.2.9)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 7 of 23<br />

www.<strong>ladbs</strong>.org


26. Exceptions to, or reductions in building code requirements<br />

based on the installation of automatic fire extinguishing<br />

system is not allowed when utilizing NFPA-13R type<br />

residential sprinkler system allowed for R- occupancies four<br />

stories or less in height. 904.1.3, 505.3, 506, 508.<br />

27. Envelope ceilings must satisfy the following conditions of<br />

Section 704.2.6<br />

a. Envelope ceilings must not be used to provide fire<br />

protection for beam and girders supporting more<br />

than one floor or roof.<br />

b. Columns must be individually fire protected.<br />

c. The areas of openings for copper, sheet steel and ferrous<br />

plumbing pipes must be limited to 100 square inches in<br />

each 100 square feet of ceiling area. Duct openings<br />

must be protected by approved ceiling fire dampers.<br />

d. Individual electrical outlet boxes must be of steel and<br />

not greater than 16 square inches in area.<br />

28. Combustible materials framed into a fire-resistive wall must<br />

have one half the required wall thickness as end protection.<br />

( 709.2)<br />

29. In fire-resistive exterior wall construction, the fire-resistive<br />

rating must be maintained for such walls passing through attic<br />

areas. ( 709.3)<br />

30. Penetrations in walls requiring protected openings must be fire<br />

stopped with an approved material in accordance with Section<br />

709.6. Space between penetrating materials (described below)<br />

must be designed to prevent the movement of hot flame or<br />

gases.<br />

a. Copper or ferrous pipes or conduits may penetrate the<br />

walls or partitions, provided they are fire stopped.<br />

b. Openings for steel electrical outlet boxes not exceeding<br />

16 square inches are permitted provided openings do not<br />

aggregate more than 100 square inches or 100 square<br />

feet of wall or partitions. Outlet boxes on opposite sides<br />

of walls or partitions must be separated by a horizontal<br />

distance of 24 inches.<br />

c. Where walls are penetrated by the other materials or<br />

where larger openings are required than permitted in (b)<br />

above, they must be qualified by tests conducted in<br />

accordance with Section 703.2.<br />

32. Show the location on the plans.<br />

Class I, II or III standpipe (dry, wet, combination) are<br />

required in this building. Hose size is respectively 2 ½",<br />

1 ½" outlets for the sprinkler system. (904.5.1 thru 5, T-9-A)<br />

33. The Type I parking structure permitted by section 311.2.2 is<br />

a story rather than a basement. This structure is 4 stories in<br />

height and requires sprinklers throughout (904.2.2-5)<br />

.<br />

34. This structure has Atrium(s). Show that the<br />

requirements of Section 402 are satisfied. (402.1 thru 10)<br />

35. All openings in an exterior wall below and within 10 ft.<br />

measured horizontally, of an exterior exit stairway serving<br />

buildings over two stories in height shall be protected by fixed<br />

or self-closing assembly having 3/4 -hr. fire protection rating,.<br />

Openings may be unprotected when two separated exterior<br />

stairways serves an exterior exit balcony. (1006.3.3.3)<br />

36. Pressurized enclosures are required for all exits in buildings<br />

having floors used for human occupancy located more than 75<br />

ft. above the lowest level of Fire Department vehicle access.<br />

(1005.3.3.7)<br />

37. The exit passageway requires hour construction<br />

for walls, floor and ceiling. Walls shall be without openings<br />

except for required exits. Exit openings through enclosing<br />

walls shall be ______ hour rated. (1005.3.4.3, 1005.3.4.4)<br />

J. MEANS OF EGRESS<br />

1. In determinating the occupant load, all portions of a building<br />

shall be presumed to be occupied at the same time except for<br />

accessory use areas that ordinarily are used only by persons<br />

who occupy the main area. ( 1003.2.2.2.1)<br />

2. For areas without fixed seats, the occupant load shall not be<br />

less than the number determined by dividing the floor area<br />

under consideration by the occupant load factor. (Table 10-A)<br />

3. For areas having fixed benches or pews, the occupant load<br />

shall not be less than the number of seats based on one person<br />

for each 18 inches (457 mm) of length of pew or bench.<br />

Where fixed booths are used in dining areas, the occupant<br />

load shall be based on one person for each 24 inches (610<br />

mm) of booth length. Where fixed benches, pews or booths<br />

are curved, the larger radius shall determine the booth length.<br />

(1003.2.2.2.3)<br />

31. Smoke and fire dampers must be installed in the following<br />

locations per Section 713.11:<br />

a. Duct penetrations of area or occupancy separation walls<br />

with ratings of two hours or less.<br />

b. Ducts passing through horizontal exit walls.<br />

c. Ducts penetrating shafts (see exception).<br />

d. Ducts penetrating fire-resistive elements of fire-rated<br />

corridor walls. See exception for steel ducts with no<br />

openings into corridor.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 8 of 23<br />

4. All exit doors serving an occupant load of 10 or more, along<br />

the path of exit travel anywhere in a means of egress system<br />

shall comply with the requirements of Section (1003.3.1)<br />

a. Revolving, sliding and overhead doors shall not be used<br />

as required exit doors. (1003.3.1.2)<br />

www.<strong>ladbs</strong>.org


. All required exit doors shall be not less than 3 ft. wide<br />

6'-8" high, shall have a clear exit way width of not less<br />

than 32" and shall be capable of opening 90 degrees.<br />

The maximum door leaf width is 4 feet when serving an<br />

occupant load of 10 or more. (1003.3.1.3a) & (1003.3.1.4)<br />

c. Exit doors shall be of the pivoted, balanced or sidehinged<br />

swinging type. (1003.3.1.5)<br />

5. Swing door(s) in the direction of travel. OL>50<br />

(1003.3.1.5)<br />

6. The path of exit travel to and within exits in this building shall<br />

be identified by exit signs conforming to the requirements of<br />

Section 1003.2.8. Exit signs shall be readily visible from any<br />

direction of approach. Exit signs shall be located as necessary<br />

to clearly indicate the direction of egress travel. No point<br />

shall be more than 100 feet (30480 mm) from the nearest<br />

visible sign. (1003.2.8.2)<br />

7. Exit signs shall be internally or externally illuminated. When<br />

the face of an exit sign is illuminated from an external source,<br />

it shall have an intensity of not less than 5 foot candles (54<br />

(Ix)) from either of two electric lamps. Internally illuminated<br />

signs shall provide equivalent luminance and be listed for the<br />

purpose. (1003.2.8.4)<br />

8. The exit signs shall also be connected to an emergency<br />

electrical system provided from storage batteries, unit<br />

equipment or an on-site generator set, and the system shall be<br />

installed in accordance with the Electrical Code. For high-rise<br />

buildings, see Section 403. (1003.2.8.5)<br />

14. Elevators or escalators shall not be used as a required means<br />

of egress component. (1003.2.7)<br />

15. Exit doors shall be openable from the inside without the use<br />

of a key, special knowledge or effort. Flush bolts or surface<br />

bolts are prohibited. “Applies also to exit gates”. The<br />

unlatching of any leaf shall not require more than one<br />

operation. (1003.3.1.8)<br />

16. Show that the exit hardware on the exterior exit doors of this<br />

building satisfies the requirements of Section 1003.3.1.9.<br />

17. Double-acting door must not be used as exits where serving an<br />

occupant load of more than 100 (the door is part of a fire<br />

assembly) (the door is a part of a smoke- and draft-control<br />

assembly) (panic hardware is required or provided).<br />

(1003.3.1.5)<br />

18. Double-acting doors must have a view panel of not less than<br />

200 square inches. (1003.3.1.5)<br />

19. This structure has ramps. Provide enough details<br />

to show that the width, slope, landings and handrails satisfy<br />

the requirements of section 1003.3.4. (1003.1.3.1.6)<br />

20. Exiting through more than one intervening room is not<br />

permitted for an occupant load of more than 10. (1004.2.2)<br />

21. Post a sign adjacent to the required main exit door with 1"<br />

lettering stating: “ THIS DOOR MUST REMAIN<br />

UNLOCKED DURING BUSINESS HOURS.” Main exit<br />

only. (1003.3.1.8)<br />

9. The power supply for means of egress illumination shall<br />

normally be provided by the premises of electrical supply. In<br />

the event of its failure, illuminator shall be automatically<br />

provided from an emergency system for Group I, Divisions<br />

1.1 and 1.2 Occupancies and for all other occupancies where<br />

the means of egress system serves an occupant load pf 100 or<br />

more. (1003.2.9.2)<br />

10. Exits must have a minimum separation of one half the<br />

maximum overall diagonal of the building or area served<br />

measured in a straight line between exits. (1003.3)<br />

11. All exits must be continuous and terminate in a public way or<br />

exit court leading to a public way. (1001.1)<br />

12. All exterior elevation changes and interior elevation changes<br />

of 12 inches (305 mm) or more along the path of exit travel<br />

shall be made by steps, stairs or stairways conforming with<br />

the requirements of Section 1003.3.3.3 or ramps conforming<br />

with the requirements of Section 1003.3.3.4. (1003.2.6)<br />

13. Interior elevation changes of less than 12 inches (305 mm)<br />

along the path of exit travel serving an occupant load of 10 or<br />

more shall be by ramps conforming with the requirements of<br />

Section 1003.3.4. (1003.2.6)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 9 of 23<br />

