HGP-SIV Energy meter - Brunata

HGP-SIV Energy meter - Brunata HGP-SIV Energy meter - Brunata

<strong>HGP</strong>-<strong>SIV</strong> <strong>Energy</strong> <strong>meter</strong><br />

Installation and users manual


Please read this before installation<br />

This manual is intended for skilled personal having a formal knowledge to <strong>meter</strong>s.<br />

The <strong>Brunata</strong> <strong>HGP</strong>-<strong>SIV</strong> energy <strong>meter</strong> must only be used and installed as described in the<br />

manual.<br />

The working data of the <strong>meter</strong> are shown on the label of the <strong>meter</strong>. For further information<br />

we refer to the data sheet.<br />

IMPORTANT: Seals and void labels must not be removed or damaged. This will infringe<br />

the warranty of the <strong>meter</strong>.<br />

The <strong>meter</strong> contains of following parts:<br />

1. Flow sensor<br />

2. Flow electronic unit<br />

3. Display unit<br />

4. Signal cable between flow electronics and display unit<br />

5. Two paired temperature sensors with sensor pockets<br />

6. Installation and users manual<br />

When unpacking the <strong>meter</strong>, please check that all parts are enclosed. The serial numbers<br />

of the flow sensor, the electronic units, and the temperature sensors must be identical,<br />

since the parts are calibrated. The serial number is also programmed into the memory<br />

of the <strong>meter</strong>, the Service Menu.<br />

Versions and ordering code<br />

x: Flow of the <strong>meter</strong><br />

(q p<br />

)in m 3 /h<br />

yy: Connectionsize:<br />

-39: G2B x 300 mm<br />

-40: DN40 x 300 mm<br />

-50: DN50 x 270 mm<br />

-65: DN65 x 300 mm<br />

-80: DN80 x 300 mm<br />

-100: DN100 x 360 mm<br />

-125: DN125 x 360 mm<br />

-150: DN150 x 500 mm<br />

z: Menu/display:<br />

184: Standard version<br />

with peak values<br />

185: Heat- / cooling <strong>meter</strong><br />

188: Tariff <strong>meter</strong><br />

<strong>HGP</strong>-<strong>SIV</strong>x-yy-18z/ABCDEF<br />

A: Power supply:<br />

1: 230 VAC<br />

2: 24 VAC<br />

B: Display backlight:<br />

B: with /-: without<br />

C: External <strong>meter</strong>s:<br />

0, 1 or 2<br />

D: Kommunikationsmodul:<br />

M-Bus / LonWorks / RS232<br />

/ - none<br />

E: No. of accounting periods:<br />

0 / 6 / 12 / 24<br />

F: Programmed for Glycol<br />

(% in service menu)


Installation<br />

Preparation for installation<br />

Please note that the installation must be done in such a way that it meets the requirements<br />

for internal fitting, distances that have to be respected, etc. Straight pipe sections<br />

before or after the <strong>meter</strong> are not required.<br />

It is recommended that stop valves are fitted before and after the <strong>meter</strong> to<br />

make it easier to remove and reinstall the <strong>meter</strong> if service and verification are<br />

required. To ensure that there are no foreign bodies in the pipe section, it is recommended<br />

that the pipes are flushed through before the <strong>meter</strong> is installed. A<br />

adapter pipe can be used for this purpose. After installation, the valves should<br />

be opened in the order which provides correct flow through the <strong>meter</strong>.<br />

The HG-<strong>meter</strong> has been approved for installation in industrial areas, but it is recommended<br />

that installation close to components that may cause strong electromagnetic<br />

interference is avoided.<br />

Installation of the flow sensor<br />

The flowsensor is installed with the arrow in the flow direction. The flow sensor can<br />

be installed in any direction (vertically, horizontally etc), only the flow sensor must always<br />

be filled with water when running. Do not insulate the housing of the flow sensor.<br />

