<strong>Isolating</strong> <strong>switching</strong> <strong>amplifier</strong><br />

dual-channel<br />

IM1-22EX-R<br />

The dual-channel isolating <strong>switching</strong> <strong>amplifier</strong><br />

IM1-22EX-R is equipped with an intrinsically<br />

safe input circuit.<br />

Sensors according to EN 60947-5-6 (NAMUR)<br />

or potential-free contactors can be connected<br />

to the device.<br />

The output circuits feature 2 relays, each with<br />

NO contact.<br />

Six front panel switches are used to set the<br />

output mode separately for each channel (NO/<br />

NC mode), as well as to enable/disable wirebreak<br />

(WB) and short-circuit (SC) monitoring<br />

separately.<br />

When using mechanical contacts, the wirebreak<br />

and short-circuit monitoring must be<br />

switched off or the contact must be connected<br />

to resistors (II) (see circuit diagram).<br />

The green LED indicates operational readiness.<br />

The <strong>switching</strong> status of the corresponding<br />

output is indicated yellow by the two color<br />

LED. In the event of input circuit errors the<br />

dual color LED changes to red, provided the<br />

input circuit monitoring function is activated.<br />

Thereupon the correspondent output relay is<br />

de-energized.<br />

■<br />

Intrinsically safe input circuits E<strong>Ex</strong> ia<br />

■ For application in zone 2<br />

■<br />

FM, NEPSI<br />

■ SIL 2<br />

■<br />

■<br />

■<br />

■<br />

■<br />

■<br />

■<br />

Application areas [<strong>Ex</strong>ia] IIC/IIB und <strong>Ex</strong><br />

nA nC [nL] IIC/IIB T4<br />

Adjustable output mode (NO/NC)<br />

SIL2<br />

Galvanic isolation of input circuits to<br />

output circuits and supply voltage<br />

Removable terminal blocks<br />

Universal operating voltage (20…<br />

250VAC/ 20…125VDC)<br />

Galvanic isolation of input circuits to<br />

output circuits and supply voltage<br />

Edition • 2011-05-14T19:38:54+02:00<br />

1 / 3 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com


<strong>Isolating</strong> <strong>switching</strong> <strong>amplifier</strong><br />

dual-channel<br />

IM1-22EX-R<br />

Type<br />

IM1-22EX-R<br />

Ident-No. 7541231<br />

Dimensions<br />

Nominal voltage<br />

Operational voltage range:<br />

Frequency<br />

Operational voltage range<br />

Power consumption<br />

Universal voltage supply unit<br />

20…250 VAC<br />

ï 40…ð 70 Hz<br />

20…125 VDC<br />

ð 3 W<br />

NAMUR<br />

No-load voltage<br />

Short-circuit current<br />

Input resistance<br />

Cable resistance<br />

Switch-on threshold:<br />

Switch-off threshold:<br />

Wire breakage threshold<br />

Short-circuit threshold<br />

EN-60947-5-6<br />

8.2 VDC<br />

8.2 mA<br />

1 kò<br />

ð 50 ò<br />

1.55 mA<br />

1.75 mA<br />

ð 0.1 mA<br />

ï 6 mA<br />

Output relay electrical lifetime<br />

Output circuits (digital)<br />

Relay <strong>switching</strong> voltage<br />

Switching current per output<br />

Switching capacity per output<br />

Switching frequency<br />

Contact quality<br />

2 x relay (NO)<br />

ð 250 VAC/120 VDC<br />

ð 2 A<br />

ð 500 VA/60 W<br />

ð 10 Hz<br />

AgNi, 3µ Au<br />

Galvanic isolation<br />

Test voltage<br />

2.5 kV<br />

<strong>Ex</strong> approval acc. to conformity certificate TÜV 04 ATEX 2553<br />

Application area<br />

II (1) GD<br />

Protection type<br />

[E<strong>Ex</strong> ia] IIC<br />

Max.output voltage U o<br />

ð 9.6 V<br />

Max. output current I o<br />

ð 11 mA<br />

Max. output power P o<br />

ð 26 mW<br />

Rated voltage<br />

250 V<br />

Characteristic<br />

linear<br />

<strong>Ex</strong>ternal inductance/capacitance L o /C o E<strong>Ex</strong> ia IIC E<strong>Ex</strong> ia IIB<br />

<strong>Ex</strong> approval acc. to conformity certificate<br />

Application area<br />

Max.output voltage U o<br />

Max. output current I o<br />

Max. output power P o<br />

Lo<br />

[mH]<br />

Co<br />

[µF]<br />

1,0 5,0 10,0 2,0 10,0 20,0<br />

1,1 0,83 0,74 5,2 3,8 3,4<br />

TÜV 06 ATEX 552968 X<br />

II 3 G<br />

ð 9.6 V<br />

ð 11 mA<br />

ð 26 mW<br />

Edition • 2011-05-14T19:38:54+02:00<br />

<strong>Ex</strong>ternal inductance/capacitance L o /C o <strong>Ex</strong> nL IIC <strong>Ex</strong> nLIIB<br />

Lo 1,0 5,0 10,0 1,0 5,0 10,0<br />

[mH]<br />

Co<br />

[µF]<br />

1,9 1,4 1,2 11 7,5 6,6<br />

<strong>Ex</strong> approval acc. to conformity certificate<br />

Protection class for belonging equipment (zone 2)<br />

FM3019329<br />

E<strong>Ex</strong> nA nC [nL] IIC/IIB T4<br />

2 / 3 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com


<strong>Isolating</strong> <strong>switching</strong> <strong>amplifier</strong><br />

dual-channel<br />

IM1-22EX-R<br />

Approval SIL 2<br />

Approval<br />

Indication<br />

Operational readiness<br />

Switching state<br />

Error indication<br />

green<br />

yellow<br />

red<br />

Mechanical Data<br />

Protection class<br />

IP20<br />

Ambient temperature -25…+70 °C<br />

Dimensions<br />

104 x 18 x 110 mm<br />

Weight<br />

144 g<br />

Mounting instruction<br />

Mounting on DIN rail or mounting panel<br />

Housing material<br />

Polycarbonate/ABS<br />

Electrical connection<br />

4 x 3-pole removable terminal blocks, reverse polarity<br />

protected, screw connection<br />

Terminal cross-section<br />

1 x 2.5 mm 2 / 2 x 1.5 mm 2<br />

Edition • 2011-05-14T19:38:54+02:00<br />

3 / 3 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!