Room units and controllers - Domat International
Room units and controllers - Domat International Room units and controllers - Domat International
MODBUS UC200 Room controller V3 set day/ comfort heating temp 15 LSB 15 MSB R,W EEPROM day/comfort mode heating temperature setpoint set by user recalculate: temperature = read value / 100 set night/ precomfort heating temp 16 LSB 16 MSB R,W EEPROM (default = 21°C, 0x0834) night/standby mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set depression/ economy heating temp 17 LSB 17 MSB R,W EEPROM (default = 19°C, 0x076C) off mode heating temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set day/ comfort cooling temp 18 LSB 18 MSB R,W EEPROM (default = 12°C, 0x04B0) day/comfort mode cooling temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set night/ precomfort cooling temp 19 LSB 19 MSB R,W EEPROM (default = 24°C, 0x0960) night/standby mode cooling temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 set depression/ economy cooling temp 20 LSB 20 MSB R, W EEPROM (default = 26°C, 0x0A28) off mode cooling temperature setpoint set by user 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 actual temp 21 LSB 21 MSB (default = 35°C, 0x0DAC) R, RAM actual temperature measured by the internal sensor incl. correction (see corr temp) 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex recalculate: temperature = read value / 100 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex 34
MODBUS UC200 Room controller V3 actual outside temp 22 LSB 22 MSB R, W RAM actual outside temperature, may be written to RAM optionally for display recalculate: temperature = read value / 100 0 … 0 199.99 … 19999 -0.01 … 0FFFFhex -199.99 … 0B1E1hex set presence mode 23 LSB 23 MSB 24 LSB 24 MSB R,W EEPROM presence status set by user (displayed symbols depend on the configuration register regulator settings, if set to hotel then comfort, standby, off; if set to residential then day, night, depression, auto, party) (default = comfort/day, 0x0001) reserved bit 0 … comfort (occupied house) or day (sun + occupied house) bit 1 … standby (empty house) or night (moon + occupied house) bit 2 … off (off) or depression (empty house) bit 3 … auto (clock) – only when residential bit 4 … party (sun + drink + clock, after 2h goes to auto) – only when residential bit 5 to 14 ... reserved bit 15 ... write enable (if set to 1 value will be written into register, if in 0 attempt will be ignored) actual control mode 25 LSB R, RAM actual mode used for control, if on manual then the actual control mode is equal to set presence mode, if on auto then according to time schedule (displayed symbols depend on the configuration register regulator settings, if set to hotel then comfort, standby, off; if set to residential then day, night, depression, auto, party) 25 MSB reserved bit 0 … comfort/day bit 1 … standby/night bit 2 … off/depression 35
- Page 1 and 2: Room units and controllers Communic
- Page 3 and 4: MODBUS General V3 General • All r
- Page 5 and 6: MODBUS UI01x User interface V3 stat
- Page 7 and 8: MODBUS UI01x User interface V3 set
- Page 9 and 10: MODBUS UI01x User interface V3 sett
- Page 11 and 12: MODBUS UI01x User interface V3 max
- Page 13 and 14: MODBUS UI01x User interface V3 dec
- Page 15 and 16: MODBUS UI01x User interface V3 allo
- Page 17 and 18: MODBUS UI01x User interface V3 disp
- Page 19 and 20: MODBUS UI01x User interface V3 prog
- Page 21 and 22: MODBUS UI01x User interface V3 actu
- Page 23 and 24: MODBUS UC100 Room controller V3 UC1
- Page 25 and 26: MODBUS UC100 Room controller V3 set
- Page 27 and 28: MODBUS UC100 Room controller V3 P b
- Page 29 and 30: MODBUS UC100 Room controller V3 pre
- Page 31 and 32: MODBUS UC100 Room controller V3 Rea
- Page 33: MODBUS UC200 Room controller V3 5 M
- Page 37 and 38: MODBUS UC200 Room controller V3 max
- Page 39 and 40: MODBUS UC200 Room controller V3 pro
- Page 41 and 42: MODBUS UC300 Room floor heating con
- Page 43 and 44: MODBUS UC300 Room floor heating con
- Page 45 and 46: MODBUS UC300 Room floor heating con
- Page 47 and 48: MODBUS UC300 Room floor heating con
- Page 49 and 50: MODBUS UC300 Room floor heating con
- Page 51 and 52: MODBUS FC010 Fancoil controller V3
- Page 53 and 54: MODBUS FC010 Fancoil controller V3
- Page 55 and 56: MODBUS FC010 Fancoil controller V3
- Page 57 and 58: MODBUS FC010 Fancoil controller V3
- Page 59 and 60: MODBUS FC010 Fancoil controller V3
- Page 61 and 62: MODBUS FC020 Fancoil controller V2
- Page 63 and 64: MODBUS FC020 Fancoil controller V2
- Page 65 and 66: MODBUS FC020 Fancoil controller V2
- Page 67 and 68: MODBUS FC020 Fancoil controller V2
- Page 69 and 70: MODBUS FC020 Fancoil controller V2
- Page 71 and 72: MODBUS UC210 Dynamic radiator contr
- Page 73 and 74: MODBUS UC210 Dynamic radiator contr
- Page 75 and 76: MODBUS UC210 Dynamic radiator contr
- Page 77 and 78: MODBUS UC210 Dynamic radiator contr
- Page 79 and 80: MODBUS UC220 Dynamic room controlle
- Page 81 and 82: MODBUS UC220 Dynamic room controlle
- Page 83 and 84: MODBUS UC220 Dynamic room controlle
MODBUS UC200 <strong>Room</strong> controller V3<br />
set day/ comfort<br />
heating temp<br />
15 LSB<br />
15 MSB<br />
R,W<br />
EEPROM<br />
day/comfort mode heating<br />
temperature setpoint<br />
set by user<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set night/ precomfort<br />
heating<br />
temp<br />
16 LSB<br />
16 MSB<br />
R,W<br />
EEPROM<br />
(default = 21°C, 0x0834)<br />
night/st<strong>and</strong>by mode heating<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set depression/<br />
economy heating<br />
temp<br />
17 LSB<br />
17 MSB<br />
R,W<br />
EEPROM<br />
(default = 19°C, 0x076C)<br />
off mode heating temperature<br />
setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set day/ comfort<br />
cooling temp<br />
18 LSB<br />
18 MSB<br />
R,W<br />
EEPROM<br />
(default = 12°C, 0x04B0)<br />
day/comfort mode cooling<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set night/ precomfort<br />
cooling<br />
temp<br />
19 LSB<br />
19 MSB<br />
R,W<br />
EEPROM<br />
(default = 24°C, 0x0960)<br />
night/st<strong>and</strong>by mode cooling<br />
temperature setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
set depression/<br />
economy cooling<br />
temp<br />
20 LSB<br />
20 MSB<br />
R, W<br />
EEPROM<br />
(default = 26°C, 0x0A28)<br />
off mode cooling temperature<br />
setpoint<br />
set by user<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
actual temp<br />
21 LSB<br />
21 MSB<br />
(default = 35°C, 0x0DAC)<br />
R, RAM actual temperature measured by<br />
the internal sensor incl. correction<br />
(see corr temp)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
34