22. <strong>Plan</strong>s must indicate the floor or landing on each side of doors<br />

is not more than 1/2 (1) inch lower than the threshold of the<br />

doorway. (1003.3.1.6)<br />

23. When a door opens over a landing, the landing shall have a<br />

length of not less than (36")(44")(60" HCD) and be not more<br />

than ½" below the threshold. 1" is OK if access is not<br />

required.<br />

(1003.3.1.6&7)<br />

24. Doors shall not project more than 7" into the required corridor<br />

width when fully opened, or more than one half into the<br />

required exit when in any position. Provide details showing<br />

compliance. (1003.3.1.7 & 1004.3.3.2)<br />

25. Dead end corridors and exit balconies must not exceed 20 feet.<br />

( 1004.2.6)<br />

26. Details of the stairway are required (1003.3.3)<br />

showing:<br />

a. A maximum 7" rise and minimum 11" run (tread).<br />

(1003.3.3.3)<br />

b. A minimum headroom over the stairs of 6'-8."<br />

(1003.3.3.3)<br />

c. A minimum (36") (44") clear width.<br />

(1003.3.3.2)<br />

www.<strong>ladbs</strong>.org


d. Handrails at all stairways with two or more risers, on<br />

the open, one or both sides.<br />

e. Handgrip portion of handrail shall not be less than 1 ¼"<br />

nor more than 2" cross-section diam. Dimension having<br />

a smooth surface with no sharp corners. (1003.3.3.6)<br />

f. A handrail height 34" to 38" above the nosing, 1 ½"<br />

clearance to the wall, 2" max. width and ends returned<br />

to the wall. The open side shall have intermediates<br />

rails or balusters spaced 4" maximum.(Less than 4"<br />

clear spacing)<br />

g. Handrails designed for 20 or 50 lbs./ft. lateral load.<br />

(T-16-B)<br />

h. One handrail extending 12" beyond the top and bottom<br />

riser.<br />

i. Stairway framing, footing, connections and bracing.<br />

j. One-hour construction for the enclosed usable space<br />

under the stairs. (1003.3.3.9)<br />

k. A stair width complying with section 1003.2.3 but not<br />

less than 44" for OL > 50, 36" for OL < 50.<br />

(1003.3.3.2)<br />

l. Stairway landing(s) (36") (44"). (1003.3.3.5)<br />

27. Spiral stairways shall not serve as required exit for an area<br />

exceeding 400 sq. ft. (1003.3.3.8.2)<br />

28. Submit drawings for spiral stairway showing compliance<br />

with Section 1003.3.3.8.2.<br />

29. Provide spiral stairway column base connection / footing<br />

detail.<br />

30. Provide sufficient details of the winding stairway to show<br />

compliance with Section 1003.3.3.8.2.<br />

31. For glass handrails and guardrails, without vertical supports,<br />

submit test report from a recognized testing agency showing<br />

that the glass and base connections shown on the plan are<br />

adequate for the required 20 or 50 lbs./ft lateral load.<br />

(T-16-B)<br />

32. The means of egress system shall have a clear height of not<br />

less than 7 feet (2134 mm) measured vertically from the<br />

walking surface to the lowest projection from the ceiling or<br />

overhead structure. (1003.2.3.4)<br />

33. The second story requires two exits. Occupant load > 10.<br />

(1004.2.3.2)<br />

34. Two exits, separated by feet at the floor and/or<br />

roof are required. (1004.2.3.2)<br />

35. A barrier in the exit enclosure is required to prevent<br />

accidental entry into the basement. (1005.3.3.4)<br />

36. Structures four (4) or more stories in height shall have an<br />

approved stairway sign indicating the floor level, terminus of<br />

the top and bottom of the stair and the identification number<br />

of the stair. It shall be located approximately 5 ft. above the<br />

floor landing and be readily visible when the stair doors are<br />

in an open or closed position. (1003.3.3.13, UBC Std. 10-2)<br />

37. Exit enclosure required for all interior public stairways.<br />

Enclosure shall be continuous until egress is provided from<br />

building. (1005.3.3.1a)<br />

a) One required stairway shall extend to the roof of<br />

buildings four or more stories in height. (1003.3.3.11)<br />

b) Stair construction shall comply with T 6-A.<br />

(1005.3.3.2)<br />

c) All openings to be protected by (1) (1 1 / 2 ) - hour self<br />

closing fire assemblies. No openings other than exit<br />

doorways and exterior wall openings are permitted.<br />

(1005.3.3.5)<br />

d) Provide barrier at exit level between upper story and<br />

basement. (1005.3.3.4 )<br />

e) Space under stairway shall not be used for any purpose.<br />

(1005.3.3.6)<br />

f) All exit enclosures four or more stories shall be of two<br />

hour construction. (1005.3.3.2)<br />

38. Show stairway landing details.<br />

a) Landing dimension in the direction of travel must equal<br />

the required width of the stairs. (1003.3.1.7)<br />

2. Swinging doors shall not reduce required landing width<br />

to less than one half. (1003.3.1.7)<br />

3. When door opens over landing, the landing shall have<br />

a length of not less than 44 inches. (1003.3.1.7)<br />

4. Maximum vertical distance between landings is 12 ft.<br />

(1003.3.3.5 )<br />

39. There shall not be enclosed usable space under interior<br />

stairways or ramps in an exit enclosure, and exterior<br />

stairways. The open space under such stairways shall not be<br />

used for any purpose. (1005.3.3.6, 1006.3.3.2)<br />

40. Provide floor-level exit signs in all corridors serving guest<br />

rooms of hotels where exit signs are required by Section<br />

1003.2.8.2. (1007.6.2)<br />

41. Where an exit passageway is used and more than one exit is<br />

required, dead ends shall not exceed 20 feet in length.<br />

(1005.3.4.6)<br />

42. Opening into exit passageways shall be limited to those<br />

necessary for egress from normally occupied spaces.<br />

is not considered as normally occupied space.<br />

Elevators shall not open into an exit passageway.<br />

(1005.3.4.4)<br />

43. Where an exit passageway is used and more than one exit is<br />

required, dead ends shall not exceed 20 feet in length.<br />

(1005.3.4.6)<br />

44. If occupant load is 50 or more, the minimum clear width of<br />

corridor is 44 inches. (1004.3.4.2)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 10 of 23<br />

