<strong>DK32</strong> - DK34 - DK37 H<strong>and</strong>book<br />

<strong>Variable</strong> area flowmeter<br />

© KROHNE 01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


: IMPRINT :::::::::::::::::::::::::::::::::::::::<br />

All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without<br />

the prior written authorisation of KROHNE Messtechnik GmbH.<br />

Subject to change without notice.<br />

Copyright 2012 by<br />

KROHNE Messtechnik GmbH - Ludwig-<strong>Krohne</strong>-Str. 5 - 47058 Duisburg (Germany)<br />

2 www.krohne.com 01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

CONTENTS<br />

1 Safety instructions 5<br />

1.1 Intended use ..................................................................................................................... 5<br />

1.2 Certifications .................................................................................................................... 5<br />

1.3 Safety instructions from the manufacturer ..................................................................... 6<br />

1.3.1 Copyright <strong>and</strong> data protection ................................................................................................ 6<br />

1.3.2 Disclaimer ............................................................................................................................... 6<br />

1.3.3 Product liability <strong>and</strong> warranty ................................................................................................ 7<br />

1.3.4 Information concerning the documentation........................................................................... 7<br />

1.3.5 Warnings <strong>and</strong> symbols used................................................................................................... 8<br />

1.4 Safety instructions for the operator................................................................................. 8<br />

2 Device description 9<br />

2.1 Scope of supply................................................................................................................. 9<br />

2.2 Device versions............................................................................................................... 10<br />

2.3 Nameplate ...................................................................................................................... 11<br />

2.4 Description code............................................................................................................. 12<br />

3 Installation 13<br />

3.1 Notes on installation ......................................................................................................13<br />

3.2 Storage ........................................................................................................................... 13<br />

3.3 Installation requirements .............................................................................................. 13<br />

4 Electrical connections 14<br />

4.1 Safety instructions.......................................................................................................... 14<br />

4.2 Electrical connection of limit switches .......................................................................... 15<br />

4.3 Setting the limit switch...................................................................................................16<br />

4.4 DK37/M8M limit switches............................................................................................... 17<br />

4.5 DK37/M8E electrical signal output ................................................................................ 18<br />

4.5.1 Power supply......................................................................................................................... 19<br />

4.5.2 Load for HART ® communication .......................................................................................... 19<br />

4.5.3 Parametrization .................................................................................................................... 19<br />

4.6 Ground connections........................................................................................................ 20<br />

4.7 Protection category ........................................................................................................21<br />

5 Start-up 22<br />

5.1 St<strong>and</strong>ard device .............................................................................................................. 22<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

3


CONTENTS<br />

<strong>DK32</strong> - DK34 - DK37<br />

6 Service 23<br />

6.1 Maintenance ................................................................................................................... 23<br />

6.2 Spare parts availability...................................................................................................24<br />

6.3 Availability of services .................................................................................................... 24<br />

6.4 Returning the device to the manufacturer..................................................................... 24<br />

6.4.1 General information.............................................................................................................. 24<br />

6.4.2 Form (for copying) to accompany a returned device............................................................ 25<br />

6.5 Disposal .......................................................................................................................... 25<br />

7 Technical data 26<br />

7.1 Operating principle......................................................................................................... 26<br />

7.2 Technical data................................................................................................................. 27<br />

7.3 Dimensions..................................................................................................................... 31<br />

7.4 <strong>Flow</strong> table ....................................................................................................................... 34<br />

7.5 Differential pressure regulators.................................................................................... 36<br />

8 Notes 39<br />

4 www.krohne.com 01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

SAFETY INSTRUCTIONS 1<br />

1.1 Intended use<br />

CAUTION!<br />

Responsibility for the use of the measuring devices with regard to suitability, intended use <strong>and</strong><br />

corrosion resistance of the used materials against the measured fluid lies solely with the<br />

operator.<br />

INFORMATION!<br />

The manufacturer is not liable for any damage resulting from improper use or use for other than<br />

the intended purpose.<br />

The variable area flowmeters manufactured by KROHNE Messtechnik GmbH are suitable for<br />

measuring gases, vapors <strong>and</strong> liquids.<br />

These flowmeters are particularly suitable for measuring:<br />

• Liquids<br />

• Hydrocarbons<br />

• Water<br />

• Chemicals with low corrosiveness<br />

• Saturated steam<br />

• Superheated steam<br />

• Industrial gases<br />

DANGER!<br />

In case of instruments which are used in explosive endangered areas please consider the<br />

supplementary installation <strong>and</strong> operating instructions mentioned in the Ex-manual.<br />

WARNING!<br />

The operator shall bear sole responsibility for the use of the flowmeters with regard to<br />

suitability, intended use <strong>and</strong> corrosion resistance of the materials used to the process product.<br />

The manufacturer shall not be liable for any damage resulting from improper use or use for<br />

other than the intended purpose.<br />

Do not use any abrasive or highly viscous process products.<br />

1.2 Certifications<br />

CE marking<br />

The flowmeter meets the statutory requirements of the following EC directives:<br />

• Pressure Equipment Directive 97/23/EC<br />

• EMC Directive 89/336/EC for instruments with electrical options<br />

• ATEX Directive 94/9/EC for instruments in Ex-areas<br />

And also<br />

• NAMUR Recommendations NE 21 <strong>and</strong> NE 43 (DK37/M8E)<br />

KROHNE Messtechnik GmbH & Co. KG certifies successful testing of the product by applying the<br />

CE mark.<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

5


1 SAFETY INSTRUCTIONS<br />

<strong>DK32</strong> - DK34 - DK37<br />

1.3 Safety instructions from the manufacturer<br />

1.3.1 Copyright <strong>and</strong> data protection<br />

1.3.2 Disclaimer<br />

The contents of this document have been created with great care. Nevertheless, we provide no<br />

guarantee that the contents are correct, complete or up-to-date.<br />

The contents <strong>and</strong> works in this document are subject to copyright. Contributions from third<br />

parties are identified as such. Reproduction, processing, dissemination <strong>and</strong> any type of use<br />

beyond what is permitted under copyright requires written authorisation from the respective<br />

author <strong>and</strong>/or the manufacturer.<br />

The manufacturer tries always to observe the copyrights of others, <strong>and</strong> to draw on works created<br />

in-house or works in the public domain.<br />

The collection of personal data (such as names, street addresses or e-mail addresses) in the<br />

manufacturer's documents is always on a voluntary basis whenever possible. Whenever<br />

feasible, it is always possible to make use of the offerings <strong>and</strong> services without providing any<br />

personal data.<br />

We draw your attention to the fact that data transmission over the Internet (e.g. when<br />

communicating by e-mail) may involve gaps in security. It is not possible to protect such data<br />

completely against access by third parties.<br />

We hereby expressly prohibit the use of the contact data published as part of our duty to publish<br />

an imprint for the purpose of sending us any advertising or informational materials that we have<br />

not expressly requested.<br />

The manufacturer will not be liable for any damage of any kind by using its product, including,<br />

but not limited to direct, indirect or incidental <strong>and</strong> consequential damages.<br />

