HGP-SIV Energy meter - Brunata
HGP-SIV Energy meter - Brunata HGP-SIV Energy meter - Brunata
HGP-SIV Energy meter Installation and users manual
- Page 2 and 3: Please read this before installatio
- Page 4 and 5: Fitting and connection of display u
- Page 6 and 7: Ledningsförbindelser och anslutnin
- Page 8 and 9: Connection between the HGP flow ele
- Page 10 and 11: Connection of meters with active si
- Page 12 and 13: Operating the meter Introduction Th
- Page 14 and 15: hours. If the power supply is termi
- Page 16: Notes Brunata a/s · Vesterlundvej
<strong>HGP</strong>-<strong>SIV</strong> <strong>Energy</strong> <strong>meter</strong><br />
Installation and users manual
Please read this before installation<br />
This manual is intended for skilled personal having a formal knowledge to <strong>meter</strong>s.<br />
The <strong>Brunata</strong> <strong>HGP</strong>-<strong>SIV</strong> energy <strong>meter</strong> must only be used and installed as described in the<br />
manual.<br />
The working data of the <strong>meter</strong> are shown on the label of the <strong>meter</strong>. For further information<br />
we refer to the data sheet.<br />
IMPORTANT: Seals and void labels must not be removed or damaged. This will infringe<br />
the warranty of the <strong>meter</strong>.<br />
The <strong>meter</strong> contains of following parts:<br />
1. Flow sensor<br />
2. Flow electronic unit<br />
3. Display unit<br />
4. Signal cable between flow electronics and display unit<br />
5. Two paired temperature sensors with sensor pockets<br />
6. Installation and users manual<br />
When unpacking the <strong>meter</strong>, please check that all parts are enclosed. The serial numbers<br />
of the flow sensor, the electronic units, and the temperature sensors must be identical,<br />
since the parts are calibrated. The serial number is also programmed into the memory<br />
of the <strong>meter</strong>, the Service Menu.<br />
Versions and ordering code<br />
x: Flow of the <strong>meter</strong><br />
(q p<br />
)in m 3 /h<br />
yy: Connectionsize:<br />
-39: G2B x 300 mm<br />
-40: DN40 x 300 mm<br />
-50: DN50 x 270 mm<br />
-65: DN65 x 300 mm<br />
-80: DN80 x 300 mm<br />
-100: DN100 x 360 mm<br />
-125: DN125 x 360 mm<br />
-150: DN150 x 500 mm<br />
z: Menu/display:<br />
184: Standard version<br />
with peak values<br />
185: Heat- / cooling <strong>meter</strong><br />
188: Tariff <strong>meter</strong><br />
<strong>HGP</strong>-<strong>SIV</strong>x-yy-18z/ABCDEF<br />
A: Power supply:<br />
1: 230 VAC<br />
2: 24 VAC<br />
B: Display backlight:<br />
B: with /-: without<br />
C: External <strong>meter</strong>s:<br />
0, 1 or 2<br />
D: Kommunikationsmodul:<br />
M-Bus / LonWorks / RS232<br />
/ - none<br />
E: No. of accounting periods:<br />
0 / 6 / 12 / 24<br />
F: Programmed for Glycol<br />
(% in service menu)
Installation<br />
Preparation for installation<br />
Please note that the installation must be done in such a way that it meets the requirements<br />
for internal fitting, distances that have to be respected, etc. Straight pipe sections<br />
before or after the <strong>meter</strong> are not required.<br />
It is recommended that stop valves are fitted before and after the <strong>meter</strong> to<br />
make it easier to remove and reinstall the <strong>meter</strong> if service and verification are<br />
required. To ensure that there are no foreign bodies in the pipe section, it is recommended<br />
that the pipes are flushed through before the <strong>meter</strong> is installed. A<br />
adapter pipe can be used for this purpose. After installation, the valves should<br />
be opened in the order which provides correct flow through the <strong>meter</strong>.<br />
The HG-<strong>meter</strong> has been approved for installation in industrial areas, but it is recommended<br />
