MODBUS UC100 Room controller V3 step temp 39 LSB R,W EEPROM step minutes 39 MSB R,W EEPROM show mode 40 LSB 40 MSB 41 LSB 41 MSB R,W EEPROM show time 42 LSB R,W EEPROM edit return time 42 MSB R,W EEPROM quick edit mode number change over period 43 LSB R,W EEPROM 43 MSB R,W EEPROM long push time 44 LSB R,W EEPROM step for user temperature setpoints setting (default = 0.5 °C, 0x32) time step for time schedule setting (default = 5 mins, 0x05) reserved data that roll on the LCD display (default = 1) If only one of the bits is active there is only one value displayed. Otherwise they change periodically after show time. time (in 100 ms) to display each value in show mode (default = 3 s, 0x1E) time (in s) of user inactivity to return from edit mode to show mode (default = 30 s, 0x1E) number of mode which is editable through quick edit menu (short push of the knob) (default = 0x01) time delay when changing from heating to cooling and back (default = 30) time (in 100 ms) evaluated as long push (go to time schedule menu / leave menu) step = read value / 100 1 … 0.01 50 … 0.5 100 … 1 etc. in minutes bit 0 … temperature bit 1 … outside temp. bit 2 … current time (default = temperature, 0x0001) see show mode 0 ... push function inactive 1 ... presence mode 2 ... reserved in mins, 1 to 255 for editing of the time schedule and presence or fan mode super long push time 44 MSB R,W EEPROM (default = 1.5 s, 0x0F) time (in 100 ms) evaluated as superlong push (go to settings menu) for actual time and basic setpoints settings allowed operation modes 45 LSB 45 MSB R,W EEPROM (default = 5 s, 0x32) settings that user is able to perform 0 … disabled 1 … enabled (default = temp corr, RTC time, presence mode, time programme 0x0581) bit 0 … temp corr. bit 1 … heating day temp bit 2 … heating night temp bit 3 … heating depression temp bit 4 … cooling day temp bit 5 … cooling night temp bit 6 … cooling depression temp bit 7 … RTC time bit 8 … presence mode bit 9 … reserved bit 10 … time programme 28
MODBUS UC100 Room controller V3 presence mode edit mask display symbols RTC program Monday Event 1 time 46 LSB 46 MSB 47 LSB 47 MSB 48 LSB 48 MSB 49 LSB 49 MSB 50 LSB 50 MSB 51 LSB 51 MSB 52 LSB 52 MSB 53 LSB 53 MSB 54 LSB 54 MSB R,W EEPROM states in presence mode that user is able to switch between (default = all, 0x001F) reserved bit 0 … day (sun + occupied house) bit 1 … night (moon + occupied house) bit 2 … depression (empty house) bit 3 … auto (clock) bit 4 … party (sun + drink + clock, after 2h goes to auto) R,W RAM displayed symbols bit 0 … spanner bit 1 … boiler bit 2 … alarm bell bit 3 to 14 ... reserved bit 15 ... write enable write enable (if set to 1 value will be written into register, if in 0 attempt will be ignored) R,W EEPROM R,W EEPROM Real time clock (not subject to INIT command) reserved time schedule, Monday, time of event No. 1, in mins since 0:00 (midnight) see table; to write to those registers, write to EEPROM must be enabled in the status LSB register e.g. 121 ... 2h 1min program Monday Event 1 value program Monday Event 2 time 55 LSB 55 MSB 56 LSB 56 MSB R,W EEPROM R,W EEPROM (default = 06:00 h, 0x0168) time schedule, Monday, event No. 1, value (default = 0) time schedule, Monday, time of event No. 2, in mins since 0:00 (midnight) 0 ... day/comfort 1 ... night/standby 2 ... off/depression bit 15 = 1 ... event is disabled e.g. 121 ... 2h 1min program Monday Event 2 value program Monday Event 3 time 57 LSB 57 MSB 58 LSB 58 MSB R,W EEPROM R,W EEPROM (default = 08:00 h) time schedule, Monday, event No. 2, value (default = 1) time schedule, Monday, time of event No. 3, in mins since 0:00 (midnight) 0 ... day/comfort 1 ... night/standby 2 ... off/depression bit 15 = 1 ... event is disabled e.g. 121 ... 2h 1min (default = 14:00 h) 29
- Page 1 and 2: Room units and controllers Communic
- Page 3 and 4: MODBUS General V3 General • All r
- Page 5 and 6: MODBUS UI01x User interface V3 stat
- Page 7 and 8: MODBUS UI01x User interface V3 set
- Page 9 and 10: MODBUS UI01x User interface V3 sett
- Page 11 and 12: MODBUS UI01x User interface V3 max
- Page 13 and 14: MODBUS UI01x User interface V3 dec
- Page 15 and 16: MODBUS UI01x User interface V3 allo
- Page 17 and 18: MODBUS UI01x User interface V3 disp