This disclaimer does not apply in case the manufacturer has acted on purpose or with gross<br />

negligence. In the event any applicable law does not allow such limitations on implied warranties<br />

or the exclusion of limitation of certain damages, you may, if such law applies to you, not be<br />

subject to some or all of the above disclaimer, exclusions or limitations.<br />

Any product purchased from the manufacturer is warranted in accordance with the relevant<br />

product documentation <strong>and</strong> our Terms <strong>and</strong> Conditions of Sale.<br />

The manufacturer reserves the right to alter the content of its documents, including this<br />

disclaimer in any way, at any time, for any reason, without prior notification, <strong>and</strong> will not be liable<br />

in any way for possible consequences of such changes.<br />

6<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

SAFETY INSTRUCTIONS 1<br />

1.3.3 Product liability <strong>and</strong> warranty<br />

The operator shall bear responsibility for the suitability of the device for the specific purpose.<br />

The manufacturer accepts no liability for the consequences of misuse by the operator. Improper<br />

installation <strong>and</strong> operation of the devices (systems) will cause the warranty to be void. The<br />

respective "St<strong>and</strong>ard Terms <strong>and</strong> Conditions" which form the basis for the sales contract shall<br />

also apply.<br />

1.3.4 Information concerning the documentation<br />

To prevent any injury to the user or damage to the device it is essential that you read the<br />

information in this document <strong>and</strong> observe applicable national st<strong>and</strong>ards, safety requirements<br />

<strong>and</strong> accident prevention regulations.<br />

If this document is not in your native language <strong>and</strong> if you have any problems underst<strong>and</strong>ing the<br />

text, we advise you to contact your local office for assistance. The manufacturer can not accept<br />

responsibility for any damage or injury caused by misunderst<strong>and</strong>ing of the information in this<br />

document.<br />

This document is provided to help you establish operating conditions, which will permit safe <strong>and</strong><br />

efficient use of this device. Special considerations <strong>and</strong> precautions are also described in the<br />

document, which appear in the form of underneath icons.<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

7


1 SAFETY INSTRUCTIONS<br />

<strong>DK32</strong> - DK34 - DK37<br />

1.3.5 Warnings <strong>and</strong> symbols used<br />

Safety warnings are indicated by the following symbols.<br />

DANGER!<br />

This information refers to the immediate danger when working with electricity.<br />

DANGER!<br />

This warning refers to the immediate danger of burns caused by heat or hot surfaces.<br />

DANGER!<br />

This warning refers to the immediate danger when using this device in a hazardous atmosphere.<br />

DANGER!<br />

These warnings must be observed without fail. Even partial disregard of this warning can lead to<br />

serious health problems <strong>and</strong> even death. There is also the risk of seriously damaging the device<br />

or parts of the operator's plant.<br />

WARNING!<br />

Disregarding this safety warning, even if only in part, poses the risk of serious health problems.<br />

There is also the risk of damaging the device or parts of the operator's plant.<br />

CAUTION!<br />

Disregarding these instructions can result in damage to the device or to parts of the operator's<br />

plant.<br />

INFORMATION!<br />

These instructions contain important information for the h<strong>and</strong>ling of the device.<br />

LEGAL NOTICE!<br />

This note contains information on statutory directives <strong>and</strong> st<strong>and</strong>ards.<br />

• HANDLING<br />

This symbol designates all instructions for actions to be carried out by the operator in the<br />

specified sequence.<br />

i<br />

RESULT<br />

This symbol refers to all important consequences of the previous actions.<br />

1.4 Safety instructions for the operator<br />

WARNING!<br />

In general, devices from the manufacturer may only be installed, commissioned, operated <strong>and</strong><br />

maintained by properly trained <strong>and</strong> authorized personnel.<br />

This document is provided to help you establish operating conditions, which will permit safe <strong>and</strong><br />

efficient use of this device.<br />

8<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

DEVICE DESCRIPTION 2<br />

2.1 Scope of supply<br />

INFORMATION!<br />

Inspect the cartons carefully for damages or signs of rough h<strong>and</strong>ling. Report damage to the<br />

carrier <strong>and</strong> to the local office of the manufacturer.<br />

INFORMATION!<br />

Do a check of the packing list to make sure that you have all the elements given in the order.<br />

INFORMATION!<br />

Look at the device nameplate to ensure that the device is delivered according to your order.<br />

Check for the correct supply voltage printed on the nameplate.<br />

Figure 2-1: Scope of supply<br />

1 <strong>Flow</strong>meter in the version ordered<br />

2 Manual<br />

3 Certificates, calibration certificate (supplied to order only)<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

9


2 DEVICE DESCRIPTION<br />

<strong>DK32</strong> - DK34 - DK37<br />

2.2 Device versions<br />

• <strong>DK32</strong> with valve <strong>and</strong> horizontal connection<br />