The <strong>meter</strong>’s type label will indicate whether the flow sensor should be fitted on the return<br />

pipe (low temperature) or the supply pipe (high temperature). Please note that if the <strong>meter</strong><br />

is used in a cooling system, the supply pipe is low temperature.<br />

Fitting and connection of flow electronic unit, fig. 1<br />

Place the flow electronic unit on an even surface with 3 screws. All connections to the<br />

<strong>meter</strong> must be fitted before mains voltage is connected.<br />

The connection cable from the Flow Sensor is inserted into the socket marked Flow<br />

Head [8] in fig. 1. Note the locking system and how the cable exits the box. To dismantle<br />

the plug, use a small screwdriver to lift the lock. Never shorten nor lengthen the cables<br />

for the flowsensor. If the cable must be rolled up, the dia<strong>meter</strong> of the roll should<br />

at least be 30 cm.<br />

The power supply cable (230 or 24 V) is inserted through the strain relief, which must<br />

be tightened before tightening the terminal connections [1] in fig. 1.<br />

Signal cable to display unit are installed in terminals A1, A2, B1 and B2, [11] in fig. 1.


Fitting and connection of display unit, fig 2<br />

Place the display unit on an even surface with 3 screws. All connections to the <strong>meter</strong><br />

must be fitted before mains voltage is connected.<br />

The connecting cable from flow electronic unit is connected to plug M57, see fig 4.<br />

The other cables that need to be connected are led through rubber membrane and<br />

bypass and connected with their respective terminals. Temperature sensors are connected<br />

with terminal [2] and [3], pulse inputs with terminal [9] and [10], and the remote<br />

reading with terminal [5] and [6]. A small screwdriver or the like can be used to perforate<br />

the rubber membrane.<br />

The power supply cable for 230 Volt (possibly 24 Volt) is led through the rubber<br />

membrane and connected with terminal [4] in fig.1, then the strain relief is tightened<br />

moderately. Earth connection is not required.


NINGSKLEMMER<br />

Connecting terminals<br />

Flow electronic unit<br />

24 V AC)<br />

ængde<br />

abel<br />

isplayenhed *<br />

ndstikskort *<br />

Fig. 1 Connecting <br />

terminals <strong>HGP</strong> flow electronics<br />

<br />

No. Indication Connection <br />

1 230 VAC Power (24VAC is possible)<br />

2 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />

3 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />

4 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />

5 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />

13<br />

4 5 6 7 8<br />

på <strong>HGP</strong>-<strong>SIV</strong><br />

varme rør (rød)<br />

kolde rør (blå)<br />

an være 24VAC)<br />

r datakommunikation, M-Bus, Lon eller RS232<br />

r datakommunikation, M-Bus, Lon eller RS232<br />

pulsudgang, volumen<br />

12<br />

11<br />

10<br />

6 - VOL. + Pulse out, water volume<br />

7 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />

8 FLOWHEAD Plug for flow sensor cable<br />

9 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />

10 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />

11 A1, A2, B1, B2 Cable connection to Display unit*<br />

12 HF-udgang Connection to insertion module*<br />

* see next page<br />

9<br />

<br />

<br />

forsyning<br />

<br />

<br />

erafhængigaf<br />

måleresstørrelse.<br />

Fremgåraftypeskiltet.<br />

<br />

harsamme


Ledningsförbindelser och anslutningsklämmer<br />

Displayenhet Display unit<br />

1<br />

13<br />

12<br />

11<br />

10<br />

9<br />

2 3 4<br />

5 6 7 8<br />

NR. MÄRKNING ANSLUTNING Fig. 2 Connecting terminals <strong>HGP</strong>-<strong>SIV</strong> Display Unit<br />

