31.03.2014 Views

Room units and controllers - Domat International

Room units and controllers - Domat International

Room units and controllers - Domat International

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

MODBUS UC300 <strong>Room</strong> floor heating controller V3<br />

set day/ comfort<br />

heating temp<br />

15 LSB<br />

15 MSB<br />

R,W<br />

EEPROM<br />

day/comfort mode heating<br />

temperature setpoint<br />

set by user<br />

recalculate:<br />

temperature =<br />

read value / 100<br />

set night/ precomfort<br />

heating<br />

temp<br />

16 LSB<br />

16 MSB<br />

R,W<br />

EEPROM<br />

(default = 21°C, 0x0834)<br />

night/st<strong>and</strong>by mode heating<br />

temperature setpoint<br />

set by user<br />

0 … 0<br />

199.99 … 19999<br />

-0.01 … 0FFFFhex<br />

-199.99 … 0B1E1hex<br />

recalculate:<br />

temperature =<br />

read value / 100<br />

set depression/<br />

economy heating<br />

temp<br />

17 LSB<br />

17 MSB<br />

R,W<br />

EEPROM<br />

(default = 19°C, 0x076C)<br />

off mode heating temperature<br />

setpoint<br />

set by user<br />

0 … 0<br />

199.99 … 19999<br />

-0.01 … 0FFFFhex<br />

-199.99 … 0B1E1hex<br />

recalculate:<br />

temperature =<br />

read value / 100<br />

18 LSB<br />

18 MSB<br />

(default = 12°C, 0x04B0)<br />

reserved<br />

0 … 0<br />

199.99 … 19999<br />

-0.01 … 0FFFFhex<br />

-199.99 … 0B1E1hex<br />

19 LSB<br />

19 MSB<br />

reserved<br />

20 LSB<br />

20 MSB<br />

reserved<br />

actual temp<br />

21 LSB<br />

21 MSB<br />

R, RAM actual temperature measured by<br />

the internal sensor incl. correction<br />

(see corr temp)<br />

recalculate:<br />

temperature =<br />

read value / 100<br />

0 … 0<br />

199.99 … 19999<br />

-0.01 … 0FFFFhex<br />

-199.99 … 0B1E1hex<br />

actual external<br />

(floor) temp<br />

22 LSB<br />

22 MSB<br />

R, RAM actual floor temperature measured<br />

by the external Pt1000 sensor<br />

inclusive correction (see external<br />

temp sensor corr)<br />

recalculate:<br />

temperature =<br />

read value / 100<br />

0 … 0<br />

199.99 … 19999<br />

-0.01 … 0FFFFhex<br />

-199.99 … 0B1E1hex<br />

43