that installation close to components that may cause strong electromagnetic<br />
interference is avoided.<br />
Installation of the flow sensor<br />
The flowsensor is installed with the arrow in the flow direction. The flow sensor can<br />
be installed in any direction (vertically, horizontally etc), only the flow sensor must always<br />
be filled with water when running. Do not insulate the housing of the flow sensor.<br />
The <strong>meter</strong>’s type label will indicate whether the flow sensor should be fitted on the return<br />
pipe (low temperature) or the supply pipe (high temperature). Please note that if the <strong>meter</strong><br />
is used in a cooling system, the supply pipe is low temperature.<br />
Fitting and connection of flow electronic unit, fig. 1<br />
Place the flow electronic unit on an even surface with 3 screws. All connections to the<br />
<strong>meter</strong> must be fitted before mains voltage is connected.<br />
The connection cable from the Flow Sensor is inserted into the socket marked Flow<br />
Head [8] in fig. 1. Note the locking system and how the cable exits the box. To dismantle<br />
the plug, use a small screwdriver to lift the lock. Never shorten nor lengthen the cables<br />
for the flowsensor. If the cable must be rolled up, the dia<strong>meter</strong> of the roll should<br />
at least be 30 cm.<br />
The power supply cable (230 or 24 V) is inserted through the strain relief, which must<br />
be tightened before tightening the terminal connections [1] in fig. 1.<br />
Signal cable to display unit are installed in terminals A1, A2, B1 and B2, [11] in fig. 1.
Fitting and connection of display unit, fig 2<br />
Place the display unit on an even surface with 3 screws. All connections to the <strong>meter</strong><br />
must be fitted before mains voltage is connected.<br />
The connecting cable from flow electronic unit is connected to plug M57, see fig 4.<br />
The other cables that need to be connected are led through rubber membrane and<br />
bypass and connected with their respective terminals. Temperature sensors are connected<br />
with terminal [2] and [3], pulse inputs with terminal [9] and [10], and the remote<br />
reading with terminal [5] and [6]. A small screwdriver or the like can be used to perforate<br />
the rubber membrane.<br />
The power supply cable for 230 Volt (possibly 24 Volt) is led through the rubber<br />
membrane and connected with terminal [4] in fig.1, then the strain relief is tightened<br />
moderately. Earth connection is not required.
NINGSKLEMMER<br />
Connecting terminals<br />
Flow electronic unit<br />
24 V AC)<br />
ængde<br />
abel<br />
isplayenhed *<br />
ndstikskort *<br />
Fig. 1 Connecting <br />
terminals <strong>HGP</strong> flow electronics<br />
<br />
No. Indication Connection <br />
1 230 VAC Power (24VAC is possible)<br />
2 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />
3 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />
4 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />
5 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />
13<br />
4 5 6 7 8<br />
på <strong>HGP</strong>-<strong>SIV</strong><br />
varme rør (rød)<br />
kolde rør (blå)<br />
an være 24VAC)<br />
r datakommunikation, M-Bus, Lon eller RS232<br />
r datakommunikation, M-Bus, Lon eller RS232<br />
pulsudgang, volumen<br />
12<br />
11<br />
10<br />
6 - VOL. + Pulse out, water volume<br />
7 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />
8 FLOWHEAD Plug for flow sensor cable<br />
9 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />
10 Not in use on <strong>HGP</strong>-<strong>SIV</strong><br />
11 A1, A2, B1, B2 Cable connection to Display unit*<br />
12 HF-udgang Connection to insertion module*<br />
* see next page<br />
9<br />
<br />
<br />
forsyning<br />
<br />
<br />
erafhængigaf<br />
måleresstørrelse.<br />