1 FLÖDESSENSOR .. 4-polig, skärmad stickkontakt till flödessensorkabel<br />

PULSVÄRDEN:<br />

2 HIGH Nr. TEMP. Indication ........... Temperatursensor, Installation varma rör (röd)<br />

3 LOW TEMP............. Temperatursensor, kalla rör (blå)<br />

Mätarens volymp<br />

4 230 VAC.................. 1 FLOWSENSOR Strömspänning Not (Kan in use vara on 24 <strong>HGP</strong>-<strong>SIV</strong> VAC)<br />

är beroende av<br />

5 A1 B1. ................... 1. Anslutning av datakommunikation, M-Bus, Lon eller RS232 mätarens storlek.<br />

2 HIGH TEMP. Temp. sensor, high<br />

6 A2 B2. ................... 2. Anslutning av datakommunikation, M-Bus, Lon eller RS232 Framgår av<br />

7 - VOL. 3+................... LOW TEMP. Öppen kollektor Temp. pulsutgång, sensor, low volym<br />

typmärket.<br />

8 - ENERGI +. ............ Öppen kollektor pulsutgång, energi<br />

4 230 V AC. Power (24VAC is possible)<br />

Energipuls har<br />

9 - AUX2 +. ................ Extern pulsingång från t ex elmätare<br />

samma värde som<br />

10 - AUX1 5+. ................ A1 B1. Extern pulsingång 1 st Installation från t ex of kallvattenmätare<br />

datacommunication, MBus, Lon or RS232 sista siffran i<br />

11 Kontakter 1 & 2 ....... Kontakter för tillkoppling av intern +5 V till AUX- ingångarna<br />

displayen.<br />

12 0 V +5<br />

6<br />

V. ................<br />

A2 B2.<br />

Genemsam<br />

2<br />

noll nd Installation<br />

och +5 V DC<br />

of datacommunication,<br />

utgång<br />

MBus, Lon or RS232<br />

Har t ex MWh-display<br />

13 M52. ........................ 7 - VOL. +. Stickkontakt Open för datakommunikationskort, collector pulse out, volume M-Bus, Lon eller RS232<br />

siffror efter kommat, ä<br />

8 - ENERGI +. Open collector pulse out, energy<br />

9 - AUX2 +. External incoming pulse from f.inst. electricity <strong>meter</strong><br />

Pulsutgångar för volym och energi<br />

Pulsutgångens 10 optokopplare - AUX1 +. strömförsörjs External via belastningsmotstånd incoming pulse from R, f.inst. som dimensioneras cold water <strong>meter</strong> enl. tabell<br />

11 Switches 1 & 2 Switches for connection of internal +5V to AUX terminals<br />

Inställning 12 av 0 extern V +5 V. +Vmax<br />

<br />

Common<br />

V 1.5V<br />

zero and 28 V +5V DC exit<br />

Motstånd R<br />

strömförsörjning<br />

R <br />

Imax 20 mA<br />

13 M52. Connector 5mA<br />

for data<br />

(från mätare: 5 VDC)<br />

Von max 1,5 V communication module, MBus, Lon<br />

or RS232<br />

+V R för I=5 mA<br />

ton=toff=140 ms är standardinställning<br />

Values of pulse<br />

Pulsperiod T= ton + toff = 280 ms.<br />

5 700 <br />

+<br />

+Voff<br />

10 Volume 1,7 pulse k HGG-<strong>SIV</strong>-<strong>meter</strong> pulse value depends on size of the <strong>meter</strong>. Please consult<br />

15 the type 2,7 sign. k<br />

20 <strong>Energy</strong> 3,7 pulse k has the same Von value as toff the ton last digit in display.<br />