• DK34 without valve <strong>and</strong> vertical connection<br />

• DK37 with valve <strong>and</strong> horizontal connection<br />

The following designs are available as options:<br />

• with inlet pressure regulator<br />

• with outlet pressure regulator<br />

Device versions<br />

1 <strong>DK32</strong> with valve - with horizontal connection<br />

2 DK34 without valve - with vertical connection<br />

3 DK37/M8E with valve <strong>and</strong> electronic display<br />

4 DK37/M8M with valve <strong>and</strong> mechanical display<br />

Versions with regulator<br />

1 <strong>DK32</strong> with inlet pressure regulator<br />

2 DK37 with inlet pressure regulator<br />

10<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

DEVICE DESCRIPTION 2<br />

2.3 Nameplate<br />

INFORMATION!<br />

Before installing the flowmeter, make sure that the information given on the nameplate<br />

corresponds to the ordering data.<br />

Figure 2-2: Nameplates<br />

1 Type of meter<br />

2 Manufacturer<br />

3 Appointed ATEX & DGRL body<br />

4 Design data: temperature & pressure rating<br />

5 DGRL data<br />

6 Ex data<br />

7 Electrical connection data<br />

8 Pay regard to manual<br />

9 KROHNE website<br />

Additional markings on the flowmeter:<br />

• SO - sales order / item<br />

• PA - order<br />

• Vx - product configurator code<br />

• AC - article code<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

11


2 DEVICE DESCRIPTION<br />

<strong>DK32</strong> - DK34 - DK37<br />

2.4 Description code<br />

Description code <strong>DK32</strong> DK34<br />

The description code consists of the following elements*:<br />

1 32 - with valve <strong>and</strong> horizontal connection / 34 without valve <strong>and</strong> vertical connection<br />

2 RE - inlet pressure regulator / RA - outlet pressure regulator<br />

3 K1 - one limit switch / K2 - two limit switches<br />

4 S - plug connector / L - cable gl<strong>and</strong> incl. cable<br />

5 HT - high-temperature version<br />

6 A - limit switch EC type-tested<br />

7 EX - Explosion-protected equipment<br />

8 SK - SIL2 compliance of limit switches acc. to IEC 61508<br />

* positions which are not needed are omitted (no blank positions)<br />

Description code DK37<br />

The description code* consists of the following elements:<br />

1 M8M - Mechanical display / M8E - Electronic display <strong>and</strong> signal output 4...20mA<br />

2 RE - Inlet pressure regulator / RA - Outlet pressure regulator<br />

3 K1 - one limit switch / K2 - two limit switches<br />

4 Ex is not part of the designation key<br />

5 SK - SIL2 compliance of limit switches acc. to IEC 61508<br />

SE - SIL1 compliance of current output acc. to IEC 61508<br />

* positions which are not needed are omitted (no blank positions)<br />

12<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

INSTALLATION 3<br />

3.1 Notes on installation<br />

INFORMATION!<br />

Inspect the cartons carefully for damages or signs of rough h<strong>and</strong>ling. Report damage to the<br />

carrier <strong>and</strong> to the local office of the manufacturer.<br />

INFORMATION!<br />

Do a check of the packing list to make sure that you have all the elements given in the order.<br />

INFORMATION!<br />

Look at the device nameplate to ensure that the device is delivered according to your order.<br />

Check for the correct supply voltage printed on the nameplate.<br />

3.2 Storage<br />

• Store the flowmeter in a dry <strong>and</strong> dust-free location.<br />

• Avoid lasting direct exposure to the sun.<br />

• Store the flowmeter in its original packaging.<br />

• The permissible storage temperature is from -40 to +80°C for st<strong>and</strong>ard meters.<br />

3.3 Installation requirements<br />

CAUTION!<br />

When installing the flowmeter in the piping please observe the following points:<br />

• The variable area flowmeter must be installed vertically (measuring principle). The flow<br />

direction must be from bottom to top. For installation recommendations please refer also to<br />

VDI/VDE Directive 3513 Sheet 3.<br />

• Before connecting, blow or flush out the pipes leading to the flowmeter.<br />

• Pipes for gas flow need to be dried before the flowmeter is installed.<br />

• Use connectors suitable for the particular version of the flowmeter.<br />

• Align the pipes axially with the connections on the flowmeter so that they are free of stresses.<br />

• If necessary, the piping has to be supported to prevent vibrations being transmitted to the<br />

flowmeter.<br />

• Do not lay signal cables directly next to cables for the power supply.<br />

• If several instruments are installed side by side, a minimum distance between these divices is<br />

required (see Technical Data).<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

13


4 ELECTRICAL CONNECTIONS<br />

<strong>DK32</strong> - DK34 - DK37<br />

4.1 Safety instructions<br />

DANGER!<br />

All work on the electrical connections may only be carried out with the power disconnected. Take<br />

note of the voltage data on the nameplate!<br />

DANGER!<br />

Observe the national regulations for electrical installations!<br />

DANGER!<br />

For devices used in hazardous areas, additional safety notes apply; please refer to the Ex<br />

documentation.<br />

WARNING!<br />

Observe without fail the local occupational health <strong>and</strong> safety regulations. Any work done on the<br />

electrical components of the measuring device may only be carried out by properly trained<br />

specialists.<br />

INFORMATION!<br />

Look at the device nameplate to ensure that the device is delivered according to your order.<br />

Check for the correct supply voltage printed on the nameplate.<br />

14<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

ELECTRICAL CONNECTIONS 4<br />

4.2 Electrical connection of limit switches<br />

The electrical connections for limit switches is effected:<br />

• DK../../S - in the plug connector<br />

• DK../../L - using a preassembled cable.<br />

The following procedures must be performed (DK../../S):<br />

• Slacken screw 6 of the connector plug<br />

• Pull out the plug<br />

• Remove screw 6 completely from the plug<br />

• Insert a screwdriver in the marked opening 5 (Lift) <strong>and</strong> remove the terminal block.<br />

• Thread the connecting cable through the cable gl<strong>and</strong>.<br />

• Insert the cable (max. 1.5mm 2 ) <strong>and</strong> screw down.<br />

Figure 4-1: Electrical connection of limit switches<br />

5 - Lift slot<br />

6 - Fastening screw of terminal box<br />

Contact connection<br />

Cable colors of assembled cable<br />

1 Min minus white<br />

2 Min plus yellow<br />

3 Max minus green<br />

4 Max plus brown<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

15


4 ELECTRICAL CONNECTIONS<br />

<strong>DK32</strong> - DK34 - DK37<br />

Connection three-wire reed contact<br />

Figure 4-2: Electrical connection of reed contact limit switch<br />

Str<strong>and</strong> colours for flowmeters with preassembled cables:<br />

1 Silicone-insulated wire - yellow/green / FEP-insulated wire - red<br />

2 Silicone-insulated wire - brown / FEP-insulated wire - brown<br />

3 Silicone-insulated wire - blue / FEP-insulated wire - blue<br />

4.3 Setting the limit switch<br />

Set the pointers to the desired limit values as a min. contact 1 <strong>and</strong> max. contact 2 using a slip<br />

coupling along the scale.<br />

Figure 4-3: Limit switch settings<br />

Adjusting the limit switch with reed contact:<br />

• Slacken nut 3<br />

• Set reed cartridge to the required value<br />

• Secure with nut 3<br />

Comment<br />

The reed contact is actuated directly by the float magnet. The desired operating point can only be<br />

determined in measuring mode. A reference to the scale <strong>and</strong>/or pointer cannot be established.<br />

