MODBUS UC220 Dynamic room controller V2 6 LSB reserved 6 MSB relay 7 LSB R, RAM output relay status (DO2) bit 0 ... reserved (relay 1: fast PWM fan control output) bit 1 ... relay 2, heating bit 2 ... relay 3, cooling inputs 7 MSB R, RAM input states, binary heating / cooling demands. Inputs are physical states regardless of settings in the input settings register. bit 0 ... DI1 bit 1 ... DI2 bit 2 ... heating demand (PID output heat > 5%) bit 3 ... cooling demand (PID output cool > 5%) PID output 8 LSB R, RAM heating controller output in %, range 0 .. 100% HEAT PID output 8 MSB R, RAM cooling controller output in %, range 0 .. 100% COOL PID fan stage 9 LSB R, RAM fan speed displayed on the LCD 0 ... off 1 ... stage 1 2 ... stage 2 3 ... stage 3 PID fan speed 9 MSB R, RAM fan speed in %, range 0 .. 100% manual control 10 LSB R, W RAM manual output control; if a bit is set to 1, the output goes to state defined below (see manual heat output); if set to 0, PID output values apply manual fan stage manual heat output manual hecoolat output set temp correction 10 MSB R, W RAM manual fan stage setting (only if the corresponding bit in the manual control register is set) 11 LSB R, W RAM manual heat output setting (only if the corresponding bit in the manual control register is set) 11 MSB R, W RAM manual cool output setting (only if the corresponding bit in the 12 LSB 12 MSB manual control register is set) R, W RAM setpoint correction set by user; resets at each operation mode change bit 0 ... fan bit 1 ... heat output bit 2 ... cool output bit 3 to 4 ... reserved bit 5 ... change-over (1... C/O active) 0 ... off 1 ... stage 1 2 ... stage 2 3 ... stage 3 in %, range 0 .. 100% in %, range 0 .. 100% recalculate: temperature = read value / 100 actual temp set point HEAT 13 LSB 13 MSB 3.5°C reads 350 (limits are set in the min and max rel. temp correction registers) R, RAM actual heating setpoint incl. setpoint correction (reg. 12) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex 80
MODBUS UC220 Dynamic room controller V2 actual temp set point COOL 14 LSB 14 MSB R, RAM actual cooling setpoint incl. setpoint correction (reg. 12) recalculate: temperature = read value / 100 set day/ comfort heating temp 15 LSB 15 MSB R,W EEPROM day/comfort mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set night/ precomfort heating temp 16 LSB 16 MSB R,W EEPROM (default = 21°C, 0x0834) night/standby mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set depression/ economy heating temp 17 LSB 17 MSB R,W EEPROM (default = 19°C, 0x076C) off mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set day/ comfort cooling temp 18 LSB 18 MSB R,W EEPROM (default = 12°C, 0x04B0) day/comfort mode cooling temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set night/ precomfort cooling temp 19 LSB 19 MSB R,W EEPROM (default = 24°C, 0x0960) night/standby mode cooling temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set depression/ economy cooling temp 20 LSB 20 MSB R, W EEPROM (default = 26°C, 0x0A28) off mode cooling temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 (default = 35°C, 0x0DAC) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex 81
- Page 29 and 30: MODBUS UC100 Room controller V3 pre
- Page 31 and 32: MODBUS UC100 Room controller V3 Rea
- Page 33 and 34: MODBUS UC200 Room controller V3 5 M
- Page 35 and 36: MODBUS UC200 Room controller V3 act
- Page 37 and 38: MODBUS UC200 Room controller V3 max
- Page 39 and 40: MODBUS UC200 Room controller V3 pro
- Page 41 and 42: MODBUS UC300 Room floor heating con
- Page 43 and 44: MODBUS UC300 Room floor heating con
- Page 45 and 46: MODBUS UC300 Room floor heating con
- Page 47 and 48: MODBUS UC300 Room floor heating con
- Page 49 and 50: MODBUS UC300 Room floor heating con
- Page 51 and 52: MODBUS FC010 Fancoil controller V3
- Page 53 and 54: MODBUS FC010 Fancoil controller V3
- Page 55 and 56: MODBUS FC010 Fancoil controller V3
- Page 57 and 58: MODBUS FC010 Fancoil controller V3
- Page 59 and 60: MODBUS FC010 Fancoil controller V3
- Page 61 and 62: MODBUS FC020 Fancoil controller V2
- Page 63 and 64: MODBUS FC020 Fancoil controller V2
- Page 65 and 66: MODBUS FC020 Fancoil controller V2
- Page 67 and 68: MODBUS FC020 Fancoil controller V2
- Page 69 and 70: MODBUS FC020 Fancoil controller V2
- Page 71 and 72: MODBUS UC210 Dynamic radiator contr
- Page 73 and 74: MODBUS UC210 Dynamic radiator contr
- Page 75 and 76: MODBUS UC210 Dynamic radiator contr
- Page 77 and 78: MODBUS UC210 Dynamic radiator contr
- Page 79: MODBUS UC220 Dynamic room controlle
- Page 83 and 84: MODBUS UC220 Dynamic room controlle
- Page 85 and 86: MODBUS UC220 Dynamic room controlle
- Page 87 and 88: MODBUS UC220 Dynamic room controlle
- Page 89 and 90: MODBUS US100 Heating controller wit
- Page 91 and 92: MODBUS US100 Heating controller wit
- Page 93 and 94: MODBUS US100 Heating controller wit
- Page 95 and 96: MODBUS US100 Heating controller wit
MODBUS UC220 Dynamic room controller V2<br />
actual temp set<br />
point COOL<br />
14 LSB<br />
14 MSB<br />
R, RAM actual cooling setpoint incl.<br />
setpoint correction (reg. 12)<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set day/ comfort<br />
heating temp<br />
15 LSB<br />
15 MSB<br />
R,W<br />
EEPROM<br />
day/comfort mode heating<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set night/ precomfort<br />
heating<br />
temp<br />
16 LSB<br />
16 MSB<br />
R,W<br />
EEPROM<br />
(default = 21°C, 0x0834)<br />
night/st<strong>and</strong>by mode heating<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set depression/<br />
economy heating<br />
temp<br />
17 LSB<br />
17 MSB<br />
R,W<br />
EEPROM<br />
(default = 19°C, 0x076C)<br />
off mode heating temperature<br />
setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set day/ comfort<br />
cooling temp<br />
18 LSB<br />
18 MSB<br />
R,W<br />
EEPROM<br />
(default = 12°C, 0x04B0)<br />
day/comfort mode cooling<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set night/ precomfort<br />
cooling<br />
temp<br />
19 LSB<br />
19 MSB<br />
R,W<br />
EEPROM<br />
(default = 24°C, 0x0960)<br />
night/st<strong>and</strong>by mode cooling<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set depression/<br />
economy cooling<br />
temp<br />
20 LSB<br />
20 MSB<br />
R, W<br />
EEPROM<br />
(default = 26°C, 0x0A28)<br />
off mode cooling temperature<br />
setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
(default = 35°C, 0x0DAC)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
81