24<br />

GND (0V)<br />

4,5 k<br />

Fig. 2 Anslutningsexempel för<br />

F.inst. MWh-display shows<br />

Pulsperioder<br />

3 digits<br />

från 40 till<br />

after<br />

1560 ms kan<br />

comma,<br />

förekomma<br />

the value is 1 kWh/pulse<br />

volympulsutgång med intern 5 V<br />

28 5,3 k<br />

försörjning


af forbindelsesledning mellem flowelektronik og displayenhed<br />

ation skal der være slukket for netspændingen til såvel flowelektronikken som displayenheden.<br />

egel er <strong>HGP</strong>-<strong>SIV</strong> Connection måleren of leveret connecting som en cable komplet between enhed, flow<br />

modulet <strong>HGP</strong>-HF-SD-conv. electronics and display monteret unit i <strong>HGP</strong> flowmåleren.<br />

konverterer hurtigpuls signalet fra flowmåleren til et hurtigder<br />

kan anvendes Before installation, af displayenhed. the mains voltage to the flow<br />

electronics as well as to the display unit must be<br />

odulet leveret turned som off. løst tilbehør (se fig 3) gøres følgende:<br />

t monteres<br />

Usually<br />

på stikket<br />

the<br />

i måleren,<br />

<strong>HGP</strong> <strong>SIV</strong><br />

se<br />

<strong>meter</strong><br />

tegning.<br />

is delivered<br />

Sørg for,<br />

as<br />

at alle<br />

a complete<br />

unit with the insertion module <strong>HGP</strong>-HF-SD-<br />

ads i stikket. Den nye skillebøjle monteres i kassen i stedet<br />

terende, og det 2-polede stik monteres på M12 i måleren.<br />

conv. already installed in the <strong>HGP</strong> flow <strong>meter</strong>. The<br />

insertion module transforms the fast pulse signal<br />

from the flow <strong>meter</strong> into a fast pulse signal usable<br />

for the display unit.<br />

Fig. <br />

3 Insertion module with<br />

division clamp<br />

In case the insertion module comes as a separate item (as fig. 3) the following guidelines<br />

must be observed: The insertion module is mounted on the connector in<br />

the <strong>meter</strong>, see drawing fig 4. Pay attention when mounting the insertion module<br />

and make sure that all pins are placed correctly in the connector. The enclosed<br />

division clamp is installed instead of the existing one and finally the 2-poled connector<br />

is mounted onto the pins M12 in the <strong>meter</strong>.<br />

<strong>HGP</strong> electronics<br />

n mellem <strong>HGP</strong> flowelektronik og displayenhed sker ved anvendelse af det medfølgende 4-leder<br />

M57 USB<br />

rbindes i flowelektronikkens terminaler A1, A2, B1 og B2 som vist i fig 4. Det hvide stik monteres<br />

i displayenheden, og ledning og gummimembran trykkes på plads i aflastningen.<br />

M57<br />

1<br />

<br />

<br />

inaler Ledningsfarve, tegning Ledningsfarve M57-stik (<strong>HGP</strong>-<strong>SIV</strong>) Signal<br />

Rød<br />

<strong>HGP</strong> HP-SD Conv.<br />

Rød 5 +5V<br />

Sort Sort 1 GND<br />

Gul<br />

1<br />

M12<br />

Gul 4 Data<br />

Grøn Grøn 2 Clock<br />

A1 A2<br />

B1 B2<br />

ing af måleren<br />

g tilsluttes til begge enheder, og måleren vil straks begynde at registrere, hvis der er vandflow.<br />

er ikke skade, såfremt der ikke er vand på anlægget, men kan, hvis flowsensoren M57 ikke er helt<br />

<strong>HGP</strong> HP-SD Conv.<br />

gistrere et tilfældigt flow.<br />

1 Black<br />

Green<br />

odulet er der i øverste højre hjørne to lysdioder til indikation af signal. Grøn diode indikerer mod-<br />

Yellow<br />

1<br />

Red<br />

Red<br />

M12<br />

nal fra <strong>HGP</strong>, og når der er flow, blinker dioden. Hvis den ikke blinker, kan det skyldes manglen-<br />