www.<strong>ladbs</strong>.org


45. Handrails and doors, when fully opened, shall not reduce the<br />

required corridor width by more than 7 inches. Doors in any<br />

position shall not reduce the required width by more than one<br />

half. The width shall not be reduced by non-structural<br />

projection by more than 1 ½” on either side. (1004.3.4.2)<br />

46. Corridors require 1-hour rated walls and ceiling construction<br />

when occupant load is 10 or more OL$10. Provide details,<br />

properly referenced, at all corridors. (1004.3.4.3.1)<br />

47. Door(s) located in a 1-hour corridor shall be<br />

protected by a 20-minutes tight fitting, self-closing smoke<br />

and draft control door and frame assembly which bears an<br />

approved label followed by the letter “S”. (1004.3.4.3.2.1)<br />

48. Windows in corridor walls shall be protected by fixed glass<br />

of 3/4 hour rating in steel frames. The total area of window<br />

in a corridor shall not exceed 25% of the area of a common<br />

wall with any room. (1004.3.4.3.2.2)<br />

49. Both smoke and fire dampers are required for duct openings<br />

in corridors. (1004.3.4.3.2.3)<br />

50. Provide 36" (42") high guardrail at ( ) with less<br />

than 4" clear spacing between intermediate rails. (509.2.3)<br />

51. Ramp slopes shall not exceed one foot in 8 feet (12 feet)<br />

(1003.2.5)<br />

52. Exterior stairs and exit balconies shall not project into areas<br />

where protected openings are required. (1006.2.1)<br />

53. Parking spaces shall not obstruct required exits. (1001.3)<br />

K. GENERAL REQUIREMENTS<br />

1. Submit structural calculations to justify the adequacy of the<br />

structural system for seismic, wind, dead and live loads.<br />

2. Each sheet of the architectural and structural plans must bear<br />

the signatures, registration number and expiration date of an<br />

architect or engineer registered in the State of California.<br />

3. The ( Soils engineer ) (Geologist) shall review and approve<br />

the detailed plans prior to issuance of any permit.<br />

4. Delete notes and details on sheets that do not<br />

apply.<br />

5. Specifications must be provided for all construction<br />

materials. (106.3.2)<br />

6. Toilet room floors shall have a smooth, hard non-absorbent<br />

surface such as Portland cement, ceramic tile or other<br />

approved material that extends upward onto the walls at<br />

least 5 inches (127 mm). (807.1.1)<br />

7. Walls within 2 feet (610 mm) of the front and sides of urinals<br />

and water closets shall have a smooth, hard non-absorbent<br />

surface of Portland cement, concrete, ceramic tile or other<br />

smooth, hard non-absorbent surface to a height of 4 feet<br />

(1219 mm), and except for structural elements, the materials<br />

used in such walls shall be of a type that is not adversely<br />

affected by moisture. (807.1.2)<br />

8. According to Section 2512, when gypsum is used as a base<br />

for tile or wall panels for tub, shower or water closet<br />

compartment walls, water resistant gypsum backing board<br />

shall be used. Regular gypsum wallboard is permitted under<br />

tile or wall panels in other wall and ceiling areas when<br />

installed in accordance with Table 25-G. Water-resistant<br />

gypsum board shall not be used in the following locations:<br />

a. Over a vapor retarder.<br />

b. In areas subject to continuous high humidity, such as<br />

saunas, steam rooms or gang shower rooms.<br />

c. On ceilings where frame spacing exceeds 12 inches<br />

(305 mm) on center.<br />

9. All shower compartments, regardless of shape, shall have a<br />

minimum finished interior area of not less than 1024 square<br />

inches (0.66 m 2 ) and shall be capable of encompassing a 30<br />

inch (0.76 m) circle. The minimum area and dimensions<br />

shall be maintained to a point 70 inches (1.8 m) above the<br />

shower drain outlet. (P.C. 410.4)<br />

10. Separation is required between food preparation area<br />

(including food storage rooms) and toilet room by a tight<br />

fitting door. (302.6)<br />

11. Each light of safety glazing material installed in hazardous<br />

locations as defined in section 2406.4 shall be identified by<br />

a permanent label that specifies the labeler, and states that<br />

safety glazing material has been utilized in such installations<br />

6. Details of the guardrails at the floor and roof openings,<br />

occupied roofs and balconies or porches more than 30" above<br />

grade are required. Guardrails shall be 42" in height, have<br />

intermediate rails or balusters spaced at 4" maximum and be<br />

designed for 20 or 50 lbs./ft. lateral load. (T-16-b) (509.1)<br />

7. Toilet rooms shall be provided with a fully openable exterior<br />

window with an area not less than 3 square feet (0.279 m 2 ),<br />

or a vertical duct not less than 100 square inches (64,516<br />

mm 2 )in area for the first water closet plus 50 square inches<br />

(32,258 mm 2 ) additional of area for each additional water<br />

closet, or a mechanically operated exhaust system capable of<br />

providing a complete change of air every 15 minutes. Such<br />

mechanically operated exhaust system shall be connected<br />

directly to the outside, and the point of discharge shall be at<br />

least 3 feet (914 mm) from any opening that allows air entry<br />

into occupied portions of the building.<br />

(1202.2.1)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 11 of 23<br />

www.<strong>ladbs</strong>.org


8. Indicate on plans that interior finish materials applied to wall<br />

and ceilings shall be tested as specified in Section 802. In<br />

addition, provide details showing application in accordance<br />

with Section 803, 804, and Table 8A & 8B.<br />

9. The flame-spread rating of paneling materials on the walls<br />

of the corridor, lobby and exit enclosure must be<br />

class<br />

. Clearly indicate on the plans.<br />

(T-8-B)<br />

10. Clearly indicate on the plans if the skylights are glass or<br />

plastic. Show that the requirements of Chapter 24 or 26 are<br />

satisfied.<br />

11. Glass skylights shall comply with Section 2409. Plastic<br />

skylights shall comply with Section 2603.7.1.<br />

12. Provide veneer details. Show method of anchorage, size and<br />

spacing of anchors. Type of backing to comply with Section<br />

1403.<br />

13. Note on the plans: “A fire alarm system is required for this<br />

structures. <strong>Plan</strong>s for the fire alarm system must be submitted<br />

to the Fire Department for approval prior to installation.”<br />

Required for:<br />

a. Apartment buildings three or more stories in height or<br />

containing more than 15 units.<br />

b. Hotels three or more stories in height, or containing 20<br />

or more guest rooms. (310.14.12.1)<br />

20. Show on the plans the location of the descriptive diagram<br />

indicating the identification patter and location of each<br />

dwelling unit in the apartment house or complex. Required<br />

for 6 or more units.<br />

21. This structure is required to have 3 approved recording<br />

accelerographs. Show the locations on the plans. (Appendix<br />

Chap. 16 Div. II)<br />

22. This building is of Type I construction and requires special<br />

fire and life safety features. Provide complete plans and<br />

specification. (401.3 thru 403,10 & 602)<br />

23. Provide, on the plans, details of the suspended ceiling that<br />

conform to the requirements of the section 2504.<br />

24. Wood structures three and four stories in height suffer<br />

breakage of plumbing pipes due to wood shrinkage. Clearly<br />

indicate on the plans how this problem is going to be<br />

addressed. (PCM 313.2)<br />

25. Provide “36/42" inch high (minimum) protective guardrail for<br />

decks, porches, balconies and raised floors (when more than<br />

30 inches above grade or floor below), and open side(s) of<br />

stair landings. Opening between balusters/ rails shall preclude<br />

passage of 4 inch diameter sphere. (509)<br />

26.Show attic ventilation type, size, and location. The required net<br />

ventilation area ratio is 1/150 of attic area or 1/300 of attic area<br />

if at least half of the vent area is located more than 3 feet above<br />

eave vents with the balance of the required ventilation provided<br />

by the eave vents. Openings shall have 1/4 inch corrosion<br />

resistant metal mesh covering. (1505.3)<br />

27.Show underfloor net ventilation opening size and locations<br />

equal to 1 sq. ft. for each 150 sq. ft. of under floor area.<br />

Openings shall be as close to corners as practicable and shall<br />

provide cross ventilation along the length of at least two<br />

opposite sides. Opening shall have 1/4 inch corrosion resistant<br />

metal mesh covering. (2306.7)<br />

28.Where planter boxes are installed adjacent to wood frame walls<br />

a 2-inch-wide air space shall be provided between the planter<br />

and the wall. Flashings shall be installed when the air space is<br />

less than 6 inches in width. (2306.8)<br />

29.This plan contains<br />

courts. See plan for location.<br />

Call out dimensions of the courts. Provide details of the<br />

proposed wall construction, opening protection and stair<br />

protection. (204, 503.3, T5-A, 1203.4.3, 1006.3.5)<br />

30.For interior courts more than 2 stories in height, the following<br />

is required:<br />

a. Provide access to the bottom for cleaning purposes.<br />

b. Provide a horizontal air intake at the bottom not less than 10<br />

sq. ft. in area. The intake shall be at least 1-hr. construction<br />

and shall be lead to the exterior of the building unless<br />

abutting a yard or public space.<br />

31.This plan contains<br />

shafts. See plans for location.<br />

Provide details of the 1-hr./2-hr. wall construction and on the<br />

door) schedule provide 1-hr./ 1 ½ hr. opening protection.<br />

(711-1, T6-A, 711.4)<br />

32.A vent is required at an elevator shaft extending through more<br />

than two stories. The venting area shall be 3 ½ percent of the<br />

shaft area but no less than 3 sq. ft. per elevator. (3004)<br />

33.Provide notes on <strong>Plan</strong> Sheet<br />

Stating all the<br />

provisions of Chapter 30 that the elevators in this structure<br />

must satisfy. Reference to Code sections is not acceptable.<br />

34.Rubbish and/or linen chutes and termination rooms shall be<br />

separated from the remaining of the building by a 1-hour<br />

occupancy separation or as required for the shaft enclosure.<br />

(711.5)<br />

35.Openings into trash chutes shall not be located in corridors or<br />

stairways. Separation may be by an intervening vestibule with<br />

all openings protected. (711.5)<br />

36.Sprinkler heads are required in trash and linen chutes extending<br />

through three or more floors. Provide a section view through<br />

the shaft. (904.2.2.2)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 12 of 23<br />

www.<strong>ladbs</strong>.org


37.The mezzanine(s) on <strong>Plan</strong> Sheet(s)<br />

does<br />

not/do not satisfy the definition given in Section 214 and 507.<br />

This is a story.<br />

38.Combustible material (wood) in ducts and return air plenums<br />

shall have a flame-spread rating # 50. Clearly note on the<br />

plans. (M.C. 601.4)<br />

39.Required 1-hr. corridors (including the space above the<br />

dropped ceiling) shall not be used as a return air plenum for<br />

circulating air.<br />

(M.C.601.1.1)<br />

40.No mechanical duct penetration are permitted (except for those<br />

serving the exit enclosure) through exit enclosure walls or<br />

ceiling. (1005.3.3.5)<br />

2. Smoke detectors shall be provided as follows: ( 310.9.1.3,4)<br />

a) In new construction smoke detectors shall receive their<br />

primary power source from the building wiring and shall be<br />

equipped with battery back up and low battery signal.<br />

Smoke detectors shall be located in each sleeping room &<br />

hallway or area giving access to a sleeping room, and on<br />

each story and basement for dwellings with more than one<br />

story.<br />

b) In existing construction smoke detectors may be battery<br />

operated, installed in location as specified in a) above. -~<br />

3. Provide smoke detectors at the top of common stairwells<br />

serving two or more tenants. (Health and Safety Code<br />

13113.7)~<br />

41.Smoke and fire dampers are required at duct penetration of area<br />

or occupancy separations walls, horizontal exit walls, fire-rated<br />

shafts, fire-resistive floor-ceiling or roof ceiling assemblies,<br />

and fire-rated corridor walls or ceilings when any extension of<br />

the ducts leads to an opening into the corridor. Show all<br />

dampers on the mechanical plan. (713.11)<br />

42.Note on the plan “ The construction shall not restrict a fivefoot<br />

clear and unobstructed access to any water or power<br />

distribution facilities (Power poles, pull-boxes, transformers,<br />

vaults, pumps, valves, meters, appurtenances, etc.) or to the<br />

location of the hook-up. The construction shall not be within<br />

ten feet of any power lines-whether or not the lines are<br />

located on the property. Failure to comply may cause<br />

construction delays and/or additional expenses.”<br />

43.<br />

44.Walls and floors separating dwelling units in the same building<br />

shall not be less than 1-hour fire resistive construction. Clearly<br />

identify on the plans and provide details showing how fire<br />

resistive rating will be provided.<br />

45.Note on the plan “ All elevator pits shall be equipped with<br />

a drain to prevent the accumulation of water. The water<br />

and other liquids collected in the bottom of an elevator<br />

shaft may not be discharged to the sanitary sewer or<br />

storm drain.” See Plumbing Information Bulletin P/PC<br />

2001-04. Visit LADBS.ORG for a copy of the Information<br />

Bulletin.<br />

L. SPECIAL HAZARDS<br />

1. Glazing in hazardous locations shall be tempered.<br />

(2406.4)<br />

a Ingress and egress doors<br />

b.Panels in sliding or swinging doors<br />

c. Doors and enclosure for hot tub, bathtub, showers (Also<br />

glazing in wall enclosing these compartments within 5' of<br />

standing surface)<br />

1115B.9.8<br />

d.If within 2' of vertical edge of closed door and within 5' of<br />

standing surface<br />

e.In wall enclosing stairway landing<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 13 of 23<br />