16<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

ELECTRICAL CONNECTIONS 4<br />

4.4 DK37/M8M limit switches<br />

The limit switches can be set over the entire measuring range using the maximum pointer. The<br />

set limit values are displayed on the scale. The pointers are set to the desired limit values using<br />

a slip coupling along the scale.<br />

Figure 4-4: Limit switch setting<br />

1 Maximum pointer, switching point indicator<br />

2 Limit switch<br />

3 Connection board<br />

4 Connection terminal<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

17


4 ELECTRICAL CONNECTIONS<br />

<strong>DK32</strong> - DK34 - DK37<br />

4.5 DK37/M8E electrical signal output<br />

Figure 4-5: Electrical connection M8E<br />

1 Terminal connection<br />

2 Auxiliary power 14.8...30VDC<br />

3 Measurement signal 4...20mA<br />

4 External load, HART ® communication<br />

The circuitry for connection to other devices such as digital evaluator units or process control<br />

equipment must be designed with especial care. In some circumstances internal connections in<br />

these devices (e.g. GND with PE, ground loops) may lead to impermissible voltage potentials,<br />

which can compromise the function of the device itself or a connected device. In such cases a<br />

protected extra-low voltage (PELV) is recommended.<br />

Figure 4-6: Electrical connection with galvanic isolation<br />

1 Terminal connection<br />

2 Converter supply isolator with galvanic isolation<br />

3 Auxiliary power (see supply isolator information)<br />

4 Measurement signal 4...20mA<br />

5 External load, HART ® communication<br />

18<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

ELECTRICAL CONNECTIONS 4<br />

4.5.1 Power supply<br />

INFORMATION!<br />

The supply voltage has to be between 14.8VDC <strong>and</strong> 30VDC. This is based on the total resistance<br />

of the measuring loop. To determine this, add up the resistances of each component in the<br />

measuring loop (not including the meter).<br />

The required supply voltage can be calculated using the formula below:<br />

U ext. = R L * 22mA + 14.8V<br />

where<br />

U ext. = the minimum supply voltage <strong>and</strong><br />

R L = the total measuring loop resistance.<br />

INFORMATION!<br />

The power supply has to be able to supply a minimum of 22mA.<br />

4.5.2 Load for HART ® communication<br />

INFORMATION!<br />

For HART ® communication a load of at least 230 ohm is required.<br />

The maximum load impedance is calculated as follows:<br />

DANGER!<br />

Use a twisted two-core cable to prevent electrical interference from impeding the DC output<br />

signal.<br />

In some cases a shielded cable may be necessary. The cable shield may only be earthed<br />

(grounded) at one place (on the power supply unit).<br />

4.5.3 Parametrization<br />

The M8E electronic display can be parametrized via HART ® communications. DD (Device<br />

Descriptions) for AMS 6.x <strong>and</strong> PDM 5.2 <strong>and</strong> a DTM (Device Type Manager) are available for<br />

parametrization (download center).<br />

The current flowrate can be transmitted using the integral HART ® communications. A flow<br />

counter can be parametrized. Two limit values can be monitored. The limit values are assigned<br />

either to flow values or to the counter overflow. The limit values are not depicted on the display.<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

19


4 ELECTRICAL CONNECTIONS<br />

<strong>DK32</strong> - DK34 - DK37<br />

4.6 Ground connections<br />

The earthing can be done on the head piece of the measuring section (M4 threaded hole)<br />

Figure 4-7: Ground connections<br />

1 Earth connection on the measuring section<br />

DANGER!<br />

The earth conductor must not transfer any interference voltage.<br />

Do not use this earth conductor to ground any other items of electrical equipment.<br />

20<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

ELECTRICAL CONNECTIONS 4<br />

4.7 Protection category<br />

The variable area flowmeters <strong>DK32</strong> / DK34 / DK37 have been tested for ingress protection<br />

according to EN 60529. The following grades of protection are confirmed:<br />

Ingress Protection<br />

EN 60529<br />

Mechanical version<br />

without cable gl<strong>and</strong>s<br />

Electrical version<br />

with cable gl<strong>and</strong>s<br />

<strong>DK32</strong> / DK34 IP66 / IP68 IP65<br />

DK37 IP66 IP66<br />

DANGER!<br />

After all servicing <strong>and</strong> maintenance work on the flowmeter, the specified protection category has<br />

to be ensured again.<br />

Therefore it is essential to observe the following points:<br />

• Use only original gaskets. They must be clean <strong>and</strong> free of any damage. Defective gaskets have<br />

to be replaced.<br />

• The electrical cables used must be undamaged <strong>and</strong> must comply with regulations.<br />

• The cable has to be laid with a loop 3 upstream of the flowmeter to prevent water from<br />

getting into the housing.<br />

• The cable gl<strong>and</strong>s 2 have to be firmly tightened.<br />

• Close the unused cable gl<strong>and</strong>s using blanking plugs 1.<br />

• Do not remove the specified outer sheath from the cable gl<strong>and</strong>.<br />

Figure 4-8: Cable gl<strong>and</strong><br />

1 Close the unused cable gl<strong>and</strong>s using blanking plugs.<br />

2 The cable gl<strong>and</strong>s have to be firmly tightened.<br />

3 The cable has to be laid with a loop.<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

21


5 START-UP<br />

<strong>DK32</strong> - DK34 - DK37<br />

5.1 St<strong>and</strong>ard device<br />

CAUTION!<br />

When starting up the device, the following points must be observed:<br />

• Compare the actual operating pressure <strong>and</strong> the product temperature of the system with the<br />

specifications on the nameplate (PS <strong>and</strong> TS). These specifications may not be exceeded.<br />