Black<br />

at stikket er faldet af eller er vendt forkert.<br />

Yellow<br />

Green<br />

A1 A2<br />

B1 B2<br />

dikerer at der sendes data til Beregningsenheden. Den blinker for hvert 1,6 sekund, og hvis den<br />

undersøges det om stikket på M57 er korrekt monteret, samt forbindelserne A1, A2, B1, B2 er i<br />

ema og skitser.<br />

<br />

er tilsluttet, og der løber vand gennem flowsensoren blinker en firkant i display i takt med vand-


Connection between the <strong>HGP</strong> flow electronics and the display unit takes place using<br />

the enclosed 4-poled cable which is connected in the terminals A1, A2, B1 and B2 of<br />

the flow electronics as shown on the drawing. The white connector is mounted on connector<br />

M57 of the display unit and the cable and rubber membrane are pressed to fit<br />

at the strain relief.<br />

<strong>HGP</strong><br />

terminals<br />

Wire colour<br />

M57 pin no.<br />

(<strong>HGP</strong>-<strong>SIV</strong>)<br />

Signal<br />

A1 Red 5 +5V<br />

A2 Black 1 GND<br />

B1 Yellow 4 Data<br />

B2 Green 2 Clock<br />

Putting the <strong>meter</strong> into operation<br />

Mains voltage is connected to both units and the <strong>meter</strong>s starts registration at once. The<br />

<strong>meter</strong> does not sustain damage if there is no water in the system, but it may register a<br />

random flow in case the flow sensor is not completely filled with water.<br />

In the upper right corner of the PCB are two lightemitting diodes (LEDs) for indication<br />

of signals. The green LED indicates received flow signal from <strong>HGP</strong> an when you have<br />

flow the LED flashes. If it does not flash it could be due to lack of flow, the connector<br />

has fallen out or has been reversed.<br />

The red LED indicates that data is being sent to the calculation unit. It flashes every 1.6<br />

seconds and if it does not flash it is advised to check if the connector M57 is installed<br />

correctly and that the connections A1, A2, B1 and B2 are working correctly. See table<br />

and drawings.<br />

When the <strong>meter</strong> is connected and water is running through the flow sensor a square in<br />

the display is flashing concurrently with the water pulses.<br />

Attention: The <strong>meter</strong>’s counter cannot be zeroed after delivery.


Specification of Output Pulses:<br />

Pulse output for volume and energy<br />

The open collector pulse out is power supplied with load resistance R, whic<br />

The open collector pulse out is power supplied with load resistance R, which is dimensioned<br />

according to table<br />

table below.<br />

below.<br />

Setting of external <br />

voltage supply <br />

(from <strong>meter</strong>: 5 VDC) <br />

+ V −1.5V<br />

R =<br />

5mA<br />

+V R for I=5 mA <br />

5 700 Ω Ω<br />

<br />

10 1,7 k Ω Ω <br />

15 2,7 k Ω Ω <br />

<br />

20 3,7 k Ω Ω<br />

Ω<br />

24 4,5 k Ω<br />

lied with load resistance R, which is dimensioned Ω according to<br />

28 5,3 k Ω<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

5V<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Insertion og communication module<br />

A communication module RS262, M-Bus or LON is plugged into the display<br />

nected to the terminals A1+B1 and A2+B2, [5] and [6] in fig 2.<br />

+<br />

Connection of external <strong>meter</strong>s with pulse outlet<br />

NB only valid for <strong>meter</strong>s, which has been programmed for connection<br />

The <strong>meter</strong> accepts active as well as passive signal source. The most comm<br />

