MODBUS FC010 Fancoil controller V3 serial port settings 5 LSB R,W EEPROM 5 MSB reserved serial line parameter settings (default = no parity, 1 stop bit) bit 0-1 ... parity (00 – no parity, 01 – even, 10 – odd) bit 2 ... stop bits (0 – one, 1 - two) !!! the change will be effective after restart only (however the register will be set immediately) 6 LSB reserved 6 MSB relay 7 LSB R, RAM output relay status (DO1-DO5) bit 0 ... relay 1, heating bit 1 ... relay 2, cooling bit 2 ... relay 3, fan st. 1 bit 3 ... relay 4, fan st. 2 bit 4 ... relay 5, fan st. 3 inputs 7 MSB R, RAM digital input status (DI1 ... presence, DI2 ... window contact) and heat/cool demands; DI1 and DI2 are physical values and are not influenced by the inputs settings register settings bit 0 ... input DI1 bit 1 ... input DI2 bit 2 ... heating demand (PID output HEAT > 5%) bit 3 ... cooling demand (PID output COOL > 5%) PID output 8 LSB R, RAM heating controller output in %, range 0 .. 100% HEAT PID output 8 MSB R, RAM cooling controller output in %, range 0 .. 100% COOL PID fan speed 9 LSB R, RAM fan demand from the PID controller UC comm. state 9 MSB R, RAM communication status of the room unit UC 010 (if comm fails for 60 secs, all controller outputs go to off (except for those controlled manually, see register manual control) manual control 10 LSB R, W RAM manual output control; if a bit is set to 1, the output goes to state defined below (see manual fan speed, manual heat output, manual cool output); if set to 0, PID output values apply manual fan speed manual heat output manual cool output 10 MSB R, W RAM manual fan speed setting (only if the corresponding bit in the manual control register is set) 11 LSB R, W RAM manual heat output setting (only if the corresponding bit in the manual control register is set) 11 MSB R, W RAM manual cool output setting (only if the corresponding bit in the manual control register is set) 0 ... off 1 ... Stage 1 2 ... Stage 2 3 ... Stage 3 0 ... communication OK 1 ... timeout 2 ... MB exception 3 ... MB error bit 0 ... fan bit 1 ... heat output bit 2 ... cool output 0 ... off 1 ... Stage 1 2 ... Stage 2 3 ... Stage 3 in %, range 0 .. 100% in %, range 0 .. 100% 52
MODBUS FC010 Fancoil controller V3 set temp correction 12 LSB 12 MSB R, W RAM setpoint correction set by user; resets at each operation mode change recalculate: temperature = read value / 100 actual temp set point HEAT 13 LSB 13 MSB 3.5°C reads 350 (limits are set in the min and max rel. temp correction registers) R, RAM actual heating setpoint incl. setpoint correction (reg. 12) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 actual temp set point COOL 14 LSB 14 MSB R, RAM actual cooling setpoint incl. setpoint correction (reg. 12) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set day/ comfort heating temp 15 LSB 15 MSB R,W EEPROM day/comfort mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set night/ precomfort heating temp 16 LSB 16 MSB R,W EEPROM (default = 21°C, 0x0834) night/standby mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set depression/ economy heating temp 17 LSB 17 MSB R,W EEPROM (default = 19°C, 0x076C) off mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set day/ comfort cooling temp 18 LSB 18 MSB R,W EEPROM (default = 12°C, 0x04B0) day/comfort mode cooling temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 (default = 24°C, 0x0960) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex 53
- Page 1 and 2: Room units and controllers Communic
- Page 3 and 4: MODBUS General V3 General • All r
- Page 5 and 6: MODBUS UI01x User interface V3 stat
- Page 7 and 8: MODBUS UI01x User interface V3 set
- Page 9 and 10: MODBUS UI01x User interface V3 sett
- Page 11 and 12: MODBUS UI01x User interface V3 max
- Page 13 and 14: MODBUS UI01x User interface V3 dec