4. O “Provide an approved spark arrester for the chimney of<br />

a fireplace, stove, or barbecue.” (L.A.M.C. 57.20.25 )~<br />

5. O “Provide an alarm for doors to the dwelling that form a<br />

part of the pool enclosure. The alarm shall sound<br />

continuously for a min. of 30 seconds when the door is<br />

opened It shall automatically reset and be equipped with a<br />

manual means to deactivate (for 15 secs. max.) for a single<br />

opening. The deactivation switch shall be at least 54" above<br />

the floor.” RGA 14-67~<br />

6. O “An approved Seismic gas shutoff valve will be installed<br />

on the fuel gas line on the down stream side of the utility<br />

meter and be rigidly connected to the exterior of the building<br />

or structure containing the fuel gas piping.” (Per Ordinance<br />

171,874-for work over $10,000.)~<br />

7. “Water heater must be strapped to wall.” Sec. 507.3, UPC .<br />

8. Fire lane access is required. The entrance to the dwelling<br />

is more than 150 ft. as measured from the edge of an<br />

improved street or approved fire lane along the normal<br />

entrance roadway or walkway to the front door. Obtain<br />

clearance from the Hydrants and Access Unit of the Fire<br />

Department in 221 N. Figueroa Street, Suite # 1500.<br />

(L.A.M.C. 57.09.03) A fire lane is 20' min. width, 15%max.<br />

Slope and has a std. turn around.<br />

F. RECREATION ROOM (A-3 <strong>Occupancy</strong>) OL # 300, No<br />

Stage<br />

1. The windows shown are inadequate for the required light and<br />

ventilation. (1203)<br />

2. Assembly room(A-3) must be 1-hour construction. It is located<br />

in a basement or above the first story.<br />

(303.2.2.2, T 5-B)<br />

3. Assembly room must be separated from the usable space below<br />

by 1-hour construction. OL$50. (303.2.2.2)<br />

4. Provide two (2) exits from the assembly room separated by<br />

feet. OL$50. (1004.2.3.2, T 10-A, 1004.2.4)<br />

5. Show that the exit hardware in the doors from the room and<br />

building satisfy Sections 1003.3.1.5, 1003.3.1.8, 1003.3.1.9 and<br />

1007.2.5.<br />

www.<strong>ladbs</strong>.org


6. Occupant load signs are required in assembly rooms with an<br />

occupant load $50. At all required locations, note on the plans<br />

“Post Occupant Load Sign - Maximum Occupant Load<br />

People”.<br />

(1007.2.6, T 10-A)<br />

N. LAUNDRY ROOM<br />

1. Clothes dryer(s) located in an area that is habitable or<br />

containing fuel burning appliances shall be exhausted to the<br />

outside or to an area which is not habitable and does not<br />

contain other fuel burning appliances (but not beneath the<br />

building or in the attic area). (M.C. 504.3.1.)<br />

2. A 4" clothes dryer moisture exhaust duct is limited to a 14"<br />

length with two elbows from the clothes dryer to the point of<br />

termination. Reduce this length by 2 feet for every elbow in<br />

excess of 2. (M.C. 504.3.2, M.C. 908)<br />

3. Door, window and exhaust openings are not permitted or must<br />

be protected within feet of the property lines.<br />

(T5-A)<br />

4. Show the opening protection for and provide details properly<br />

referenced of the occupancy separation wall required between<br />

the B and R-1/S-3/U-1 occupancies.<br />

(T3-B, 503-3)<br />

6. The following are required:<br />

a. A rated self-closing door between the<br />

garage and<br />

. (302.4, T 3-B)<br />

b. An asphalt floor or concrete floor. (312.5)<br />

c. A garage floor system adequate to support a wheel load of<br />

2000 lbs. (1607.3.3)<br />

d. Minimum headroom of 7'-0". (311.2.3.3)<br />

e. Delete door(s) and openings from garage into sleeping room.<br />

(312.4)<br />

7. S-3 <strong>Occupancy</strong> garage requires (three-hour) (two-hour)<br />

separation from R-1 <strong>Occupancy</strong>. Show details. (302.4,<br />

exception 2)<br />

8. Sprinklers required in basement(s) where distance between<br />

access openings exceeds 75'. (904.2.2)<br />

9. U-1 <strong>Occupancy</strong> garage requires one-hour occupancy<br />

separation from R-1 <strong>Occupancy</strong>. (302.4)<br />

Show:<br />

a)Specification for one-hour separation wall.<br />

b)All openings to be protected by one-hour fire assemblies.<br />

c)Specifications for l-hour floor-ceiling assembly.<br />

d)Walls, beams, and columns supporting floor above garage<br />

shall be protected with one-hour, fire-resistive construction.<br />

O. GARAGE (S-3 or U-1 <strong>Occupancy</strong>)<br />

1. A U-1 garage shall not exceed 1000 sq. ft. or one-story in<br />

height except in a mixed occupancy where the floor area shall<br />

not exceed 3000 sq. ft. provided the exterior walls and<br />

openings are protected as required for the major occupancy of<br />

the buildings. (312.2.1, 312.2.2)<br />

2. For the S-3 occupancy, show how the ventilation requirements<br />

of Section 1202.2.7 are satisfied. If a mechanical system is<br />

used, provide plans and show how and where it exhausts to the<br />

outside. (1206)<br />

3. For this garage, the wall and opening protection within<br />

feet of the property line must be<br />

and<br />

respectively. Show how this is achieved.<br />

(T-5-A)<br />

4. Exterior wall openings for a S-3 garage require a ¾-hour<br />

assemblies within 20' (10') from property line or center line of<br />

public way.91.602.3.2, T 5-A .<br />

5. This occupancy requires an automatic fire sprinkler and stand<br />

pipes systems. (311.7, 904.2.2, 904.2.9)<br />

P. TYPE V 1-HOUR CONSTRUCTION<br />

1. Continuous drywall behind all tubs is required unless the walls<br />

are within the unit and non-bearing. Back to back tubs with a<br />

common plumbing wall are impractical in 1-hour buildings.<br />

2. Interior nonload-bearing partitions within individual dwelling<br />

units in apartment houses and guest rooms or suites in hotels<br />

when such dwelling units, guest rooms or suites are separated<br />

from each other and from corridors by not less than 1-hour fireresistive<br />

constructive construction (continuous to the roof) may<br />

be constructed of: (310.2.2)<br />

a. Noncombustible materials (steel studs and drywall) or fireratardant-teated<br />

wood in buildings in any type of construction<br />

or<br />

b. Combustible framing (wood studs) with noncombustible<br />

materials (drywall) applied to the framing in buildings of<br />

Type III or V construction.<br />

3. Continuous drywall is required behind all electrical service<br />

panels, fire hoses and medicine cabinets.<br />

4. Recessed ceiling light fixtures must be boxed around with 5/8"<br />

Type “X” drywall” to maintain the 1-hour ceiling assembly.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 14 of 23<br />