<br />

which are connected to the terminals AUX 1 or AUX 2 and the switch in pos<br />

Fig. 5 Example of connection for volume pulse output with internal 5V<br />

fig. 6. <br />

<br />

Insertion og<br />

Connection<br />

communication<br />

of <strong>meter</strong>s<br />

module<br />

with active signal source is done as illustrated in pictu<br />

position OFF.<br />

A communication module RS262, M-Bus or LON is plugged into the display unit, and<br />

the signal cable Each is connected of the 2 input to the AUX1 terminals and A1+B1 AUX2 and can A2+B2, be set [5] separately. and [6] in fig Please 2 note th<br />

r LON is plugged into the display unit, and the signal cable is con-<br />

, [5] and [6] in fig 2.<br />

<br />

Connection of external <strong>meter</strong>s with pulse outlet<br />

(only valid for <strong>meter</strong>s, which has been programmed for connection of external <strong>meter</strong>s)<br />

<br />

pulse outlet<br />

n programmed for connection of external <strong>meter</strong>s.<br />

e signal source. position ON The as most shown common in picture B, is fig. passive 6. signal source,<br />

1 or AUX 2 and the switch in position ON as shown in picture B,<br />

The <strong>meter</strong> accepts active as well as passive signal source. The most common is passive<br />

signal source, which are connected to the terminals AUX 1 or AUX 2 and the switch in<br />

Connection of <strong>meter</strong>s with active signal source is done as illustrated in picture B, fig. 6<br />

with the switch in position OFF.<br />

Each of the 2 input AUX1 and AUX2 can be set separately. Please note the polarity,<br />

urce is done see fig. as 6. illustrated in picture B, fig. 6 with the switch in<br />

e set separately. Please note the polarity, see fig. 6.


Connection of <strong>meter</strong>s with active signal source is done as illustrated in picture B, fig. 6 with the switch in<br />

position OFF.<br />

Each of the 2 input AUX1 and AUX2 can be set separately. Please note the polarity, see fig. 6.<br />

<br />

+V on<br />

<br />

+ -<br />

<br />

AUX1 (Flödesmätare) AUX2<br />

Minus<br />

<br />

AUX1 (Flödesmätare) AUX2<br />

A. Aktiv signalkälla B. Passiv signalkälla<br />

<br />

Kontakter 1 & 2: OFF<br />

Kontakter 1 & 2: ON<br />

Galvaniskt A. Active åtskilt signal source B. Ej Passive galvaniskt signal åtskilt source<br />

Switch 1 & 2: OFF<br />

Switch 1 & 2: ON<br />

Galvanic separated NOT galvanic separated<br />

<br />

V off t on t off<br />

GND (0V)<br />

<br />

<br />

<br />

Input-specifikation<br />

<br />

Von<br />

V<br />

>2,5 V<br />

on<br />

>2,5 V<br />

Voff 50 ms<br />

Fig. 3 Anslutning av externa mätare<br />

<br />

<br />

Sealing<br />

Vesterlundvej 14 DK-2730 Herlev Denmark Tel:+45 7777 7000 Fax: +45 7777 7001<br />

E-mail: brunata@brunata.com Internet: www.brunata.com<br />

<br />

Fig. 6 Connection of external <strong>meter</strong>s<br />

The flow electronic unit is from the factory sealed through the transparent lid and<br />

the screw allowing access to the terminals. After mounting and connecting the unit the<br />

black lid is screwed on and the unit can be sealed using sealing wire and a seal.<br />

The display unit is sealed electronically when delivered. The box is closed and sealed<br />

with <strong>Brunata</strong> special seal made of plastic, which is pushed into the narrow hole on the<br />

bottom of the box. The seal can be removed with a screwdriver. The broken piece of<br />

the seal is to be pushed into the box with the screwdriver and hereafter the box can be<br />

opened. Alternatively the box can be closed with the enclosed screw and sealed with<br />

thread through the hole next to the screw for the lid.<br />

The temperature sensors are sealed in their pockets using sealing wire and a seal.<br />

Head sensors are sealed through the hole in the locking screw.<br />

energi-IV-BV-DK4/08.05.2006 Copyright © <strong>Brunata</strong> a/s 2006 Sida 4<br />

<strong>Brunata</strong> a/s • Kapplöpningsg. 14 • Box 5066 • S-250 05 Helsingborg • Sverige • Tel:+46 (0)42-13 37 59<br />

