MODBUS FC020 Fancoil controller V2 baud rate 4 MSB R,W EEPROM serial port settings 5 LSB R,W EEPROM 5 MSB reserved communication speed 10dec … 1 200 bps 11dec … 2 400 bps 12dec … 4 800 bps 13dec … 9 600 bps (default) 14dec … 19 200 bps 15dec … 38 400 bps 16dec … 57 600 bps 17dec … 115 200 bps serial line parameter settings (default = no parity, 1 stop bit) 6 LSB reserved 6 MSB relay 7 LSB R, RAM output relay status (DO1-DO7), outputs DO4 and DO5 are not controlled by any internal algorithm in this firmware version inputs 7 MSB R, RAM digital input status and heat/cool demands; DIx are physical values and are not influenced by the inputs settings register settings PID output HEAT 8 LSB R, RAM heating controller output (or cooling output at change-over active) 8 MSB R, RAM cooling controller output PID output COOL (also at change-over active) PID fan speed 9 LSB R, RAM fan demand from the PID controller reserved 9 MSB manual control 10 LSB R, W RAM bits 0..2: manual output control; if a bit is set to 1, the output goes to state defined below (see manual fan speed, manual heat output, manual cool output); if set to 0, PID output values apply bits 3..4: always controlled through this register bit 5: change-over command over bus; active only if hardware C/O disabled, see input settings !!! the change will be effective after restart only (however the register will be set immediately) bit 0-1 ... parity (00 – no parity, 01 – even, 10 – odd) bit 2 ... stop bits (0 – one, 1 - two) !!! the change will be effective after restart only (however the register will be set immediately) bit 0 ... DO1, fan st. 1 bit 1 ... DO2, fan st. 2 bit 2 ... DO3, fan st. 3 bit 3 ... DO4, bit 4 ... DO5, bit 5 ... DO6, heating bit 6 ... DO7, cooling bit 0 ... DI1, presence bit 1 ... DI2, window contact bit 2 ... DI3, change-over bit 3 ... DI4, party mode bit 4 ... heating demand (PID output HEAT > 5%) bit 5 ... cooling demand (PID output COOL > 5%) in %, range 0 .. 100% in %, range 0 .. 100% 0 ... off 1 ... Stage 1 2 ... Stage 2 3 ... Stage 3 bit 0 ... fan bit 1 ... heat output bit 2 ... cool output bit 3 ... DO4 bit 4 ... DO5 bit 5 ... SW change-over command 62
MODBUS FC020 Fancoil controller V2 manual fan speed manual heat output manual cool output set temp correction 10 MSB R, W RAM manual fan speed setting (only if the corresponding bit in the manual control register is set) 11 LSB R, W RAM manual heat output setting (only if the corresponding bit in the manual control register is set) 11 MSB R, W RAM manual cool output setting (only if the corresponding bit in the 12 LSB 12 MSB manual control register is set) R, RAM setpoint correction set by user; resets at each operation mode change 0 ... off 1 ... Stage 1 2 ... Stage 2 3 ... Stage 3 in %, range 0 .. 100% in %, range 0 .. 100% recalculate: temperature = read value / 100 actual temp set point HEAT 13 LSB 13 MSB 3.5°C reads 350 (limits see pot_correction) R, RAM actual heating setpoint incl. setpoint correction (reg. 12) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 actual temp set point COOL 14 LSB 14 MSB R, RAM actual cooling setpoint incl. setpoint correction (reg. 12) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set day/ comfort heating temp 15 LSB 15 MSB R,W EEPROM day/comfort mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set night/ precomfort heating temp 16 LSB 16 MSB R,W EEPROM (default = 21°C, 0x0834) night/standby mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set depression/ economy heating temp 17 LSB 17 MSB R,W EEPROM (default = 19°C, 0x076C) off mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 (default = 12°C, 0x04B0) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex 63
- Page 11 and 12: MODBUS UI01x User interface V3 max
- Page 13 and 14: MODBUS UI01x User interface V3 dec
- Page 15 and 16: MODBUS UI01x User interface V3 allo
- Page 17 and 18: MODBUS UI01x User interface V3 disp
- Page 19 and 20: MODBUS UI01x User interface V3 prog