www.<strong>ladbs</strong>.org


5. All plumbing penetration through walls which required<br />

protected openings (occupancy separation walls, area<br />

separation walls, corridor walls and walls to close to a real or<br />

imaginary property line) are required to be galvanized or cast<br />

iron piping.<br />

6. Plumbing penetration through a horizontal occupancy<br />

separations shall be boxed out and filled with approved safing<br />

material. Insulation is not approved. (709.6.3)<br />

7. Plastic bathroom fans in the ceiling or laundry hookup boxes in<br />

occupancy separation walls are not permitted unless<br />

specifically approved by a recognized testing agency. Provide<br />

a detail showing what is to be done. (710.2.1)<br />

8. Exhaust fans from the bathroom must enter through the wall.<br />

Dampers are required if the ceiling is penetrated. (713.11)<br />

9. Steel beams and columns shall be protected as required for 1-<br />

hour protection.<br />

(704, T7-A)<br />

a. Where ceiling forms the protective membrane for fireresistive<br />

assemblies (occupancy separations and rated<br />

roof/ceiling or floor/ceiling assemblies), the construction<br />

(floor joists) and their supporting horizontal structural<br />

members (beams) need not be individually fire protected<br />

except where such members support directly applied loads<br />

from more than one floor or roof. The required fire<br />

resistance shall not be less than that required for individual<br />

protection of members. (704.2.6)<br />

b. Columns must always be individually protected.<br />

c. Water heater combustion air ducts through 1-hour ceilings<br />

must be in a shaft. Water heater combustion air ducts in<br />

walls and ceiling without penetrating the ceiling are<br />

permitted. (710.2.1)<br />

10.Attic access openings in 1-hour ceiling can be 2 layers of 3/4"<br />

plywood or one layer of 1-5/8" T&G material, self-closing.<br />

11.Plastic electrical boxes are to be clearly identified as approved<br />

for 1-hour construction. (710.2.1, 710.3)<br />

12.Penetration of the 1-hour ceiling by ducts from the FAU and<br />

the stove hood require dampers (use a ductless hood whenever<br />

possible). Attic units (including heat pumps) require dampers<br />

at all ceiling penetrations.<br />

R. ROOF AND ATTICS<br />

1. A fire retardant roof covering is required. Provide a complete<br />

description on the plans. Class A roof covering is required for<br />

all buildings located in Fire Zone 4 or Very High Fire Hazard<br />

Severity Zone. (1503, 1504, 6403.2)<br />

2. Show roof slope(s), drain(s) and overflow drain(s) or scuppers<br />

on the roof plan. Provide a detail of the roof drain and<br />

overflow system.<br />

a. Use Appendix D of the UPC and 3"/hour for a 15 minute<br />

duration to size the drains.<br />

b. The roof drain and overflow drain must be independent lines<br />

to a yard box. (1506.3)<br />

c. Roof drainage is not permitted to flow over public property.<br />

It must be conducted under sidewalk. (1506.5)<br />

d. Overflow scuppers shall have a minimum opening height of<br />

4", a minimum area three times that of the roof drain and<br />

shall be located not more than 2" above the low point of the<br />

roof. (1506.3)<br />

3. The roof slope shown for the roof<br />

is not adequate. A<br />

Slope is required.<br />

(T-15-B-1, B-2)<br />

4. An attic access opening (22" x 30" with 30" headroom above<br />

the opening) is required into each separate attic space.<br />

(1505.1)<br />

5. Roof access to service equipment is required.<br />

(1513, MC 307.5)<br />

6. A stairway to the roof is required in every building four (4) or<br />

more stories in height unless the roof slope over 4 to 12.<br />

(1003.3.3.11)<br />

7. Show that the penthouse satisfy the requirements of section<br />

1511. Aggregate area of penthouses and roof structures is<br />

limited to 33% of the roof area.<br />

8. Attic ventilation of 1/150 of the area of ventilated space<br />

(approximately 10 sq. in. for each 10 sq. ft. of attic area) is<br />

required. (1505.3)<br />

13.Special details at all soffits are required to show the 1-hour<br />

floor/ceiling or roof/ceiling assembly. Soffits are normally<br />

shown on the plans with hash marks or shading.<br />

Q. TRASH ENCLOSURE (when it is covered and defined as<br />

S-1 <strong>Occupancy</strong>)<br />

1. Provide details for the wall and roof construction enclosing the<br />

bin.<br />

2. An occupancy separation of hours is required<br />

between the trash enclosure and the<br />

. Show<br />

the required wall and ceiling construction and the hour<br />

door rating.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 15 of 23<br />

9. Unprotected openings are prohibited in envelope protection<br />

type ceilings. All duct openings require fire dampers and are<br />

limited in area to 100 sq. in. in any 100 sq. ft. of ceiling. Access<br />

openings require 1-hour fire rated assemblies with closing<br />

devices approved by the Department. (710.2)<br />

S. DWELLING UNITS (R-1 <strong>Occupancy</strong>)<br />

1. The window area in is insufficient for light and<br />

ventilation. (1203.1 thru 3)<br />

2. A porch over required windows must have a minimum clear<br />

height of 7 feet with the longer side at least 65% open and<br />

unobstructed. (1203.1)<br />

www.<strong>ladbs</strong>.org


3. For the purpose of providing natural light or ventilation at<br />

exterior openings of buildings, a minimum yard of 3 feet in<br />

width for one and two story building is required. For buildings<br />

more than two stories, the minimum width of the yard shall be<br />

increased to 1 foot for each additional story.<br />

(1203.4.2)<br />

4. For the purposed of providing natural light or ventilation at<br />

exterior openings of buildings, a minimum court of 3 feet in<br />

width is required. Courts having windows opening on opposite<br />

slides shall not be less than 6 feet in width. Courts bounded on<br />

three or more sides by the walls of the buildings shall not be<br />

less than 10 feet in length, unless bounded one end by a public<br />

way or yard. For buildings more than two stories in height, the<br />

court shall be increased 1 foot in width and 2 feet in length for<br />

each additional story. (1203.4.3)<br />

5. A mechanical ventilation system in lieu of openable windows<br />

in the bathroom, toilet room and laundry, which furnishes five<br />

air changes per hour direct to the outside, is required.<br />

(1203.3)<br />

6. One openable window with an openable area of not less than<br />

5.7 sq. ft., minimum clear 24" height and 20" width, and a sill<br />

height not over 44" above the floor is required in all bedrooms<br />

below the fourth story and basement. (310.4)<br />

7. Escape and rescue windows with a finished sill height below<br />

the adjacent ground elevation shall have a window well<br />

complying with Section 310.4. All window wells shall extend<br />

below the window sill height. (1402.5)<br />

8. One habitable room shall have not less than 120 square feet of<br />

floor area. Other habitable rooms, except kitchens, shall contain<br />

at least 70 square feet of floor area. A minimum room area of<br />

sq. ft. is required for the . (310.6.2)<br />

9. Habitable rooms other than a kitchen shall not be less than 7<br />

feet in any dimension. (310.6.3)<br />

10.Show that ceiling height for habitable rooms is 7 ft. 6 in.<br />

Minimum. (310.6.1)<br />

11.Show that ceiling height for kitchens, halls, bathrooms, and<br />

toilet compartment is 7 feet minimum. (310.6.1)<br />

12.Show locations of hard-wired smoke detectors with a battery<br />

back up in each sleeping room and at a point centrally located<br />

in the corridor or area giving access to each sleeping area.<br />

(310.9.1)<br />

13.The inside finished dimensions of the shower and toilet must be<br />

30" min. width and 24" clear space in front of the toilet.<br />

(2904)<br />

14.The wall covering shall be cement plaster, tile or approved<br />

equal, 70" above the drain at the showers or tubs with showers.<br />

Materials other than a structural elements shall be moisture<br />

resistant. Glass enclosure doors and panels must be labeled<br />

Category II. Swing the door outward. Net area of shower<br />

receptor shall be not less than 1024 sq. in. of floor area, and<br />

encompass 30 inch diameter circle.<br />

(807.1.3, 2406.4, 2407, T24-2-A, UBC STD. 24-2)<br />

15.A min 12" sq. access panel to the bathtub trap slip joint<br />

connection is required. Show the location and size on the<br />

plans,. If a solid joint is to be used, clearly state on the plans<br />

and no access panel is required. (P.C. 405.2)<br />

16.Show how the dwelling unit is provided with comfort heating<br />

facilities capable of maintaining a room temperature of 70<br />

degrees F above 3 feet from the floor. (310.11)<br />

17.The type of glass, thickness and method of protection against<br />

impact for glass lights with bottoms 18" or less above the floor<br />

or walking surface must be indicated on the plans.<br />

(2406.4-7)<br />

18.Prefabricated fireplaces are required to be approved by a<br />

recognized agency. Show the make, model and ICBO / UL<br />

number on the plans. (3102.5)<br />

19.Interior wall and ceiling finishes shall be installed in<br />

accordance with section 803. Show flame spread and smoke<br />

density ratings for finish materials.<br />

20.Provide veneer details. Show method of anchorage, size and<br />

spacing of anchors, and type of backing to comply with Chapter<br />

14. (2320.5.3,1403).<br />

21.Glass skylights shall comply with 91.2409. Plastic skylight<br />

shall comply with section 2603.7.1.<br />

22.Architectural projections on ( )limited to ( )<br />

(Not allowed). Must be constructed of ( ).<br />

(3204)<br />

23.Provide 32" wide doors to all interior accessible rooms.<br />

(2306.3).<br />

24.Fire alarm system is required. Submit three copies of system<br />

to Fire Department for approval prior to installation.<br />

(310.10).<br />

25.Courts having required windows opening therein shall not be<br />

less than (3') (6') ( _______ ) in width and (10')<br />

( _____) in length. (1203.4.2).<br />

26. Provide access to the bottom of the court for cleaning<br />

purposes. (1203.4.3).<br />

27. A court more than two stories in height shall be provided<br />

with a horizontal air intake with a minimum area of 10 sq ft.<br />

91.1203.4.3.<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 16 of 23<br />