Fax: +46 (0)42-18 74 65 • E-mail: brunata@brunata.se • Internet: www.brunata.se<br />

<br />

10


PERATING MANUAL<br />

Operating manual<br />

he menu of the <strong>meter</strong> is structured in 3-4 menus, and you navigate from one display to another using the<br />

ush button on The the menu display of unit. the <strong>meter</strong> The following is structured illustration in 3-4 shows menus, the standard you menu navigate structure from one a <strong>Brunata</strong> display<br />

G energy <strong>meter</strong> to another using the push button on the display unit. The following illustration shows<br />

the standard menu structure on a <strong>Brunata</strong> HG energy <strong>meter</strong><br />

<br />

3)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

2)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

2)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

1)<br />

1)<br />

<br />

<br />

<br />

<br />

Operating<br />

hours h<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

1)<br />

1)<br />

4)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

2)<br />

2)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

2)<br />

4)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

HG-serial<br />

number<br />

<br />

<br />

<br />

<br />

Remarks<br />

emarks<br />

1) Only 1) in <strong>meter</strong> Only in programmed <strong>meter</strong> programmed for pulse input for pulse from external input from <strong>meter</strong>s external <strong>meter</strong>s<br />

2) Only 2) in <strong>meter</strong> Only in type <strong>meter</strong> -188 type programmed -188 programmed with tariff functions with tariff functions<br />

3) File menu 3) File is menu included is included only if <strong>meter</strong> only is if programmed <strong>meter</strong> is programmed for storage of for data storage of data<br />

4) Only 4) in <strong>meter</strong> Only in programmed <strong>meter</strong> programmed for remote for reading remote reading<br />

11


Operating the <strong>meter</strong><br />

Introduction<br />

The <strong>meter</strong> is operated using the push button on the<br />

front of the electronic unit. Pressing once you step<br />

down in the actual menu you are in. By pressing<br />

the button in a few seconds, you can step from one<br />

menu to the next.<br />

Except for the User Menu the No. of the actual<br />

menu is shown in the display.<br />

Push<br />

button<br />

In case the <strong>meter</strong> is delivered with Storage Menu, the <strong>meter</strong> read itself and stores data<br />

as default on the 1st each month or at an optional selected date, see the order confirmation<br />

or consult the Service Menu. Until the first date occur the menu will be empty,<br />

displaying _ _._ _._ _._ _<br />

Peak values are registered in the period from the 1st in actual month. Values are reset<br />

(zeroed) at each turn of the storing date e.g. for standard <strong>meter</strong>s each month.<br />

In addition to registration of the highest return temperature (Peak t L<br />

) the concurrent<br />

flow temperature (Peak t H<br />

) is registered.<br />

With <strong>meter</strong>s supplied with module for remote reading, the user himself in the User<br />

Menu can check the time where the <strong>meter</strong> has been read. The communication address<br />

of the <strong>meter</strong> appears in the Service Menu.<br />

Normal operation – User menu<br />

By pushing the button once there will be light in the display, and you will see the accumulated<br />

energy (MWh). When pushing once again the display will change to different<br />

pictures (see above). After the last display picture in the menu the display will show the<br />

accumulated energy (MWh) again.<br />

When the pushbutton has not been activated for approx. 1 minute the display will automatically<br />

return to accumulated volume (MWh) and the light will turn off.<br />

Advanced operation – all menus<br />

When holding down the button for a short while, the display will change from one<br />

menu to the next. The menu reached is indicated in the upper part of the display (except<br />

Menu 1). The order of the menus is therefore [none], 2, 3, 4.<br />

When you reach the needed menu, release the pushbutton and the menu is now activated.<br />

By pushing once the different display pictures in the chosen menu will show (as<br />

mentioned above).<br />

Display pictures containing peak values - f.inst. peak flow, peak power etc., will automatically<br />

alternate between peak value and date/time of registration.<br />

12


For <strong>meter</strong>s delivered with tariff function the consumption is displayed in Tariff <strong>Energy</strong><br />

