Room units and controllers - Domat International
Room units and controllers - Domat International
Room units and controllers - Domat International
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
MODBUS UC200 <strong>Room</strong> controller V3<br />
5 MSB reserved<br />
6 LSB<br />
reserved<br />
6 MSB<br />
relay 7 LSB R, RAM output relay status (DO1, DO2) bit 0 ... relay 1, heating<br />
bit 1 ... relay 2, cooling<br />
inputs 7 MSB R, RAM input states, binary heating /<br />
cooling dem<strong>and</strong>s.<br />
DI1 <strong>and</strong> DI2 are physical input<br />
states regardless of the inputs<br />
settings setting.<br />
bit 0 ... DI1<br />
bit 1 ... DI2<br />
bit 2 ... heating dem<strong>and</strong><br />
(PID output heat > 5%)<br />
bit 3 ... cooling dem<strong>and</strong><br />
(PID output cool > 5%)<br />
pid output HEAT 8 LSB R, RAM heating controller output in %, range 0 .. 100%<br />
pid output<br />
COOL<br />
8 MSB R, RAM cooling controller output in %, range 0 .. 100%<br />
9 LSB reserved<br />
9 MSB reserved<br />
manual control 10 LSB R, W RAM manual output control; if a bit is set<br />
to 1, the output goes to state<br />
defined below (see manual heat<br />
output, manual cool output); if<br />
set to 0, PID output values apply<br />
10 MSB R, W RAM reserved<br />
manual heat<br />
output<br />
manual cool<br />
output<br />
set temp<br />
correction<br />
11 LSB R, W RAM manual heat output setting (only if<br />
the corresponding bit in the<br />
manual control register is set)<br />
11 MSB R, W RAM manual cool output setting (only if<br />
the corresponding bit in the<br />
12 LSB<br />
12 MSB<br />
manual control register is set)<br />
R, W RAM setpoint correction set by user;<br />
resets at each operation mode<br />
change<br />
bit 0 ... reserved<br />
bit 1 ... heat output<br />
bit 2 ... cool output<br />
in %, range 0 .. 100%<br />
in %, range 0 .. 100%<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
actual temp set<br />
point HEAT<br />
13 LSB<br />
13 MSB<br />
3.5°C reads 350<br />
(limits are set in the min <strong>and</strong> max<br />
rel. temp correction registers)<br />
R, RAM actual heating setpoint incl.<br />
setpoint correction (reg. 12)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
actual temp set<br />
point COOL<br />
14 LSB<br />
14 MSB<br />
R, RAM actual cooling setpoint incl.<br />
setpoint correction (reg. 12)<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
recalculate:<br />
temperature =<br />
read value / 100<br />
0 … 0<br />
199.99 … 19999<br />
-0.01 … 0FFFFhex<br />
-199.99 … 0B1E1hex<br />
33