- Page 15 and 16: MODBUS UI01x User interface V3 allo
- Page 17 and 18: MODBUS UI01x User interface V3 disp
- Page 19 and 20: MODBUS UI01x User interface V3 prog
- Page 21 and 22: MODBUS UI01x User interface V3 actu
- Page 23 and 24: MODBUS UC100 Room controller V3 UC1
- Page 25 and 26: MODBUS UC100 Room controller V3 set
- Page 27 and 28: MODBUS UC100 Room controller V3 P b
- Page 29 and 30: MODBUS UC100 Room controller V3 pre
- Page 31 and 32: MODBUS UC100 Room controller V3 Rea
- Page 33 and 34: MODBUS UC200 Room controller V3 5 M
- Page 35 and 36: MODBUS UC200 Room controller V3 act
- Page 37 and 38: MODBUS UC200 Room controller V3 max
- Page 39 and 40: MODBUS UC200 Room controller V3 pro
- Page 41 and 42: MODBUS UC300 Room floor heating con
- Page 43 and 44: MODBUS UC300 Room floor heating con
- Page 45 and 46: MODBUS UC300 Room floor heating con
- Page 47 and 48: MODBUS UC300 Room floor heating con
- Page 49 and 50: MODBUS UC300 Room floor heating con
- Page 51: MODBUS FC010 Fancoil controller V3
- Page 55 and 56: MODBUS FC010 Fancoil controller V3
- Page 57 and 58: MODBUS FC010 Fancoil controller V3
- Page 59 and 60: MODBUS FC010 Fancoil controller V3
- Page 61 and 62: MODBUS FC020 Fancoil controller V2
- Page 63 and 64: MODBUS FC020 Fancoil controller V2
- Page 65 and 66: MODBUS FC020 Fancoil controller V2
- Page 67 and 68: MODBUS FC020 Fancoil controller V2
- Page 69 and 70: MODBUS FC020 Fancoil controller V2
- Page 71 and 72: MODBUS UC210 Dynamic radiator contr
- Page 73 and 74: MODBUS UC210 Dynamic radiator contr
- Page 75 and 76: MODBUS UC210 Dynamic radiator contr
- Page 77 and 78: MODBUS UC210 Dynamic radiator contr
- Page 79 and 80: MODBUS UC220 Dynamic room controlle
- Page 81 and 82: MODBUS UC220 Dynamic room controlle
- Page 83 and 84: MODBUS UC220 Dynamic room controlle
- Page 85 and 86: MODBUS UC220 Dynamic room controlle
- Page 87 and 88: MODBUS UC220 Dynamic room controlle
- Page 89 and 90: MODBUS US100 Heating controller wit
- Page 91 and 92: MODBUS US100 Heating controller wit
- Page 93 and 94: MODBUS US100 Heating controller wit
- Page 95 and 96: MODBUS US100 Heating controller wit
MODBUS FC010 Fancoil controller V3<br />
set temp<br />
correction<br />
12 LSB<br />
12 MSB<br />
R, W RAM setpoint correction set by user;<br />
resets at each operation mode<br />
change<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
actual temp set<br />
point HEAT<br />
13 LSB<br />
13 MSB<br />
3.5°C reads 350<br />
(limits are set in the min <strong>and</strong> max<br />
rel. temp correction registers)<br />
R, RAM actual heating setpoint incl.<br />
setpoint correction (reg. 12)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
actual temp set<br />
point COOL<br />
14 LSB<br />
14 MSB<br />
R, RAM actual cooling setpoint incl.<br />
setpoint correction (reg. 12)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set day/ comfort<br />
heating temp<br />
15 LSB<br />
15 MSB<br />
R,W<br />
EEPROM<br />
day/comfort mode heating<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set night/ precomfort<br />
heating<br />
temp<br />
16 LSB<br />
16 MSB<br />
R,W<br />
EEPROM<br />
(default = 21°C, 0x0834)<br />
night/st<strong>and</strong>by mode heating<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set depression/<br />
economy heating<br />
temp<br />
17 LSB<br />
17 MSB<br />
R,W<br />
EEPROM<br />
(default = 19°C, 0x076C)<br />
off mode heating temperature<br />
setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set day/ comfort<br />
cooling temp<br />
18 LSB<br />
18 MSB<br />
R,W<br />
EEPROM<br />
(default = 12°C, 0x04B0)<br />
day/comfort mode cooling<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
(default = 24°C, 0x0960)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
53