www.<strong>ladbs</strong>.org


28. ICBO evaluation reports are required for the following<br />

non-structural items; provide report number:~<br />

9 deck coating 9 roofing tile 9 interior finishes<br />

9 sound/thermal insulation 9 hardboard siding<br />

9 fiber cement panel 9 9<br />

29. All openings in floors are required to be enclosed by a shaft<br />

having wall, floor, and ceiling of ________ hour fire<br />

resistive construction.<br />

(601.1, T’ 6-A)<br />

30. Building exceeds allowable height limit of T’5-B for Type<br />

( )construction. (506)<br />

31. Building exceeds allowable height limit of T’5-B for Type<br />

( )construction. (506)<br />

32. Parapet walls not less than (30") ( ) in height<br />

are required at .............................................. (709.4)<br />

33. Rubbish and linen chutes: Provide automatic sprinkler<br />

system at top of chute and in the terminal room. (904.2.2)<br />

34. Sprinklers are required for floor areas over 1500 sq ft.<br />

(904.2.2)<br />

35. Note on the plan "Sprinkler system to be approved by<br />

Plumbing Section prior to installation."<br />

36. “Provide Ultra flush water closets for all new construction.<br />

Existing shower heads and toilets must be ultra flush.”<br />

37. Provide and specify LARR# for an approved graffitiresistant<br />

finish for the first 9 feet of exterior walls.<br />

(6306)<br />

38. Provide and specify LARR # for damp-proofing for all walls<br />

below grade that enclose habitable or non-habitable space.<br />

(1402.4)<br />

*T. FIRE ZONE REQUIREMENT ( LA CITY SPECIFIC)<br />

1. Type V buildings shall comply with (7206.2)<br />

2. Type (IV) (V) building is not permitted in Fire District<br />

No 1. (7204.1).<br />

3. In every building in Fire District Nos. 1 and 2, every story<br />

or basement with a floor surface elevation more than 4 ft<br />

lower than the highest elevation of the floor landing or tread<br />

of any required exit that story shall be sprinklered .<br />

(7203.5.1)<br />

U. FLOOD HAZARD<br />

1. The lot is located in an area subject to flood. An Elevation<br />

Certificate must be filled out for submittal to the inspector<br />

certifying that foundation was built at the required elevation.<br />

2. This project is in the Special Flood Hazard Zone ( ).<br />

Elevate the structure above elevation ( ), or design the<br />

structure for flood proofing.<br />

3. Flood Zone (A, AR VI-30, AO (AF), A1-30 (FW)) require<br />

clearance from the Department of Public Works, NFIP<br />

Coordinator, (213) 847-5210.<br />

4. Note on the plan:<br />

a) “Survey by a licensed surveyor or Civil Engineer<br />

authorized to perform survey work is required to verify<br />

elevation of lowest finished floor.”<br />

b) “Completed (Elevation/Flood Proofing) Certificate<br />

(attached) shall be given to the inspector. If misplaced, the<br />

certificate can be downloaded from the Internet at<br />

http://www.fema.gov/library/elvinst.htm<br />

V. STRUCTURAL REQUIREMENTS<br />

1. Floor dead load must include a 20 psf partition, in addition<br />

to other loads. (1606.2)<br />

2. Exit facilities must be designed for a 100 psf live load.<br />

(T16-A)<br />

3. Garage floors which support private or pleasure-type cars<br />

must be designed per Section 1607.3.3.<br />

4. The following uniform (concentrated, special) loads must be<br />

used in accordance with T16-A & T16-B.<br />

5. Marquees (balconies) must be designed for a 60 psf<br />

live load.<br />

(T16-A)<br />

6. Ceiling joists must be designed for a live load of not less than<br />

10 psf. (T16-B)<br />

7. The live load for which commercial and<br />

industrial floors are designed shall be posted in each room.<br />

Clearly note on the plans and show the design live load on<br />

the structural plans. (1607.3.5, T-16-A )<br />

8. Key or identify all sections and details as to their location on<br />

the plan or elevation views.<br />

9. Structural observation per Section 1702 is required for this<br />

project. The engineer of record shall prepare an inspection<br />

program, including the name(s) of the individuals or firms<br />

who will perform the work. The inspection program shall be<br />

shown on the first sheet of the structural drawings. (See<br />

attached “General Notes for Structural Observation” form)<br />

10. The required snow load for this area is psf.<br />

The tributary live load reduction in section 1607.5 is not<br />

permitted. See Section 1614 for snow load reduction.<br />

(1607.5, T-16-C)<br />

11. For the design wind load in this area, use<br />

q s<br />

= _______psf, exposure B, C or D from Table 16-G<br />

and Cq from Table 16-H. (1620)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 17 of 23<br />

www.<strong>ladbs</strong>.org


12. Specify the grade and species of framing lumber, treated mud<br />

sills, type and grade of plywood, design strength of concrete,<br />

and glued-laminated timber, ASTM designation of structural<br />

steel shapes and masonry units, mix of mortar and grout, type<br />

of soil and bearing value, and . (106.4.3)<br />

13. Note on plans. "An AITC Certificate of Inspection for all<br />

glued laminated timber shall be submitted to a Building and<br />

Safety Division inspector prior to erection."<br />

14. Submit design and details of manufactured trussed rafters<br />

with a layout plan, complete calculations and connector plate<br />

design.<br />

15. Fabricated wood trusses shall comply with the requirements<br />

of Section 2321.<br />

16. Note or detail lateral support for the top of interior nonbearing<br />

walls when manufactured trusses are used. (1611.5)<br />

17. Specify the size, spacing and direction of rafters.(106.4.3)<br />

18. The _____” x __________ rafters at _________ o.c. over<br />

_____________ exceed the allowable span for __________<br />

grade.<br />

(T 23-IV-R)<br />

19. The size of ridge board, valley or hip members shall not be<br />

less than the cut end depth of the rafter. (2320.12.3)<br />

20. Roof purlins shall not be smaller than the rafter they support.<br />

The maximum span for 2x4 / 2x6 inch roof purlins is 4 / 6 ft.<br />

respectively. For purlin supports provide struts not smaller<br />

than 2x4 inch with an unbraced length not over 8 feet, and<br />

not flatter than 45 from the horizontal, to bearing walls or<br />

partitions. (2320.12.7)<br />

21. Provide designed ridge beams (4 x min.) for open beam<br />

vaulted ceilings when ceiling joists or rafter ties are not<br />

provided.<br />

28. Show size, spacing and direction of floor joists. (106.4.3)<br />

29. Doubled joists are required under parallel bearing partitions.<br />

(2320.8.5)<br />

30. The “ x “ floor joists at ” o.c.<br />

at<br />

exceeds the allowable span for<br />

grade. (T-23-IV-J-1 & J-2)<br />

31. The “x “ floor girder / beam under<br />

exceeds the allowable stress for grade.<br />

(T-4A, N.D.S.)<br />

32. Specify the header size at door, window and other openings<br />

over 4 ft. wide in bearing walls. (2320.11.6)<br />

33. The _____ x______ ‘ header at _____________ exceeds the<br />

allowable stress for _____________ grade. (T 23-4-A N.D.S.)<br />

34. Detail is required for header support at the corner window(s)<br />

at (106.4.3)<br />

35. Studs in bearing walls are limited to 10 feet in height unless<br />

an approved design is submitted.<br />

(T 23-IV-B)<br />

36. Note the use of full length studs (balloon frame) on exterior<br />

walls of rooms with vaulted ceiling. (2320.11.1, T 23 -IV-B)<br />

37. Plywood roof panels shall be bonded with intermediate or<br />

exterior glue and bonded with exterior glue where exposed<br />

to the weather. (2312)<br />

38. For plywood roofs and floors, specify panel index no.<br />

, plywood thickness, grades, nailing schedule<br />

and panel layout Pattern. Note on the plans "Roof<br />

diaphragm nailing to be inspected before covering". Face<br />

grain of plywood shall be Perpendicular to supports. Floor<br />

shall have tongue and groove or blocked panel edges.<br />

Plywood spans shall conform with Table T-23-11-H.<br />

(106.4.3)<br />

22. Ridge / hip / valley members shall be designed as vertical<br />

load carrying members when roof slope is less than 3 :12.<br />

Provide calculations. (2320.12.1)<br />

23. Provide manufactured roof truss profiles, layout plan and<br />

calculations from truss manufacturer. (106.4.3)<br />

39. Justify the roof/floor diaphragm could be considered as<br />

flexible diaphragm.<br />

40. Specify the size, height, and spacing for studs. Studs in<br />

bearing walls are limited to 10 ft. in height unless an<br />

approved design is submitted.<br />

(T-23-IV-B)<br />

24. Show ceiling joist size, spacing, and direction on plans.<br />

(106.4.3)<br />

25. The _______ x _______ ceiling joists at ________” o.c.<br />

over___________________ exceed the allowable span for<br />

________ grade. (T 23-IV-J-3 & J- 4)<br />

26. Rafter ties spaced 4 ft. (max.) on center are required<br />

immediately above ceiling joists which are not parallel to the<br />

rafters. (2320.12.6)<br />

27. Show blocking at ends of rafters and trusses at exterior walls,<br />

and at supports of floor joists. (2320.12.8 & 2320.8.6)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 18 of 23<br />