Fremgåraftypeskiltet.<br />
<br />
harsamme
Ledningsförbindelser och anslutningsklämmer<br />
Displayenhet Display unit<br />
1<br />
13<br />
12<br />
11<br />
10<br />
9<br />
2 3 4<br />
5 6 7 8<br />
NR. MÄRKNING ANSLUTNING Fig. 2 Connecting terminals <strong>HGP</strong>-<strong>SIV</strong> Display Unit<br />
1 FLÖDESSENSOR .. 4-polig, skärmad stickkontakt till flödessensorkabel<br />
PULSVÄRDEN:<br />
2 HIGH Nr. TEMP. Indication ........... Temperatursensor, Installation varma rör (röd)<br />
3 LOW TEMP............. Temperatursensor, kalla rör (blå)<br />
Mätarens volymp<br />
4 230 VAC.................. 1 FLOWSENSOR Strömspänning Not (Kan in use vara on 24 <strong>HGP</strong>-<strong>SIV</strong> VAC)<br />
är beroende av<br />
5 A1 B1. ................... 1. Anslutning av datakommunikation, M-Bus, Lon eller RS232 mätarens storlek.<br />
2 HIGH TEMP. Temp. sensor, high<br />
6 A2 B2. ................... 2. Anslutning av datakommunikation, M-Bus, Lon eller RS232 Framgår av<br />
7 - VOL. 3+................... LOW TEMP. Öppen kollektor Temp. pulsutgång, sensor, low volym<br />
typmärket.<br />
8 - ENERGI +. ............ Öppen kollektor pulsutgång, energi<br />
4 230 V AC. Power (24VAC is possible)<br />
Energipuls har<br />
9 - AUX2 +. ................ Extern pulsingång från t ex elmätare<br />
samma värde som<br />
10 - AUX1 5+. ................ A1 B1. Extern pulsingång 1 st Installation från t ex of kallvattenmätare<br />
datacommunication, MBus, Lon or RS232 sista siffran i<br />
11 Kontakter 1 & 2 ....... Kontakter för tillkoppling av intern +5 V till AUX- ingångarna<br />
displayen.<br />
12 0 V +5<br />
6<br />
V. ................<br />
A2 B2.<br />
Genemsam<br />
2<br />
noll nd Installation<br />
och +5 V DC<br />
of datacommunication,<br />
utgång<br />
MBus, Lon or RS232<br />
Har t ex MWh-display<br />
13 M52. ........................ 7 - VOL. +. Stickkontakt Open för datakommunikationskort, collector pulse out, volume M-Bus, Lon eller RS232<br />
siffror efter kommat, ä<br />
8 - ENERGI +. Open collector pulse out, energy<br />
9 - AUX2 +. External incoming pulse from f.inst. electricity <strong>meter</strong><br />
Pulsutgångar för volym och energi<br />
Pulsutgångens 10 optokopplare - AUX1 +. strömförsörjs External via belastningsmotstånd incoming pulse from R, f.inst. som dimensioneras cold water <strong>meter</strong> enl. tabell<br />
11 Switches 1 & 2 Switches for connection of internal +5V to AUX terminals<br />
Inställning 12 av 0 extern V +5 V. +Vmax<br />
<br />
Common<br />
V 1.5V<br />
zero and 28 V +5V DC exit<br />
Motstånd R<br />
strömförsörjning<br />
R <br />
Imax 20 mA<br />
13 M52. Connector 5mA<br />
for data<br />
(från mätare: 5 VDC)<br />
Von max 1,5 V communication module, MBus, Lon<br />
or RS232<br />
+V R för I=5 mA<br />
ton=toff=140 ms är standardinställning<br />
Values of pulse<br />
Pulsperiod T= ton + toff = 280 ms.<br />
5 700 <br />
+<br />
+Voff<br />
10 Volume 1,7 pulse k HGG-<strong>SIV</strong>-<strong>meter</strong> pulse value depends on size of the <strong>meter</strong>. Please consult<br />
15 the type 2,7 sign. k<br />
20 <strong>Energy</strong> 3,7 pulse k has the same Von value as toff the ton last digit in display.<br />
24<br />
GND (0V)<br />
4,5 k<br />
Fig. 2 Anslutningsexempel för<br />
F.inst. MWh-display shows<br />
Pulsperioder<br />
3 digits<br />
från 40 till<br />
after<br />
1560 ms kan<br />
comma,<br />
förekomma<br />
the value is 1 kWh/pulse<br />
volympulsutgång med intern 5 V<br />
28 5,3 k<br />
försörjning
af forbindelsesledning mellem flowelektronik og displayenhed<br />
ation skal der være slukket for netspændingen til såvel flowelektronikken som displayenheden.<br />
egel er <strong>HGP</strong>-<strong>SIV</strong> Connection måleren of leveret connecting som en cable komplet between enhed, flow<br />