- Page 21 and 22: MODBUS UI01x User interface V3 actu
- Page 23 and 24: MODBUS UC100 Room controller V3 UC1
- Page 25 and 26: MODBUS UC100 Room controller V3 set
- Page 27 and 28: MODBUS UC100 Room controller V3 P b
- Page 29 and 30: MODBUS UC100 Room controller V3 pre
- Page 31 and 32: MODBUS UC100 Room controller V3 Rea
- Page 33 and 34: MODBUS UC200 Room controller V3 5 M
- Page 35 and 36: MODBUS UC200 Room controller V3 act
- Page 37 and 38: MODBUS UC200 Room controller V3 max
- Page 39 and 40: MODBUS UC200 Room controller V3 pro
- Page 41 and 42: MODBUS UC300 Room floor heating con
- Page 43 and 44: MODBUS UC300 Room floor heating con
- Page 45 and 46: MODBUS UC300 Room floor heating con
- Page 47 and 48: MODBUS UC300 Room floor heating con
- Page 49 and 50: MODBUS UC300 Room floor heating con
- Page 51 and 52: MODBUS FC010 Fancoil controller V3
- Page 53 and 54: MODBUS FC010 Fancoil controller V3
- Page 55 and 56: MODBUS FC010 Fancoil controller V3
- Page 57 and 58: MODBUS FC010 Fancoil controller V3
- Page 59 and 60: MODBUS FC010 Fancoil controller V3
- Page 61: MODBUS FC020 Fancoil controller V2
- Page 65 and 66: MODBUS FC020 Fancoil controller V2
- Page 67 and 68: MODBUS FC020 Fancoil controller V2
- Page 69 and 70: MODBUS FC020 Fancoil controller V2
- Page 71 and 72: MODBUS UC210 Dynamic radiator contr
- Page 73 and 74: MODBUS UC210 Dynamic radiator contr
- Page 75 and 76: MODBUS UC210 Dynamic radiator contr
- Page 77 and 78: MODBUS UC210 Dynamic radiator contr
- Page 79 and 80: MODBUS UC220 Dynamic room controlle
- Page 81 and 82: MODBUS UC220 Dynamic room controlle
- Page 83 and 84: MODBUS UC220 Dynamic room controlle
- Page 85 and 86: MODBUS UC220 Dynamic room controlle
- Page 87 and 88: MODBUS UC220 Dynamic room controlle
- Page 89 and 90: MODBUS US100 Heating controller wit
- Page 91 and 92: MODBUS US100 Heating controller wit
- Page 93 and 94: MODBUS US100 Heating controller wit
- Page 95 and 96: MODBUS US100 Heating controller wit
MODBUS FC020 Fancoil controller V2<br />
manual fan<br />
speed<br />
manual heat<br />
output<br />
manual cool<br />
output<br />
set temp<br />
correction<br />
10 MSB R, W RAM manual fan speed setting (only if<br />
the corresponding bit in the<br />
manual control register is set)<br />
11 LSB R, W RAM manual heat output setting (only if<br />
the corresponding bit in the<br />
manual control register is set)<br />
11 MSB R, W RAM manual cool output setting (only if<br />
the corresponding bit in the<br />
12 LSB<br />
12 MSB<br />
manual control register is set)<br />
R, RAM setpoint correction set by user;<br />
resets at each operation mode<br />
change<br />
0 ... off<br />
1 ... Stage 1<br />
2 ... Stage 2<br />
3 ... Stage 3<br />
in %, range 0 .. 100%<br />
in %, range 0 .. 100%<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
actual temp set<br />
point HEAT<br />
13 LSB<br />
13 MSB<br />
3.5°C reads 350<br />
(limits see pot_correction)<br />
R, RAM actual heating setpoint incl.<br />
setpoint correction (reg. 12)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
actual temp set<br />
point COOL<br />
14 LSB<br />
14 MSB<br />
R, RAM actual cooling setpoint incl.<br />
setpoint correction (reg. 12)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set day/ comfort<br />
heating temp<br />
15 LSB<br />
15 MSB<br />
R,W<br />
EEPROM<br />
day/comfort mode heating<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set night/ precomfort<br />
heating<br />
temp<br />
16 LSB<br />
16 MSB<br />
R,W<br />
EEPROM<br />
(default = 21°C, 0x0834)<br />
night/st<strong>and</strong>by mode heating<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set depression/<br />
economy heating<br />
temp<br />
17 LSB<br />
17 MSB<br />
R,W<br />
EEPROM<br />
(default = 19°C, 0x076C)<br />
off mode heating temperature<br />
setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
(default = 12°C, 0x04B0)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
63