• Make sure materials are compatible.<br />

• Slowly open the shut-off valve.<br />

• When measuring liquids, vent the pipes carefully.<br />

• When measuring gases, increase pressure slowly.<br />

• Avoid float impact (e.g. caused by solenoid valves), as this is likely to damage the measuring<br />

unit or float.<br />

22<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

SERVICE 6<br />

6.1 Maintenance<br />

Within the scope of routine maintenance of the system <strong>and</strong> pipelines, the flowmeter should also<br />

be inspected for signs of fouling, corrosion, mechanical wear <strong>and</strong> leaks, as well as damage to<br />

the measuring tube <strong>and</strong> indicator.<br />

We advise that inspections be carried out at least once a year.<br />

The device must be removed from the piping before cleaning.<br />

CAUTION!<br />

Pressurized pipes must be depressurized before removing the device.<br />

In the case of flowmeters used for measuring aggressive or hazardous products, appropriate<br />

safety precautions must be taken with regard to residual liquids in the measuring section.<br />

Always use new gaskets when reinstalling the flowmeter in the pipeline.<br />

CAUTION!<br />

Under certain circumstances the valve packing gl<strong>and</strong> may have to be adjusted during its service<br />

life. This means that the union nut 1 has to be retightened. If necessary, press the retaining pin<br />

2 against its internal spring.<br />

Apply a tightening torque of not more than 5Nm.<br />

CAUTION!<br />

Valves that have not been actuated for a longer period of time may exhibit a higher initial<br />

actuation torque.<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

23


6 SERVICE<br />

<strong>DK32</strong> - DK34 - DK37<br />

6.2 Spare parts availability<br />

The manufacturer adheres to the basic principle that functionally adequate spare parts for each<br />

device or each important accessory part will be kept available for a period of 3 years after<br />

delivery of the last production run for the device.<br />

This regulation only applies to spare parts which are subject to wear <strong>and</strong> tear under normal<br />

operating conditions.<br />

6.3 Availability of services<br />

The manufacturer offers a range of services to support the customer after expiration of the<br />

warranty. These include repair, maintenance, technical support <strong>and</strong> training.<br />

INFORMATION!<br />

For more precise information, please contact your local representative.<br />

6.4 Returning the device to the manufacturer<br />

6.4.1 General information<br />

This device has been carefully manufactured <strong>and</strong> tested. If installed <strong>and</strong> operated in accordance<br />

with these operating instructions, it will rarely present any problems.<br />

CAUTION!<br />

Should you nevertheless need to return a device for inspection or repair, please pay strict<br />

attention to the following points:<br />

• Due to statutory regulations on environmental protection <strong>and</strong> safeguarding the health <strong>and</strong><br />

safety of our personnel, manufacturer may only h<strong>and</strong>le, test <strong>and</strong> repair returned devices that<br />

have been in contact with products without risk to personnel <strong>and</strong> environment.<br />

• This means that the manufacturer can only service this device if it is accompanied by the<br />

following certificate (see next section) confirming that the device is safe to h<strong>and</strong>le.<br />

CAUTION!<br />

If the device has been operated with toxic, caustic, flammable or water-endangering products,<br />

you are kindly requested:<br />

• to check <strong>and</strong> ensure, if necessary by rinsing or neutralizing, that all cavities are free from<br />

such dangerous substances,<br />

• to enclose a certificate with the device confirming that is safe to h<strong>and</strong>le <strong>and</strong> stating the<br />

product used.<br />

24<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

SERVICE 6<br />

6.4.2 Form (for copying) to accompany a returned device<br />

Company:<br />

Address:<br />

Department:<br />

Name:<br />

Tel. no.:<br />

Fax no.:<br />

Manufacturer's order no. or serial no.:<br />

The device has been operated with the following medium:<br />

This medium is:<br />

water-hazardous<br />

toxic<br />

caustic<br />

flammable<br />

We checked that all cavities in the device are free from such<br />

substances.<br />

We have flushed out <strong>and</strong> neutralized all cavities in the<br />

device.<br />

We hereby confirm that there is no risk to persons or the environment through any residual media<br />

contained in the device when it is returned.<br />

Date:<br />

Signature:<br />

Stamp:<br />

6.5 Disposal<br />

CAUTION!<br />

Disposal must be carried out in accordance with legislation applicable in your country.<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

25


7 TECHNICAL DATA<br />

<strong>DK32</strong> - DK34 - DK37<br />

7.1 Operating principle<br />

The flowmeter operates on the float measuring principle.<br />

The measuring section consists of a metal cone in which a float can move freely up <strong>and</strong> down.<br />

The medium flows through the flowmeter from bottom to top.<br />

The float adjusts itself so that the buoyancy force A acting on it, the form drag W <strong>and</strong> its weight G<br />

are in equilibrium: G = A + W.<br />

Figure 7-1: Operating principle<br />

For the <strong>DK32</strong>, DK34 <strong>and</strong> DK37/M8M 1 the flow-dependent height of the float in the measuring<br />

section is transmitted by means of a magnetic coupling <strong>and</strong> displayed on a scale.<br />

For the DK37/M8E 2 the flow-dependent height of the float in the measuring section is<br />

transmitted to the electronic display by means of a magnetic coupling on sensors S1 <strong>and</strong> S2.<br />

26<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

TECHNICAL DATA 7<br />

7.2 Technical data<br />

INFORMATION!<br />

• The following data is provided for general applications. If you require data that is more<br />

relevant to your specific application, please contact us or your local representative.<br />

• Additional information (certificates, special tools, software,...) <strong>and</strong> complete product<br />

documentation can be downloaded free of charge from the website (Download Center).<br />

Measuring system<br />

Application range<br />

Operating method / measuring principle<br />

Measured value<br />

Primary measured value<br />

Secondary measured value<br />

<strong>Flow</strong> measurement of liquids, gases <strong>and</strong> vapors<br />

