2 Preparing for <strong>Installation</strong><br />
Preparing the Site<br />
Component<br />
EPDU 120<br />
EPDU 250<br />
UPS Control Unit*<br />
UPS Battery*<br />
Icebox<br />
Cabling (per host)<br />
Unit Weight<br />
3 lbs. (1.3 kg)<br />
3 lbs. (1.3 kg)<br />
25 lbs. (11.3 kg)<br />
80 lbs. (36.2 kg)<br />
5 lbs. (2.2 kg)<br />
1 lb. (0.4 kg)<br />
Note<br />
Inspect the floor intended to support the cluster to determine that it has sufficient structural integrity<br />
to carry the load applied by the cluster—to ensure safety, consult a structural engineer. The most ideal<br />
solution is to install a raised floor specifically designed for computer centers. A flooring system of this<br />
type provides the maximum convenience and safety, allowing you to run cables under the floor and<br />
providing a means by which cold air may be forced into rack enclosures to ensure efficient cooling.<br />
Cooling Requirements<br />
Clustered computers produce potentially large amounts of heat that can drastically reduce the life span of your<br />
cluster components. Although <strong>Evolocity</strong> <strong>II</strong> clusters operate at approximately 22° F (11° C) cooler than<br />
standard 1U and 2U solutions, you should take adequate steps to prevent the cluster from overheating.<br />
Warning!<br />
Hosts require substantial cooling targeted specifically at each host. Hosts that are not cooled<br />
sufficiently may shut down or suffer irreparable damage.<br />
One of the most significant factures in ensuring adequate cooling is room size. A large room with high ceilings<br />
allows heat to rise away from the computing equipment, providing plenty of airflow in and around the cluster.<br />
If you purchased a cluster that contains more than five hosts, it may be necessary to equip your room with an<br />
additional, commercial air-conditioning unit. Most computer rooms maintain an average temperature between<br />
60–68° F (16–20° C). If your cluster produces enough heat to overwhelm your present cooling system,<br />
additional cooling is a must. The room should have sufficient air conditioning capacity to support the cooling<br />
needs of the entire cluster and use controls that prevent excessive temperature fluctuation.<br />
To ensure that the equipment used to cool the cluster is adequate, determine the total power consumption (in<br />
watts) of all devices in the room and convert that number to British Thermal Units (BTUs). This is<br />
accomplished using the formula watts x 3.412 = BTU. For specific altitudinal cooling requirements, refer to<br />
the table on page 3.<br />