modulet <strong>HGP</strong>-HF-SD-conv. electronics and display monteret unit i <strong>HGP</strong> flowmåleren.<br />
konverterer hurtigpuls signalet fra flowmåleren til et hurtigder<br />
kan anvendes Before installation, af displayenhed. the mains voltage to the flow<br />
electronics as well as to the display unit must be<br />
odulet leveret turned som off. løst tilbehør (se fig 3) gøres følgende:<br />
t monteres<br />
Usually<br />
på stikket<br />
the<br />
i måleren,<br />
<strong>HGP</strong> <strong>SIV</strong><br />
se<br />
<strong>meter</strong><br />
tegning.<br />
is delivered<br />
Sørg for,<br />
as<br />
at alle<br />
a complete<br />
unit with the insertion module <strong>HGP</strong>-HF-SD-<br />
ads i stikket. Den nye skillebøjle monteres i kassen i stedet<br />
terende, og det 2-polede stik monteres på M12 i måleren.<br />
conv. already installed in the <strong>HGP</strong> flow <strong>meter</strong>. The<br />
insertion module transforms the fast pulse signal<br />
from the flow <strong>meter</strong> into a fast pulse signal usable<br />
for the display unit.<br />
Fig. <br />
3 Insertion module with<br />
division clamp<br />
In case the insertion module comes as a separate item (as fig. 3) the following guidelines<br />
must be observed: The insertion module is mounted on the connector in<br />
the <strong>meter</strong>, see drawing fig 4. Pay attention when mounting the insertion module<br />
and make sure that all pins are placed correctly in the connector. The enclosed<br />
division clamp is installed instead of the existing one and finally the 2-poled connector<br />
is mounted onto the pins M12 in the <strong>meter</strong>.<br />
<strong>HGP</strong> electronics<br />
n mellem <strong>HGP</strong> flowelektronik og displayenhed sker ved anvendelse af det medfølgende 4-leder<br />
M57 USB<br />
rbindes i flowelektronikkens terminaler A1, A2, B1 og B2 som vist i fig 4. Det hvide stik monteres<br />
i displayenheden, og ledning og gummimembran trykkes på plads i aflastningen.<br />
M57<br />
1<br />
<br />
<br />
inaler Ledningsfarve, tegning Ledningsfarve M57-stik (<strong>HGP</strong>-<strong>SIV</strong>) Signal<br />
Rød<br />
<strong>HGP</strong> HP-SD Conv.<br />
Rød 5 +5V<br />
Sort Sort 1 GND<br />
Gul<br />
1<br />
M12<br />
Gul 4 Data<br />
Grøn Grøn 2 Clock<br />
A1 A2<br />
B1 B2<br />
ing af måleren<br />
g tilsluttes til begge enheder, og måleren vil straks begynde at registrere, hvis der er vandflow.<br />
er ikke skade, såfremt der ikke er vand på anlægget, men kan, hvis flowsensoren M57 ikke er helt<br />
<strong>HGP</strong> HP-SD Conv.<br />
gistrere et tilfældigt flow.<br />
1 Black<br />
Green<br />
odulet er der i øverste højre hjørne to lysdioder til indikation af signal. Grøn diode indikerer mod-<br />
Yellow<br />
1<br />
Red<br />
Red<br />
M12<br />
nal fra <strong>HGP</strong>, og når der er flow, blinker dioden. Hvis den ikke blinker, kan det skyldes manglen-<br />
Black<br />
at stikket er faldet af eller er vendt forkert.<br />
Yellow<br />
Green<br />
A1 A2<br />
B1 B2<br />
dikerer at der sendes data til Beregningsenheden. Den blinker for hvert 1,6 sekund, og hvis den<br />
undersøges det om stikket på M57 er korrekt monteret, samt forbindelserne A1, A2, B1, B2 er i<br />
ema og skitser.<br />
<br />
er tilsluttet, og der løber vand gennem flowsensoren blinker en firkant i display i takt med vand-
Connection between the <strong>HGP</strong> flow electronics and the display unit takes place using<br />
the enclosed 4-poled cable which is connected in the terminals A1, A2, B1 and B2 of<br />
the flow electronics as shown on the drawing. The white connector is mounted on connector<br />
M57 of the display unit and the cable and rubber membrane are pressed to fit<br />
at the strain relief.<br />
<strong>HGP</strong><br />
terminals<br />
Wire colour<br />
M57 pin no.<br />