41. Three- and four-story wood structures require 3x4 or 2x6<br />

studs at16" o.c. max. in bearing partitions below the top<br />

two stories. Submit calculations showing that allowable<br />

stress in compression perpendicular to grain is not exceeded<br />

in the plates at the proposed stud spacing.<br />

(T-23-IV-B)<br />

42. Exterior stairs and balconies must be positively attached to<br />

the structure without the use of toenails or nails in<br />

withdrawal. (2320.13)<br />

www.<strong>ladbs</strong>.org


43. Light frame construction of unusual shape, size split-level,<br />

or more than 1 story shall be designed to resist lateral<br />

forces. Submit design for lateral forces.<br />

(2320.1)<br />

44. Provide a diaphragm analysis to show diaphragm adequacy.<br />

(1633.2.9)<br />

45. Structural framing not using Conventional Light-Frame<br />

Construction Provisions of Section 2320 requires the plans<br />

and calculations to be signed and sealed by an architect or<br />

civil/structural engineer licensed in the State of California.<br />

(106.4.2)<br />

46. Cross reference all calculations for joists, beams, shear<br />

walls, etc, to framing / floor plans.<br />

(106.4.3)<br />

47. Design and details are required for retaining walls over 4<br />

feet high (top of wall to bottom of footing) or with<br />

surcharge. (106.4.2, 106.4.3)<br />

48. Provide a vertical and longitudinal section through each<br />

glass block wall showing how it is supported at each edge<br />

and reinforced in each direction. Submit lateral<br />

calculations.<br />

a. Glass-block panels in exterior walls shall not exceed<br />

144 sq. ft. of unsupported area or 15 ft. in any<br />

dimension. (2110.5)<br />

b. Every exterior glass-block panel shall be provided with<br />

a min. 3/8 - inch expansion joints at the side and top.<br />

Expansion joints shall be entirely free of mortar and<br />

shall be filled with resilient material. Provide a detail<br />

on the plans. (2110.6)<br />

c. Lateral support shall be provided by panel anchors<br />

spaced not more than 16" o.c. (2110.3)<br />

49. Provide details, properly referenced, of the anchorage<br />

system between the wood roof and floor diaphragms and the<br />

concrete or masonry walls. Minimum design force shall be<br />

280 lb/lf. (1611.4)<br />

50. Provide calculations and details on the plans for the subdiaphragm<br />

and continuous cross-tie system required for all<br />

wood diaphragms providing lateral support to masonry or<br />

concrete walls. (1633.2.9, item 4)<br />

51. Submit structural calculations / design details for<br />

. (106.4.3)<br />

52. The Engineer or Architect of record, shall review and<br />

approve truss design for loads, location, and suitability<br />

for intended use. (106.4.4.1)<br />

53. Allowable values for structural design shall be per the 1999<br />

LABC.<br />

54. Structural calculations and details are required for anchored<br />

masonry or stone veneer that extends more than 5 ft. above<br />

the first floor. (2320.5.3)<br />

55. Veneer supported by wood frame shall not exceed 30'-0"<br />

above ground unless differential movement is considered by<br />

an engineer. (1403.1.2)<br />

56. Show size, type and location of all brace wall panels.<br />

Clearly show required braced wall lines (25 ft. o.c.<br />

maximum for Conventional Light-Frame C construction.)<br />

(2320.5.1)<br />

57. Solid blocking shall be provided at all horizontal joints<br />

occurring in braced wall panels. (2320.11.3)<br />

58. Allowable shear for stucco is (90 plf for seismic) (180 plf<br />

for wind) and for gypsum board (30 plf for seismic) (100<br />

plf for wind).<br />

(T25-I)<br />

59. Stucco and drywall shear walls cannot exceed a height to<br />

length ratio of 1:1. These shear walls are not allowed below<br />

the top level of a multi-story building. (2513.4 & T25-I)<br />

60. Stucco shear walls shall utilize furring, galvanized nails<br />

(having a minimum 11 ga., 1-1/2" long, 7/16" diameter<br />

head, and furred out a min of 1/4") to attach the lath to the<br />

studs. Staples shall not be used.” (T25-I)<br />

61. The maximum allowable shear three-ply plywood resisting<br />

seismic loads is 200 plf. Footnote 6 of T23-II-I-1.<br />

62. Limit height : length of plywood (wood structural panels)<br />

shear walls to 2:1. Provide complete calculations (including<br />

deflection) and details where straps are used at openings to<br />

reduce the effective height of shear walls. (2315.5.7, T23-II-<br />

G)<br />

63. The is inadequate to resist lateral<br />

forces / uplift wind pressure. Show roof floor diaphragm<br />

nailing, wall bracing. shear connections, tie down hardware<br />

and hold-down anchors. Submit lateral design. (1615, 1626)<br />

64. Wood structural panel shear walls shall meet the story drift<br />

limitation of section 1630.10. Conformance shall be<br />

determined by testing or calculations. Calculated deflection<br />

shall be determined according to UBC Standard 23-2<br />

section 23.223 and shall be increased by 25% to account for<br />

inelastic action and repetitive loading. Total vertical<br />

deflection shall be multiplied by the aspect ratio and added<br />

to the horizontal deflection.<br />

(2315.5.7)<br />

65. Lumber and structural wood panel diaphragms shall not be<br />

considered as transmitting lateral forces by rotation except<br />

one story, attached or detached residential garages or similar<br />

non habitable wood structures provided the diaphragm is<br />

not constructed of straight sheathing. (2315.1)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 19 of 23<br />