Float measuring principle<br />

Float position<br />

Operating <strong>and</strong> st<strong>and</strong>ard volumetric flow<br />

Measuring accuracy<br />

Directive VDI / VDE Code 3513 Sheet 2 (q G =50%)<br />

<strong>DK32</strong> DK34 4.0%<br />

DK37 2.5%<br />

Operating conditions<br />

Max. operating temperature TS<br />

Operating pressure PS<br />

Test pressure PT<br />

-80..+200°C / -112...+392°F<br />

Pressure Equipment Directive 97/23/EC<br />

Pressure Equipment Directive 97/23/EC <strong>and</strong> AD 2000-HP30<br />

Max. allowable operating pressure PS 130 bar st<strong>and</strong>ard 1<br />

Protection category<br />

<strong>DK32</strong> / DK34 without cable gl<strong>and</strong>s<br />

<strong>DK32</strong> / DK34 with cable gl<strong>and</strong>s<br />

DK37<br />

IP66 <strong>and</strong> IP68<br />

IP65<br />

IP66<br />

Installation conditions<br />

Inlet / outlet run<br />

1 higher pressures on request<br />

non<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

27


7 TECHNICAL DATA<br />

<strong>DK32</strong> - DK34 - DK37<br />

Materials<br />

Head piece, foot piece, cone<br />

CrNi steel 1.4404 / 316 L<br />

upper plug<br />

CrNi steel 1.4404 / 316 L<br />

St<strong>and</strong>ard float<br />

CrNi steel 1.4404 / 316 L or titanium<br />

Metering unit<br />

CrNi steel 1.4571 / 316 Ti<br />

Valve spindle<br />

CrNi steel 1.4404 / 316 L<br />

Valve plug gasket FPM 1<br />

Metering unit gasket FPM <strong>and</strong> PTFE 1<br />

Indicator housing <strong>DK32</strong> 34<br />

Die-cast Aluminium, coated<br />

Indicator housing DK37<br />

PPS<br />

1 other gasket materials on request<br />

Temperatures<br />

Max. process temperature at T amb. < 40°C / 104°F [°C]<br />

[°F]<br />

<strong>DK32</strong> with valve -40...+150 1 -40...+302 1<br />

DK34 without valve -80...+150 1 -112...+302 1<br />

<strong>DK32</strong> DK34 with limit switches -25/-40...+145 -13/-40...+293<br />

DK37M8M without valve -80...+150 1 -112...+302 1<br />

DK37M8M with valve -40...+150 1 -40...+302 1<br />

DK37/M8M with limit switches -25/-40...+150 13/-40...+302<br />

DK37M8E with electronical indicator -25...+135 -13...+275<br />

Max. ambient temperature T amb. -25...+70 -13...+158<br />

1 High temperature version up to 200°C / 392°F<br />

28<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

TECHNICAL DATA 7<br />

Indicators of <strong>DK32</strong> DK34 DK37/M8M with limit switches<br />

<strong>DK32</strong> - 34 /K./S<br />

DK37M8M<br />

Cable fitting M16 x 1,5<br />

Clamp terminal 1,5mm 2<br />

<strong>DK32</strong> - 34 /K./S Clamping range 4,5... 10mm<br />

DK37M8M Clamping range 3...7mm<br />

<strong>DK32</strong> - 34/K./L ∅ Connecting cable approx. 7mm<br />

Cable length<br />

approx. 1.7m (other length on request)<br />

Limit switch<br />

SC2-N0 SJ2-SN 1 SJ2-S1N 1<br />

I7S2002-N<br />

Type NAMUR 2-wire 2-wire 2-wire<br />

Switch element function<br />

Normally Normally Normally open<br />

closed closed<br />

Nominal voltage U 0 8VDC 8VDC 8VDC<br />

Pointer shaft not read ≥3mA ≥3mA ≤1mA<br />

Pointer shaft read ≤1mA ≤1mA ≥3mA<br />

<strong>DK32</strong> DK34 with reed contact Switching type bistable<br />

Switching reproducibility


7 TECHNICAL DATA<br />

<strong>DK32</strong> - DK34 - DK37<br />

M8E HART ® parameter configuration<br />

Name of manufacturer (code) KROHNE Messtechnik (69)<br />

Name of model M8E (230)<br />

HART ® protocol revision 5.1<br />

Device revision 1<br />

Physical layer<br />

FSK<br />

Device category<br />

Transmitter<br />

M8E process variable<br />

M8E process variable flow Values [%] Signal output [mA]<br />

Over range +102,5 (±1%) 20,24...20,56<br />

Device error detection >106,25 ≥21,00<br />

Maximum 112,5 22<br />

Multi-drop operation - 4,5<br />

Min. U ext.<br />

14,8VDC<br />

Approvals<br />

St<strong>and</strong>ard Indicator Designation<br />

ATEX <strong>DK32</strong> DK34 mechanical II2GD IIC<br />

II3GD IIC<br />

<strong>DK32</strong> DK34 electrical II2G Ex ia IIC T6<br />

DK37 mechanical II2GD IIC<br />

II3GD IIC<br />

DK37 electrical<br />

II2G Ex ia IIC T6<br />

IEC Ex <strong>DK32</strong> DK34 electrical Ex ia IIC T6<br />

FM <strong>DK32</strong> DK34 IS/I/1/ABCD;T6<br />

NI/I/2/ABCD;T6<br />

S/II, III/2/FG;T6<br />

IS/I, II, III/1/A-G<br />

NI/II/2/ABCD<br />

Nepsi <strong>DK32</strong> DK34 Ex nA II T1-T6<br />

DK37<br />

Ex ia IIC T1-T6<br />

30<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

TECHNICAL DATA 7<br />

7.3 Dimensions<br />

Dimensions, <strong>DK32</strong> DK34<br />

a b c d<br />

Device [mm] ["] [mm] ["] [mm] ["] [mm] ["]<br />

1 <strong>DK32</strong> with valve <strong>and</strong><br />

horizontal process<br />

connections<br />

2 DK34 without valve<br />

<strong>and</strong> vertical process<br />

connections<br />

3 <strong>DK32</strong> DK34 with<br />

limit switches K1/K2<br />

4 <strong>DK32</strong> with flange<br />

connections<br />

42 1,66 118 4,65 90 3,55 100 3,94<br />

42 1,66 110 4,33 - - 75 3,07<br />

46 1,81 approx.<br />

90<br />

ca. 3,55 1500 50,1 approx.<br />

50<br />

- - 250 10,2 90 3,55 approx.<br />

195<br />

ca. 1,97<br />

ca. 7,68<br />

<strong>DK32</strong> <strong>DK32</strong> DK34 DK34<br />

<strong>DK32</strong> (DK34) with K1/K2 <strong>DK32</strong> (DK34) with K1/K2 <strong>DK32</strong> with flange connections<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