(<strong>HGP</strong>-<strong>SIV</strong>)<br />
Signal<br />
A1 Red 5 +5V<br />
A2 Black 1 GND<br />
B1 Yellow 4 Data<br />
B2 Green 2 Clock<br />
Putting the <strong>meter</strong> into operation<br />
Mains voltage is connected to both units and the <strong>meter</strong>s starts registration at once. The<br />
<strong>meter</strong> does not sustain damage if there is no water in the system, but it may register a<br />
random flow in case the flow sensor is not completely filled with water.<br />
In the upper right corner of the PCB are two lightemitting diodes (LEDs) for indication<br />
of signals. The green LED indicates received flow signal from <strong>HGP</strong> an when you have<br />
flow the LED flashes. If it does not flash it could be due to lack of flow, the connector<br />
has fallen out or has been reversed.<br />
The red LED indicates that data is being sent to the calculation unit. It flashes every 1.6<br />
seconds and if it does not flash it is advised to check if the connector M57 is installed<br />
correctly and that the connections A1, A2, B1 and B2 are working correctly. See table<br />
and drawings.<br />
When the <strong>meter</strong> is connected and water is running through the flow sensor a square in<br />
the display is flashing concurrently with the water pulses.<br />
Attention: The <strong>meter</strong>’s counter cannot be zeroed after delivery.
Specification of Output Pulses:<br />
Pulse output for volume and energy<br />
The open collector pulse out is power supplied with load resistance R, whic<br />
The open collector pulse out is power supplied with load resistance R, which is dimensioned<br />
according to table<br />
table below.<br />
below.<br />
Setting of external <br />
voltage supply <br />
(from <strong>meter</strong>: 5 VDC) <br />
+ V −1.5V<br />
R =<br />
5mA<br />
+V R for I=5 mA <br />
5 700 Ω Ω<br />
<br />
10 1,7 k Ω Ω <br />
15 2,7 k Ω Ω <br />
<br />
20 3,7 k Ω Ω<br />
Ω<br />
24 4,5 k Ω<br />
lied with load resistance R, which is dimensioned Ω according to<br />
28 5,3 k Ω<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
5V<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
Insertion og communication module<br />
A communication module RS262, M-Bus or LON is plugged into the display<br />
nected to the terminals A1+B1 and A2+B2, [5] and [6] in fig 2.<br />
+<br />
Connection of external <strong>meter</strong>s with pulse outlet<br />
NB only valid for <strong>meter</strong>s, which has been programmed for connection<br />
The <strong>meter</strong> accepts active as well as passive signal source. The most comm<br />
<br />
which are connected to the terminals AUX 1 or AUX 2 and the switch in pos<br />
Fig. 5 Example of connection for volume pulse output with internal 5V<br />
fig. 6. <br />
<br />
Insertion og<br />
Connection<br />
communication<br />
of <strong>meter</strong>s<br />
module<br />
with active signal source is done as illustrated in pictu<br />
position OFF.<br />
A communication module RS262, M-Bus or LON is plugged into the display unit, and<br />
the signal cable Each is connected of the 2 input to the AUX1 terminals and A1+B1 AUX2 and can A2+B2, be set [5] separately. and [6] in fig Please 2 note th<br />
r LON is plugged into the display unit, and the signal cable is con-<br />
, [5] and [6] in fig 2.<br />
<br />
Connection of external <strong>meter</strong>s with pulse outlet<br />
(only valid for <strong>meter</strong>s, which has been programmed for connection of external <strong>meter</strong>s)<br />
<br />
pulse outlet<br />
n programmed for connection of external <strong>meter</strong>s.<br />
e signal source. position ON The as most shown common in picture B, is fig. passive 6. signal source,<br />
1 or AUX 2 and the switch in position ON as shown in picture B,<br />
The <strong>meter</strong> accepts active as well as passive signal source. The most common is passive<br />