www.<strong>ladbs</strong>.org


66. Provide details of the lateral support for the top and bottom<br />

of the interior non-bearing walls. (1611.5)<br />

67. Clearly indicate on the plans all plywood and drywall shear<br />

walls. Provide a complete nailing schedule for each.<br />

68. Provide shear connection details, properly referenced, at the<br />

top and bottom of all shear walls.<br />

69. Specify the size, LARR number and manufacturer of the<br />

shot pins. The max. spacing of shot pings in bearing on<br />

nonbearing wall is / Respectively<br />

indicated on plans. The max. shear value of shot pins is 100<br />

lbs./ft. without supporting calculations for their value in<br />

wood.<br />

70. Nominal shear values for shear walls framed with cold<br />

formed steel studs other than 20 gauge shall be justified by<br />

complete, accurate analysis or tests. (2220.3)<br />

71. If required by structural calculations, show size, location<br />

and embedment length of hold-down anchors on foundation<br />

plan. Note on the plans that hold-down hardware must be<br />

secured in place prior to foundation inspection. (1630.8)<br />

72. Provide referenced calculations showing the overturning<br />

moments in the shear wall segments. (106.4.3)<br />

73. The capacity of hold-down connectors that do not consider<br />

cyclic loading of the product shall be reduced to 75% of the<br />

allowable earthquake load values. (2315.5.6)<br />

74. Note on the plans that hold-down connector bolts into wood<br />

framing require approved plate washers; and hold-downs<br />

shall be tightened just prior to covering the wall framing.<br />

(2315.5.6)<br />

75. Where allowable shear values exceed 350 pounds per foot,<br />

foundation sill plates and all framing members receiving<br />

edge nailing from abutting panels shall be not less than a<br />

single 3 inch nominal or larger member.<br />

(T 23-II-I-1 note 3)<br />

76. Provide an analysis of all tilt-up panels with openings.<br />

Show that the reinforcing in the panels, on each side of the<br />

openings, is adequate.<br />

77. For each of the metal decks provide the manufacturer and<br />

designation, height, complete welding information,<br />

reinforcing and thickness and type of fill. Specify LARR on<br />

the plans.<br />

78. Bracing members and connections in steel braced frames<br />

shall be designed per Seismic Provisions for Structural Steel<br />

Building of AISE Part I, Section 13, 14 or 15.<br />

(Chapter 22 Division IV)<br />

79. Concrete shear walls must be designed based on<br />

requirements of 1921.6.3<br />

80. Concrete shear wall reinforcement shall be terminated with<br />

required development length per Section 1921.6.6.6 beyond<br />

the boundary reinforcing at the vertical and horizontal end<br />

faces of wall sections.<br />

81. Special inspection by a registered deputy inspector is<br />

required for field welding, concrete strength >2500 psi, high<br />

strength bolting, sprayed on fireproofing, high-strength<br />

masonry, high-lift grouting, prestressed concrete and special<br />

moment-resisting concrete frames. Note on the plans.<br />

(1701.5*, & Chapter 19, 21 & 22)<br />

82. Masonry shear walls shall be designed for 1.5 time the<br />

required seismic force. A stress increase of 33% is allowed.<br />

(2107.1.7)<br />

83. The masonry or concrete walls below grade may be<br />

designed to span simply supported between slabs. NOTE<br />

ON THE PLANS: "The perimeter walls are not to be<br />

backfilled until the floor slabs are poured and cured."<br />

84. Where flexible diaphragms, as defined in Section 1630.6,<br />

provide lateral support for walls and partitions of masonry<br />

and concrete. Shall be determined using Formula (33.1).<br />

85. Call out minimum thickness of 3½ inch concrete slab on<br />

grade, reinforcement, and moisture barrier on foundation<br />

plan. (1900.4.4)<br />

86. Call out foundation bolt size and spacing on foundation<br />

plan. The foundation bolts shall be 5/8 inch diameter<br />

embedded at least 7 inches into the concrete or masonry<br />

foundation spaced not more than 6 feet apart.<br />

(1806.6)<br />

87. Foundation sill bolts require steel plate washers of size and<br />

thickness as specified by table 23-II-L. (1806.6.1)<br />

88. Detail (and reference location on foundation plan) typical<br />

foundation sections for: perimeter walls, interior bearing<br />

walls, depressed slabs, foundation common to dwelling and<br />

garage, garage entrance, spread and/or post pads. (106.4.3)<br />

89. Foundations with stem walls shall be reinforced with a<br />

minimum of one No. 4 bar at the top of the wall and one<br />

No. 4 bar at the bottom of the footing. (1806.7.1)<br />

90. Slabs-on-grade with turn-down footings shall be reinforced<br />

with a minimum of one No. 4 bar at the top and one No. 4<br />

bar at the bottom. (1806.7.2)<br />

91. Foundation sections 12/15/ 18 inches wide, 6 / 8 / 10 inches<br />

thick and 12 /18 / 24 inches depth below natural ground<br />

surface or certified fill grade are required. (T 18-I-C)<br />

92. Provide details for stepped footings when slope of top<br />

and/or bottom of footing exceeds 1:10.<br />

(1806.4)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 20 of 23<br />

www.<strong>ladbs</strong>.org


93. Show minimum 18 inch underfloor clearance from grade to<br />

bottom of floor joists and minimum 12 inch clearance to<br />

bottom of girders. (2306.3)<br />

94. Specify that foundation sills shall be pressure treated, or<br />

foundation grade Redwood. (2306.4)Foundation cripple<br />

walls shall be framed and sheathed per Section 2320.11.5.<br />

A cripple wall over 4 feet in height shall be framed of studs<br />

having the size required for an additional story.<br />

95. Provide a weep screed for stucco at the foundation plate line<br />

a minimum of 4 inches above the earth or 2 inches above<br />

paved areas. (2506.5)<br />

96. Show location of underfloor access crawl hole (18 x 24<br />

inches). (2306.3)<br />

97. Foundation and floor slabs on expansive soil shall conform<br />

as follows, unless approved soil report and GPI indicates<br />

soil is not expansive by the Expansion Index Test method,<br />

or recommends other details: (1804.4)<br />

a. Continuous footings under exterior walls and interior<br />

bearing walls extending below grade 24" and 18"<br />

respectively and below foundation wall crawl hole.<br />

Piles or piers are permitted without interconnected<br />

grade beams to support first floor loads only. Pad<br />

footing located under a reinforced slab within the<br />

confines of a perimeter footing need not be connected<br />

by a grade beam.<br />

b. Four continuos #4 bars, two 4 inches from bottom and<br />

two 4 inches from top of foundation.<br />

c. Floor slab 3½ inches thick over 4-inch thick coarse<br />

aggregate base or plastic moisture barrier membrane (6<br />

mils thick) and reinforced with #3 bars at 24 inches on<br />

center both ways or welded wire mesh with a cross<br />

sectional area of not less than 0.5 square inches per<br />

foot each way.<br />

103. When the roof slope is less than 3 units vertical in 12<br />

units horizontal, members supporting rafters and ceiling<br />

joists such as ridge board, hips and valleys shall be<br />

designed as beams. (2320.12.1)<br />

104. Retaining walls higher than 12 feet (3658 mm), as<br />

measured from the top of the foundation, shall be designed<br />

to resist the additional earth pressure caused by seismic<br />

ground shaking. (1611A6)<br />

105. Provide details and calculations for a brick fireplace and<br />

chimney. Show compliance with. (3102)<br />

106. Cantilevered diaphragms shall not exceed 15% of the<br />

distance between lines of lateral load resisting elements<br />

from which the diaphragm cantilevers. The depth to width<br />

ratio of the cantilevered portion of the diaphragm shall not<br />

be less than 4:1. (2315.1)<br />

107. The principle of diaphragm rotation shall not be permitted<br />

to distribute shear forces to shear walls. (2315.1)<br />

108. For Steel moment frame connection design see attached<br />

“ Steel Frame Design” supplemental correction sheets.<br />

109. The following applies to all shear walls with a shear value<br />

greater than 300 plf. These walls shall be clearly identified<br />

on the plans. Table 23-II-I-1 footnote 3. Provide the<br />

following:<br />

a) 3x foundation sill plates.<br />

b) 3 x studs and blocks between adjacent panels.<br />

c) 1/2" edge distance for plywood boundary nailing..<br />

d) Stagger nails if nail spacing is less than 2" o.c.<br />

e) Square plate washers shall be used with all anchor<br />

bolts. Table 23-II-L<br />

5/8" bolt - 2.5x2.5x1/4 3/4"bolt - 2.75x2.75x5/16<br />

7/8" bolt - 3x3x5/16 1" bolt - 3.5x3.5x3/8<br />

d. Saturate the soil 18 inches deep before placing the<br />

concrete slab.<br />

98. Provide detail for rigid conduit. Due to shrinkage of the<br />

wood framing, provisions must be made to allow movement<br />

of the rigid conduit.<br />

99. Roof nailing must be designed for wind uplift when the<br />

mean roof height exceeds 35 feet. T 23-II-B-2, 2404.3<br />

100. Show full height studs at gable end walls for vaulted<br />

ceiling room(s).<br />

101. Cripple walls exceeding 4' in height shall be framed of<br />

studs having the size required for an additional story.<br />

(2320.11.5)<br />

102. Provide double joists under parallel bearing partitions.<br />

(2320.8.5)<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 21 of 23<br />

110. Provide pile ties: Individual pile caps and caissons subject<br />

to seismic forces shall be interconnected by ties in two<br />

directions. Ties shall be capable of resisting, in tension or<br />

compression, a minimum horizontal force equal to 10% of<br />

the larger column load. Design lateral force resisting piles<br />

and caissons for flexure for a length equal to 120% of the<br />

flexural length. (1921.4.2, 1807.2, 1809.5.1.)<br />

111. Provide an ascending slope clearance to building of H/2 or<br />

15' max. ( 1806.5.6, Figure 18-I-1)<br />

112. Earthquake Induced Liquefaction/Landslide Area:<br />

A geotechnical report is required to evaluate the<br />

potential for soil liquefaction and soil strength loss<br />

during earthquake. ( 1804.5)<br />

113. Detail a footing setback of H/3 to the face of slope or as<br />

required by the approved soil report. (1806.5.3, Fig 18-I-1)<br />

www.<strong>ladbs</strong>.org


114. There is an excavation of a greater depth than are the walls<br />

or foundation of an adjoining building or structure and<br />

located closer to the property line than the depth of the<br />

excavation. The owner shall provide the Department of<br />

Building and Safety with evidence that the adjacent property<br />

owner or owners have been given a 30-day written notice by<br />

certified mail of such intent to make an excavation prior to<br />

the issuance of the permit. This notice shall state the depth<br />

of such excavation and when it will commence. ( 3301.2.1)<br />

115. Add the following material specifications and/or notes to<br />

plans:<br />

9 Soil: Type of soil and bearing value Per T 18-I-A.<br />

9 Plywood diaphragms: Product Standard PS 1-95,<br />

Douglas fir-Larch, Structural I (or CDX).<br />

9 Particle board: ANSI A208.1-1989. Moisture protection<br />

is required.<br />

9 Wood Framing members: Grade and species of all<br />

lumber. “must be grade marked.”<br />

9 Glue Lam Beams: “GLB must be fabricated in LA City<br />

Bldg.. Dept. licenced shop.” Identify grade symbol and<br />

lamination species per T 5-A, ‘91 NDS Supp.<br />

9 “Field Welding to be done by welders must be certified<br />

by the L.A. City Building Department for (structural<br />

steel) (reinforcing steel) (light gage steel). Continuous<br />

inspection by a deputy inspector is required.”~<br />

9 Steel: Structural steel ASTM (A36)(A992), Structural<br />

Pipe ASTM A53 Gd B, Tubing ASTM A 501.<br />

Reinforcing bars ASTM A615.<br />

9 “Shop welds must be performed in a LA City Bldg.<br />

Dept. licenced fabricator’s shop.”~<br />

9 “Concrete: Standard 2500 psi concrete. 3000 psi min<br />

for grade beams and caissons.” (1905.1, 91.1921.2.4.1)<br />

9 “Continuous inspection by a deputy inspector is<br />

required for all concrete designed with f’c greater than<br />

2500psi.”<br />

9 “Lag Bolts: Provide lead hole 40%-70% of threaded<br />

shank dia. and full dia. for smooth shank portion.” ‘97<br />

NDS<br />

9 Masonry: Specify type and f’m of masonry units.<br />

Proportions of mortar and grout mixes. ( 2103, T 21-D)<br />

9 “LA City Bldg. Dept. licensed fabricator is required for<br />

(Glulam beams)(Trusses)(Structural Steel) ( ).”<br />

9 “Continuous inspection by a deputy inspector required<br />

for ( ).”<br />

9 Specify that foundation sills shall be pressure treated,<br />

or foundation grade Redwood. (2306.4).<br />

Douglas-Fir (Group II Lumber ) pressure treated sill<br />

plates shall be used. Engineer shall be notified for<br />

redesign if other species of sill plates are used or<br />

delivered to the site.<br />

9 Only common nails shall be used for all plywood shear<br />

walls and nail guns using “Clipped head” or Sinker<br />

nails are not acceptable.<br />

9 “All bolt holes shall be drilled 1/32 to 1/16"<br />

oversized. 8.1.2.1, ‘ 91 NDS .<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 22 of 23<br />

116. Provide LARR number for screws used in plywood<br />

shear walls framed with cold formed steel studs.<br />

Shear values for plywood shear walls framed with<br />

cold formed steel studs other than 20 gauge shall be<br />

justified by complete, accurate analysis or tests.<br />

(T 22-VIII-C, footnote 2, 2220.3)<br />

117. Cantilevered columns resisting seismic forces shall<br />

be designed with a K factor of 2.1 and shall be limited<br />

to a maximum inelastic response displacement, ∆M, of<br />

.025h. (1630.9.2, 1630.10.2)<br />

118. Hold down straps - Include the following in design<br />

and detailing between floors:<br />

a). Design and detail straps installation when used as<br />

hold downs across floor joists. Account for<br />

reduced number of nails across joist.<br />

b).<br />

Determine the allowable load based on the<br />

number of nails thru the strap into the posts<br />

above and below the "Dead Space" between<br />

floors. Specify # of nails required.<br />

c). Design and detail straps so that the minimum nail<br />

spacing will be provided when the strap nailing is<br />

combined with the shear wall edge nailing (i.e.<br />

provide 4x member wherever a strap and shear<br />

wall edge nailing occur or detail strap nailed over<br />

and thru unnailed plywood--show nailing pattern<br />

on plan).<br />

119. Calculate seismic drift, ∆ M = 0.7 R ∆ S , using strength<br />

level forces in accordance with Section 1630.9.2 .<br />

120. Provide separation from property line or adjacent<br />

building(s) in accordance with Section 1633.2.11.<br />

121. The value of R used for design in a specific direction<br />

shall not exceed the lowest value of R for any of the<br />

lateral force resisting systems utilized in that same<br />

direction. (1630.4.4)<br />

122. Provide calculations and details to show that collector<br />

elements, splices, and connections to resisting<br />

elements have the strength to resist the combined<br />

loads resulting from the special seismic load of<br />

Section 1612.4. (1633.2.6)<br />

123. Provide mix design calculation for concrete with f ‘ c $<br />

6000 psi.<br />

124. For concrete columns that are not part of the lateralforce-resisting<br />

system, provide transverse<br />

reinforcement in accordance with Sections 1921.7.2.2<br />

and 1921.4.4.1.<br />

www.<strong>ladbs</strong>.org


125. A supplemental plan check and permit with the applicable<br />

fees is required for deferred item(s) :<br />

1. Prefabricated stairs including handrails<br />

2. Prefabricated roof and floor trusses<br />

3. Curtain walls<br />

4. Storage Racks<br />

The engineer of record shall review the design of the<br />

deferred item(s) and verify their conformance with the<br />

intent of the original design.<br />

126. Submit structural calculations and connection details<br />

for the structural members that provide support for the<br />

seismic forces generated by elevators. The seismic<br />

forces must be determined in accordance with Section<br />

1632. The calculations and details provided must<br />

show the complete load path from the rail supports to<br />

the building’s lateral-force-resisting system.<br />

ADDITIONAL CORRECTIONS<br />

( SEE PLANS FOR ADDITIONAL COMMENTS)<br />

--------------------------------------------------------------------------------<br />

--------------------------------------------------------------------------------<br />

--------------------------------------------------------------------------------<br />

--------------------------------------------------------------------------------<br />

--------------------------------------------------------------------------------<br />

--------------------------------------------------------------------------------<br />

--------------------------------------------------------------------------------<br />

LADBS-Corr.Lst.18 (6/2003)<br />

Page 23 of 23<br />

www.<strong>ladbs</strong>.org

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!