31


7 TECHNICAL DATA<br />

<strong>DK32</strong> - DK34 - DK37<br />

DK37 dimensions<br />

a b c d approx.<br />

Device [ mm] ["] [ mm] ["] [ mm] ["] [ mm] ["]<br />

1 DK37/M8E with<br />

valve <strong>and</strong> horizontal<br />

process connections<br />

2 DK37/M8E with<br />

valve on top<br />

3 DK37/M8M/K . with<br />

valve <strong>and</strong> horizontal<br />

process connections<br />

4 DK37/M8M/K .<br />

without valve <strong>and</strong><br />

vertical process<br />

connections<br />

5 DK37/M8E without<br />

valve <strong>and</strong> vertical<br />

process connections<br />

56 2,21 153 6,03 125 4,92 144 ca. 5,67<br />

56 2,21 183 7,21 155 6,11 144 ca. 5,67<br />

56 2,21 153 6,03 125 4,92 160 ca. 6,15<br />

56 2,21 145 5,71 145 5,71 144 ca. 5,52<br />

56 2,21 145 5,71 145 5,71 121 ca. 4,77<br />

DK37/M8M with valve DK37/M8E with valve DK37/M8E with valve on top<br />

DK37/M8M with K1/K2<br />

DK37/M8M without valve <strong>and</strong><br />

vertical connections<br />

DK37/M8E without valve <strong>and</strong><br />

vertical connections<br />

32<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

TECHNICAL DATA 7<br />

Min. installation distance<br />

If several instruments are installed side by side, a minimum distance betwween these<br />

instruments is required.<br />

Min. distance<br />

Device [mm] ["]<br />

1 <strong>DK32</strong> / DK34 60 2,36<br />

2 DK37/M8M 100 3,94<br />

2 DK37/M8E 120 4,73<br />

Weights<br />

Approx. weights [g] ca. [lb]<br />

<strong>DK32</strong> 700 1,54<br />

DK34 600 1,32<br />

DK37/M8M 800 1,76<br />

DK37/M8E 1000 2,21<br />

<strong>DK32</strong> with differential pressure regulators 2500 5,51<br />

DK37/M8E with differential pressure regulators 2800 6,18<br />

DK37/M8M with differential pressure regulators 2600 5,73<br />

Connections<br />

St<strong>and</strong>ard 1/4" NPT inside thread<br />

G 1/4, Ermeto, Serto, Dilo, Gyrolok, Swagelok, flanges 1<br />

1 other connections on request<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

33


7 TECHNICAL DATA<br />

<strong>DK32</strong> - DK34 - DK37<br />

7.4 <strong>Flow</strong> table<br />

Measuring span: 10 : 1<br />

Declaration of flow: Values = 100%<br />

Water: 20°C [68°F]<br />

Air: 20°C [68°F], 1,2 bar abs. [17.4 psia]<br />

Water flow rate Air flow rate Pressure drop<br />

Cones [l/h] [GPH] [Nl/h] [SCFH] [mbar] [psig]<br />

K 005 - - 16 1 0.6 1 14 0.21<br />

K 005 - - 50 1.9 31 0.46<br />

K 010 1.5 1 0.40 1 70 1 2.6 1 66 0.97<br />

K 010 3 0.8 100 3.7 66 0.97<br />

K 015 5 1.3 150 5.6 19 0.28<br />

K 040 10 2.5 400 15 27 0.40<br />

K 080 25 6.5 800 30 55 0.81<br />

K 125 40 11 1250 45 42 0.62<br />

K 200 60 16 2000 75 85 1.25<br />

K 300 80 20 2500 90 117 1.72<br />

K 340 100 25 3400 130 166 2.44<br />

1 with titanium float<br />

INFORMATION!<br />

The operating pressure should be at least twice the pressure loss for liquids, <strong>and</strong> at least 5<br />

times the pressure loss for gases! The specified pressure drops are valid for water <strong>and</strong> air at<br />

maximum flow rate. Other flow ranges on request. Conversion of other media or operating data<br />

(pressure, temperature, density, viscosity) is performed using the calculation method in<br />

accordance with VDI /VDE Directive 3513<br />

Reference condition for gas measurements:<br />

The flow measurement of gases are refered to<br />

Nl/h or Nm 3 /h: Volume flow in Normal state 0°C, 1.013 bar abs. (DIN 1343)<br />

SCFM or SCFH: Volume flow in St<strong>and</strong>ard state 15°C, 1.013 bar abs. (ISO 13443)<br />

34<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

TECHNICAL DATA 7<br />

Valves<br />

Measuring span: 10 : 1<br />

Declaration of flow: Values = 100%<br />

Water: 20°C [68°F]<br />

Air: 20°C [68°F], 1,2 bar abs. [17.4 psia]<br />

only <strong>DK32</strong> <strong>and</strong> DK37 Max. low rate Qv Characteristic<br />

Valve spindle Water Air Kv Cv<br />

Cones Ø [mm] Ø ["] [l/h] [GPH] [Nl/h] [SCFH] [m 3 /h] [GPM]<br />

K 005 - K 010 1 0,039 5 1,32 100 3,72 0.018 0,021<br />

K 015 - K 040 - K 080 2.5 0,98 50 13,2 1000 37,2 0.15 0,175<br />

K 125 ... K 340 4.5 0,177 160 42,3 4300 160 0.48 0,552<br />

Valve characteristics<br />

Spindle 1,0mm - 0,039" Spindle 2,5mm - 0,098"<br />

Spindle 4,5mm - 0,177"<br />

1 <strong>Flow</strong>, air<br />

2 <strong>Flow</strong>, water<br />

3 Spindle rotation n<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

35


7 TECHNICAL DATA<br />

<strong>DK32</strong> - DK34 - DK37<br />

7.5 Differential pressure regulators<br />

Differential pressure regulators are used (<strong>DK32</strong> <strong>and</strong> DK37 only) to help maintain constant flow<br />

rates in the case of fluctuating inlet or outlet pressures. Minimum pressure levels are required<br />

to permit operation of the regulators (see Regulator characteristics).<br />

Differential pressure regulators are not pressure reducing valves!<br />

1 Inlet pressure regulators, types RE, NRE<br />

The regulators maintain a constant flow rate at variable inlet pressure <strong>and</strong> constant outlet<br />

pressure.<br />

Example: Inlet pressure regulator RE-1000: Current flow rate: 1000l/h air<br />

Constant outlet pressure 1.013 bar abs.<br />

p2:<br />

With a variable inlet pressure greater than 0.5 bar the flow rate in the device is constant.<br />