signal source, which are connected to the terminals AUX 1 or AUX 2 and the switch in<br />
Connection of <strong>meter</strong>s with active signal source is done as illustrated in picture B, fig. 6<br />
with the switch in position OFF.<br />
Each of the 2 input AUX1 and AUX2 can be set separately. Please note the polarity,<br />
urce is done see fig. as 6. illustrated in picture B, fig. 6 with the switch in<br />
e set separately. Please note the polarity, see fig. 6.
Connection of <strong>meter</strong>s with active signal source is done as illustrated in picture B, fig. 6 with the switch in<br />
position OFF.<br />
Each of the 2 input AUX1 and AUX2 can be set separately. Please note the polarity, see fig. 6.<br />
<br />
+V on<br />
<br />
+ -<br />
<br />
AUX1 (Flödesmätare) AUX2<br />
Minus<br />
<br />
AUX1 (Flödesmätare) AUX2<br />
A. Aktiv signalkälla B. Passiv signalkälla<br />
<br />
Kontakter 1 & 2: OFF<br />
Kontakter 1 & 2: ON<br />
Galvaniskt A. Active åtskilt signal source B. Ej Passive galvaniskt signal åtskilt source<br />
Switch 1 & 2: OFF<br />
Switch 1 & 2: ON<br />
Galvanic separated NOT galvanic separated<br />
<br />
V off t on t off<br />
GND (0V)<br />
<br />
<br />
<br />
Input-specifikation<br />
<br />
Von<br />
V<br />
>2,5 V<br />
on<br />
>2,5 V<br />
Voff 50 ms<br />
Fig. 3 Anslutning av externa mätare<br />
<br />
<br />
Sealing<br />
Vesterlundvej 14 DK-2730 Herlev Denmark Tel:+45 7777 7000 Fax: +45 7777 7001<br />
E-mail: brunata@brunata.com Internet: www.brunata.com<br />
<br />
Fig. 6 Connection of external <strong>meter</strong>s<br />
The flow electronic unit is from the factory sealed through the transparent lid and<br />
the screw allowing access to the terminals. After mounting and connecting the unit the<br />
black lid is screwed on and the unit can be sealed using sealing wire and a seal.<br />
The display unit is sealed electronically when delivered. The box is closed and sealed<br />
with <strong>Brunata</strong> special seal made of plastic, which is pushed into the narrow hole on the<br />
bottom of the box. The seal can be removed with a screwdriver. The broken piece of<br />
the seal is to be pushed into the box with the screwdriver and hereafter the box can be<br />
opened. Alternatively the box can be closed with the enclosed screw and sealed with<br />
thread through the hole next to the screw for the lid.<br />
The temperature sensors are sealed in their pockets using sealing wire and a seal.<br />
Head sensors are sealed through the hole in the locking screw.<br />
energi-IV-BV-DK4/08.05.2006 Copyright © <strong>Brunata</strong> a/s 2006 Sida 4<br />
<strong>Brunata</strong> a/s • Kapplöpningsg. 14 • Box 5066 • S-250 05 Helsingborg • Sverige • Tel:+46 (0)42-13 37 59<br />
Fax: +46 (0)42-18 74 65 • E-mail: brunata@brunata.se • Internet: www.brunata.se<br />
<br />
10
PERATING MANUAL<br />
Operating manual<br />
he menu of the <strong>meter</strong> is structured in 3-4 menus, and you navigate from one display to another using the<br />
ush button on The the menu display of unit. the <strong>meter</strong> The following is structured illustration in 3-4 shows menus, the standard you menu navigate structure from one a <strong>Brunata</strong> display<br />
G energy <strong>meter</strong> to another using the push button on the display unit. The following illustration shows<br />
the standard menu structure on a <strong>Brunata</strong> HG energy <strong>meter</strong><br />
<br />
3)<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
2)<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
2)<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
1)<br />
1)<br />
<br />
<br />
<br />
<br />
Operating<br />
hours h<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
1)<br />
1)<br />