$ and Tariff volume $, according to the criteria’s selected. The selected criteria can be<br />

seen in the service menu.<br />

Stored data menu<br />

If the <strong>meter</strong> is programmed for storage of data, in menu 3 you find data stored for 24<br />

accounting periods, and you can step through the different periods by pressing the button<br />

quickly twice. The date and time when the data has been stored is shown as first<br />

display in each accounting period. The first period showed are the most recent. You<br />

can step through the information stored by pressing the button once. By pressing the<br />

button quickly twice you step to the next period, and after having reached the latest<br />

reading (register 24) you will again see the most recent readings.<br />

Information and error codes<br />

Should an error occur in the <strong>meter</strong>, the display will be flashing ”Error” followed by one<br />

of following error codes:<br />

1. Interruption of power supply. The information is logged in the error register, and not<br />

showed in the display.<br />

2. No registration of flow pulses within the last 24 hours, provided that the temperature<br />

difference has exceeded 20 °C.<br />

3. Error, temperature sensor T H<br />

, warmest pipe [-30 °C > T H<br />

> 200 °C].<br />

4. Error, temperature sensor T L<br />

, coldest pipe [-30 °C > T L<br />

> 200 °C].<br />

5. Low voltage in back-up battery [V Bat<br />

< V Treshold<br />

].<br />

6. Short circuit of magnet coil in the flowsensor [Coil current exceeds limit value for<br />

more than 8 sec].<br />

7. Error in the programming of the <strong>meter</strong> [RAM not initialised].<br />

8. The temperature sensors in flow pipe and return pipe are reversed [Negative temperature<br />

difference exceeds limit value for more than 10 sec].<br />

9. Wrong time/date in the <strong>meter</strong> (see Service Menu) – clock must be adjusted.<br />

In case of error the <strong>meter</strong> automatically will registers when (date and time) the error has<br />

occurred and also the accumulated error time.<br />

When two errors occur at the same time, both codes are shown. Example: Error code<br />

36 indicates problems with the temperature sensor in the warmest pipe and with the<br />

flow sensor.<br />

At code nos. 2, 3, 4, 6 and 8 the error message is shown in the display as long as the<br />

error occurs. The hours with error are registered in the register for Accumulated error<br />

13


hours. If the power supply is terminated, the time without power is registered in the<br />

error hours register.<br />

At code 5, 7 and 9 the error message is shown in the display as long as the error occurs,<br />

but will not be registered in the register for Accumulated error hours.<br />

By interruption of the power supply the display will be blank. When the power is reestablished<br />

the <strong>meter</strong> will immediately start registering again.<br />

By error code 5, low battery-supply, the <strong>meter</strong> will continue the normal registration as<br />

long as it is powered but the battery must be replaced as soon as possible.<br />

By error code 9, the <strong>meter</strong> has been without power supply, and battery-supply. The<br />

<strong>meter</strong> will continue the normal registration when power is restored, but the internal<br />

clock should be adjusted.<br />

At temperature difference below 0.1 K, the energy calculation will seize. The register<br />

“Accumulated flow sensor volume” will continue registering the flow.<br />

The <strong>meter</strong>’s operating hours counter starts registration as soon as the <strong>meter</strong> is connected<br />

to the mains.<br />

In case of questions, you are always welcome to contact your local <strong>Brunata</strong> service<br />

department, or send an e-mail to service@brunata.dk.<br />

14


Notes<br />

15


Notes<br />

<strong>Brunata</strong> a/s · Vesterlundvej 14 · DK-2730 Herlev · tel. +45 77 77 70 00<br />

fax +45 77 77 70 01 · www.brunata.com · brunata@brunata.com<br />

UK-QB 10.1486/04.09.2006<br />

16

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!