Evolocity II Installation Guide.book - Abel Keogh
Evolocity II Installation Guide.book - Abel Keogh
Evolocity II Installation Guide.book - Abel Keogh
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
EXIT CHANGE SELECT<br />
A1 1 2 3 4 5 6 7 8 9<br />
EXIT CHANGE SELECT<br />
10 A2 A1 1 2 3 4 5 6 7 8 9<br />
10 A2<br />
Preparing for <strong>Installation</strong> 3<br />
Preparing the Site<br />
Static pressure is equally as important as temperature. Linux Networx recommends the static pressure be no<br />
less than 0.5 inches as measured in front of the rack enclosure. This will require a high-volume air grate such as<br />
the “Tate Access Floor GrateAire” (part number 8515). The recommended air volume is 350 Cubic Feet per<br />
Minute (CFM) per each five hosts in the subrack. The following is a comparison between a typical floor grate<br />
(on the right) that allows approximately 25% air flow and the Tate Access Floor GrateAire (on the left) that<br />
allows approximately 75% air flow.<br />
Altitude<br />
Feet<br />
Inches<br />
Mercury<br />
ALTITUDE CORRECTION CHART<br />
STANDARD AIR—ALT. 0 FT. 29.92" HG. 70° F .0740 DENSITY<br />
Lbs/sq In<br />
Atmosphere<br />
Specific<br />
Volume<br />
Cu Ft/Lb<br />
Relative<br />
Density<br />
Correction<br />
Factor<br />
Air Density<br />
Lbs/Cu Ft<br />
Cfm<br />
Transfer<br />
Factor<br />
Cfm<br />
Correction<br />
Factor<br />
0 29.92 14.70 13.340 1.000 0.0750 1.080 1.000<br />
100 29.81 14.64 13.389 0.996 0.0747 1.076 1.004<br />
200 29.70 14.58 13.439 0.993 0.0745 1.073 1.007<br />
300 29.60 14.52 13.488 0.989 0.0742 1.068 1.011<br />
400 29.49 14.46 13.538 0.985 0.0739 1.064 1.015<br />
500 29.38 14.40 13.587 0.981 0.0736 1.060 1.019<br />
600 29.28 14.36 13.636 0.978 0.0734 1.057 1.022<br />
<strong>Evolocity</strong> <strong>II</strong> <strong>Installation</strong> <strong>Guide</strong>