4)<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
2)<br />
2)<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
2)<br />
4)<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
HG-serial<br />
number<br />
<br />
<br />
<br />
<br />
Remarks<br />
emarks<br />
1) Only 1) in <strong>meter</strong> Only in programmed <strong>meter</strong> programmed for pulse input for pulse from external input from <strong>meter</strong>s external <strong>meter</strong>s<br />
2) Only 2) in <strong>meter</strong> Only in type <strong>meter</strong> -188 type programmed -188 programmed with tariff functions with tariff functions<br />
3) File menu 3) File is menu included is included only if <strong>meter</strong> only is if programmed <strong>meter</strong> is programmed for storage of for data storage of data<br />
4) Only 4) in <strong>meter</strong> Only in programmed <strong>meter</strong> programmed for remote for reading remote reading<br />
11
Operating the <strong>meter</strong><br />
Introduction<br />
The <strong>meter</strong> is operated using the push button on the<br />
front of the electronic unit. Pressing once you step<br />
down in the actual menu you are in. By pressing<br />
the button in a few seconds, you can step from one<br />
menu to the next.<br />
Except for the User Menu the No. of the actual<br />
menu is shown in the display.<br />
Push<br />
button<br />
In case the <strong>meter</strong> is delivered with Storage Menu, the <strong>meter</strong> read itself and stores data<br />
as default on the 1st each month or at an optional selected date, see the order confirmation<br />
or consult the Service Menu. Until the first date occur the menu will be empty,<br />
displaying _ _._ _._ _._ _<br />
Peak values are registered in the period from the 1st in actual month. Values are reset<br />
(zeroed) at each turn of the storing date e.g. for standard <strong>meter</strong>s each month.<br />
In addition to registration of the highest return temperature (Peak t L<br />
) the concurrent<br />
flow temperature (Peak t H<br />
) is registered.<br />
With <strong>meter</strong>s supplied with module for remote reading, the user himself in the User<br />
Menu can check the time where the <strong>meter</strong> has been read. The communication address<br />
of the <strong>meter</strong> appears in the Service Menu.<br />
Normal operation – User menu<br />
By pushing the button once there will be light in the display, and you will see the accumulated<br />
energy (MWh). When pushing once again the display will change to different<br />
pictures (see above). After the last display picture in the menu the display will show the<br />
accumulated energy (MWh) again.<br />
When the pushbutton has not been activated for approx. 1 minute the display will automatically<br />
return to accumulated volume (MWh) and the light will turn off.<br />
Advanced operation – all menus<br />
When holding down the button for a short while, the display will change from one<br />
menu to the next. The menu reached is indicated in the upper part of the display (except<br />
Menu 1). The order of the menus is therefore [none], 2, 3, 4.<br />
When you reach the needed menu, release the pushbutton and the menu is now activated.<br />
By pushing once the different display pictures in the chosen menu will show (as<br />
mentioned above).<br />
Display pictures containing peak values - f.inst. peak flow, peak power etc., will automatically<br />
alternate between peak value and date/time of registration.<br />
12
For <strong>meter</strong>s delivered with tariff function the consumption is displayed in Tariff <strong>Energy</strong><br />
$ and Tariff volume $, according to the criteria’s selected. The selected criteria can be<br />
seen in the service menu.<br />
Stored data menu<br />
If the <strong>meter</strong> is programmed for storage of data, in menu 3 you find data stored for 24<br />
