<strong>PC</strong> <strong>Control</strong> <strong>645</strong>-<strong>12M</strong> on PROFIBUS<br />
4.9.2.8. Service 9: read DP slave's diagnostic information<br />
By setting bit 7, the PROFIBUS message in operand<br />
PEaxx.yy informs the DP master that the DP slave has sent<br />
diagnostic information.<br />
Service 9 allows the master to read the diagnostic information<br />
and writes it into the data field defined by the parameter<br />
field.<br />
Parameter field<br />
Byte<br />
Parameter<br />
0<br />
B yte 1 Error#<br />
Input<br />
Descriptio n<br />
Service<br />
9 Specifies the service<br />
0 No error<br />
1 Parameter error<br />
7 Internal error<br />
B yte 2 Station#<br />
0...99<br />
Number of DP slave<br />
Byte<br />
3 Length<br />
1...244<br />
Length of diagnostic data field<br />
Byte<br />
4 D iag_Data<br />
? Start of diagnostic data field<br />
Diagnostic data field<br />
The field starts with byte 4 and ends after the length defined<br />
in byte 3. For details of this and other entries please<br />
refer to the technical documentation of the relevant device.<br />
4 - 57