- Page 19 and 20: MODBUS UI01x User interface V3 prog
- Page 21 and 22: MODBUS UI01x User interface V3 actu
- Page 23 and 24: MODBUS UC100 Room controller V3 UC1
- Page 25 and 26: MODBUS UC100 Room controller V3 set
- Page 27: MODBUS UC100 Room controller V3 P b
- Page 31 and 32: MODBUS UC100 Room controller V3 Rea
- Page 33 and 34: MODBUS UC200 Room controller V3 5 M
- Page 35 and 36: MODBUS UC200 Room controller V3 act
- Page 37 and 38: MODBUS UC200 Room controller V3 max
- Page 39 and 40: MODBUS UC200 Room controller V3 pro
- Page 41 and 42: MODBUS UC300 Room floor heating con
- Page 43 and 44: MODBUS UC300 Room floor heating con
- Page 45 and 46: MODBUS UC300 Room floor heating con
- Page 47 and 48: MODBUS UC300 Room floor heating con
- Page 49 and 50: MODBUS UC300 Room floor heating con
- Page 51 and 52: MODBUS FC010 Fancoil controller V3
- Page 53 and 54: MODBUS FC010 Fancoil controller V3
- Page 55 and 56: MODBUS FC010 Fancoil controller V3
- Page 57 and 58: MODBUS FC010 Fancoil controller V3
- Page 59 and 60: MODBUS FC010 Fancoil controller V3
- Page 61 and 62: MODBUS FC020 Fancoil controller V2
- Page 63 and 64: MODBUS FC020 Fancoil controller V2
- Page 65 and 66: MODBUS FC020 Fancoil controller V2
- Page 67 and 68: MODBUS FC020 Fancoil controller V2
- Page 69 and 70: MODBUS FC020 Fancoil controller V2
- Page 71 and 72: MODBUS UC210 Dynamic radiator contr
- Page 73 and 74: MODBUS UC210 Dynamic radiator contr
- Page 75 and 76: MODBUS UC210 Dynamic radiator contr
- Page 77 and 78: MODBUS UC210 Dynamic radiator contr
MODBUS UC100 <strong>Room</strong> controller V3<br />
step temp 39 LSB R,W<br />
EEPROM<br />
step minutes 39 MSB R,W<br />
EEPROM<br />
show mode<br />
40 LSB<br />
40 MSB<br />
41 LSB<br />
41 MSB<br />
R,W<br />
EEPROM<br />
show time 42 LSB R,W<br />
EEPROM<br />
edit return time 42 MSB R,W<br />
EEPROM<br />
quick edit mode<br />
number<br />
change over<br />
period<br />
43 LSB R,W<br />
EEPROM<br />
43 MSB R,W<br />
EEPROM<br />
long push time 44 LSB R,W<br />
EEPROM<br />
step for user temperature<br />
setpoints setting<br />
(default = 0.5 °C, 0x32)<br />
time step for time schedule setting<br />
(default = 5 mins, 0x05)<br />
reserved<br />
data that roll on the LCD display<br />
(default = 1)<br />
If only one of the bits is active<br />
there is only one value displayed.<br />
Otherwise they change<br />
periodically after show time.<br />
time (in 100 ms) to display each<br />
value in show mode (default = 3 s,<br />
0x1E)<br />
time (in s) of user inactivity to<br />
return from edit mode to show<br />
mode (default = 30 s, 0x1E)<br />
number of mode which is editable<br />
through quick edit menu (short<br />
push of the knob)<br />
(default = 0x01)<br />
time delay when changing from<br />
heating to cooling <strong>and</strong> back<br />
(default = 30)<br />
time (in 100 ms) evaluated as long<br />
push (go to time schedule menu /<br />
leave menu)<br />
step = read value / 100<br />
1 … 0.01<br />
50 … 0.5<br />
100 … 1 etc.<br />
in minutes<br />
bit 0 … temperature<br />
bit 1 … outside temp.<br />
bit 2 … current time<br />
(default = temperature,<br />
0x0001)<br />
see show mode<br />
0 ... push function inactive<br />
1 ... presence mode<br />
2 ... reserved<br />
in mins, 1 to 255<br />
for editing of the time<br />
schedule <strong>and</strong> presence or<br />
fan mode<br />
super long push<br />
time<br />
44 MSB R,W<br />
EEPROM<br />
(default = 1.5 s, 0x0F)<br />
time (in 100 ms) evaluated as<br />
superlong push (go to settings<br />
menu)<br />
for actual time <strong>and</strong> basic<br />
setpoints settings<br />
allowed<br />
operation modes<br />
45 LSB<br />
45 MSB<br />
R,W<br />
EEPROM<br />
(default = 5 s, 0x32)<br />
settings that user is able to<br />
perform<br />
0 … disabled<br />
1 … enabled<br />
(default = temp corr, RTC time,<br />
presence mode, time programme<br />
0x0581)<br />
bit 0 … temp corr.<br />
bit 1 … heating day temp<br />
bit 2 … heating night<br />
temp<br />
bit 3 … heating<br />
depression temp<br />
bit 4 … cooling day temp<br />
bit 5 … cooling night temp<br />
bit 6 … cooling<br />
depression temp<br />
bit 7 … RTC time<br />
bit 8 … presence mode<br />
bit 9 … reserved<br />
bit 10 … time programme<br />
28