accounting periods, and you can step through the different periods by pressing the button<br />
quickly twice. The date and time when the data has been stored is shown as first<br />
display in each accounting period. The first period showed are the most recent. You<br />
can step through the information stored by pressing the button once. By pressing the<br />
button quickly twice you step to the next period, and after having reached the latest<br />
reading (register 24) you will again see the most recent readings.<br />
Information and error codes<br />
Should an error occur in the <strong>meter</strong>, the display will be flashing ”Error” followed by one<br />
of following error codes:<br />
1. Interruption of power supply. The information is logged in the error register, and not<br />
showed in the display.<br />
2. No registration of flow pulses within the last 24 hours, provided that the temperature<br />
difference has exceeded 20 °C.<br />
3. Error, temperature sensor T H<br />
, warmest pipe [-30 °C > T H<br />
> 200 °C].<br />
4. Error, temperature sensor T L<br />
, coldest pipe [-30 °C > T L<br />
> 200 °C].<br />
5. Low voltage in back-up battery [V Bat<br />
< V Treshold<br />
].<br />
6. Short circuit of magnet coil in the flowsensor [Coil current exceeds limit value for<br />
more than 8 sec].<br />
7. Error in the programming of the <strong>meter</strong> [RAM not initialised].<br />
8. The temperature sensors in flow pipe and return pipe are reversed [Negative temperature<br />
difference exceeds limit value for more than 10 sec].<br />
9. Wrong time/date in the <strong>meter</strong> (see Service Menu) – clock must be adjusted.<br />
In case of error the <strong>meter</strong> automatically will registers when (date and time) the error has<br />
occurred and also the accumulated error time.<br />
When two errors occur at the same time, both codes are shown. Example: Error code<br />
36 indicates problems with the temperature sensor in the warmest pipe and with the<br />
flow sensor.<br />
At code nos. 2, 3, 4, 6 and 8 the error message is shown in the display as long as the<br />
error occurs. The hours with error are registered in the register for Accumulated error<br />
13
hours. If the power supply is terminated, the time without power is registered in the<br />
error hours register.<br />
At code 5, 7 and 9 the error message is shown in the display as long as the error occurs,<br />
but will not be registered in the register for Accumulated error hours.<br />
By interruption of the power supply the display will be blank. When the power is reestablished<br />
the <strong>meter</strong> will immediately start registering again.<br />
By error code 5, low battery-supply, the <strong>meter</strong> will continue the normal registration as<br />
long as it is powered but the battery must be replaced as soon as possible.<br />
By error code 9, the <strong>meter</strong> has been without power supply, and battery-supply. The<br />
<strong>meter</strong> will continue the normal registration when power is restored, but the internal<br />
clock should be adjusted.<br />
At temperature difference below 0.1 K, the energy calculation will seize. The register<br />
“Accumulated flow sensor volume” will continue registering the flow.<br />
The <strong>meter</strong>’s operating hours counter starts registration as soon as the <strong>meter</strong> is connected<br />
to the mains.<br />
In case of questions, you are always welcome to contact your local <strong>Brunata</strong> service<br />
department, or send an e-mail to service@brunata.dk.<br />
14
Notes<br />
15
Notes<br />
<strong>Brunata</strong> a/s · Vesterlundvej 14 · DK-2730 Herlev · tel. +45 77 77 70 00<br />
fax +45 77 77 70 01 · www.brunata.com · brunata@brunata.com<br />
UK-QB 10.1486/04.09.2006<br />
16