2 Outlet pressure regulators types RA, NRA<br />

The regulators maintain a constant flow rate at constant inlet pressure <strong>and</strong> variable outlet<br />

pressure.<br />

In order to function, there must be pressure difference between the inlet pressure <strong>and</strong><br />

the outlet pressure. The inlet pressure p1 must always be greater than the outlet pressure p2.<br />

Example: Outlet pressure regulator NRA- Current flow rate:<br />

800l/h air<br />

800<br />

Constant inlet pressure: 6 bar<br />

With a variable outlet pressure of 0...5.5 bar the flowrate in the device remains constant.<br />

Regulator characteristics<br />

1 Inlet pressure regulators, types RE <strong>and</strong><br />

NRE<br />

2 Outlet pressure regulators, types RA <strong>and</strong><br />

NRA<br />

36<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

TECHNICAL DATA 7<br />

Control range<br />

Measuring span: 10 : 1<br />

Declaration of flow: Values = 100%<br />

Water: 20°C [68°F]<br />

Air: 20°C [68°F], 1,2 bar abs. [17.4 psia]<br />

Inlet pressure regulator 1<br />

Max. flowrate<br />

Water Air Min. inlet pressure<br />

[l/h] [GPH] [Nl/h] [SCFH] p1 [bar] p1 [psig]<br />

RE-1000 ...40 ...11 ...1000 ...37 0.5 7,25<br />

RE-4000 ...80 ...20 ...2000 ...75 1 14,5<br />

...100 ...25 …3000 ...110 1.5 21,8<br />

...160 ...42 ...4000 ...150 2 29<br />

NRE-100 ...2.5 ...0.6 ...100 ...3,7 0.1 1,45<br />

NRE-800 - - …250 ...9,0 0.1 1,45<br />

- - …800 ...30 0.2 2,9<br />

...25 ...6.60 - - 0.4 5,8<br />

Outlet pressure regulator 2<br />

Max. flowrate<br />

Water Air Min. pressure diff. *<br />

[l/h] [GPH] [Nl/h] [SCFH] Δp [bar] Δp [psig]<br />

RA-1000 ...40 ...11 ...1000 ...37 0,4 5,8<br />

RA-4000 ...100 ...25 …2000 ...75 1,2 17,4<br />

- - ...3000 ...110 1,2 17,4<br />

...160 ...42 ...4000 ...150 1,5 21,8<br />

NRA-800 ...1 ...0.25 ...250 ...9,0 0,05 0,73<br />

- - ...500 ...19 0,1 1,45<br />

- - …800 ...30 0,2 2,9<br />

...25 ...6.6 - - 0,4 5,8<br />

Table 7-1: * Pressure difference between inlet <strong>and</strong> outlet pressure<br />

Reference condition for gas measurements:<br />

The flow measurement of gases are refered to<br />

Nl/h or Nm 3 /h: Volume flow in Normal state 0°C, 1.013 bar abs. (DIN 1343)<br />

SCFM or SCFH: Volume flow in St<strong>and</strong>ard state 15°C, 1.013 bar abs. (ISO 13443)<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

37


7 TECHNICAL DATA<br />

<strong>DK32</strong> - DK34 - DK37<br />

Technical data, differential pressure regulator<br />

St<strong>and</strong>ard connections<br />

Option<br />

Max. operating gauge pressure (at 20°C)<br />

1/4" NPT<br />

Serto, Ermeto 6 or 8, tube nozzle 6mm or 8mm, Dilo,<br />

Gyrolok, Swagelok, G 1/4<br />

64 bar / 928psig<br />

Medium temperature 150°C / 302°F<br />

Material CrNi-Steel 1.4404<br />

Gasket<br />

Membrane<br />

O-ring<br />

PTFE<br />

PTFE filled with carbon / graphite<br />

FPM<br />

other connections <strong>and</strong> materials, higher temperatures <strong>and</strong> pressures on request<br />

Dimensions with differential pressure regulators<br />

a (approx.) b (approx.) c d<br />

[mm] ["] [mm] ["] [mm] ["] [mm] ["]<br />

<strong>DK32</strong> 230 9.1 163 6.4 70 2.8 23 0.91<br />

DK37 230 9.1 200 7.9 70 2.8 23 0.91<br />

DK37/M8M 1 230 9.1 230 9.1 70 2.8 23 0.91<br />

1 with outlet pressure regulator<br />

<strong>DK32</strong> with inlet pressure regulator<br />

DK37/M8E <strong>and</strong> M8M with inlet pressure<br />

regulator<br />

<strong>DK32</strong> with outlet pressure regulator<br />

DK37/M8E with outlet pressure regulator<br />

38<br />

www.krohne.com<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en


<strong>DK32</strong> - DK34 - DK37<br />

NOTES 8<br />

01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en<br />

www.krohne.com<br />

39


KROHNE product overview<br />

© KROHNE 01/2012 - 4000287103 MA <strong>DK32</strong>-34-37-R05-en - Subject to change without notice.<br />

• Electromagnetic flowmeters<br />

• <strong>Variable</strong> area flowmeters<br />

• Ultrasonic flowmeters<br />

• Mass flowmeters<br />

• Vortex flowmeters<br />

• <strong>Flow</strong> controllers<br />

• Level meters<br />

• Temperature meters<br />

• Pressure meters<br />

• Analysis products<br />

• Measuring systems for the oil <strong>and</strong> gas industry<br />

• Measuring systems for sea-going tankers<br />

Head Office KROHNE Messtechnik GmbH<br />

Ludwig-<strong>Krohne</strong>-Str. 5<br />

D-47058 Duisburg (Germany)<br />

Tel.:+49 (0)203 301 0<br />

Fax:+49 (0)203 301 10389<br />

info@krohne.de<br />

The current list of all KROHNE contacts <strong>and</strong> addresses can be found at:<br />

www.krohne.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!